-15-
EVACUATING
Connect a vacuum pump to the service ports on the outdoor unit valves and evacuate the interconnecting pipework and
indoor unit to 1000 microns (1 Torr) or better and allow to be held for a minimum of 15 minutes.
After evacuating the indoor unit and interconnecting pipework, open the outdoor unit valves using a 5mm Allen key. The high
and low side pressures should equalise within a minute.
Run the system for a few minutes to allow it to stabilize.
If a manual HP cutout is fitted, ensure that the reset button is depressed (in the compressor compartment, outdoor unit).
MHPUE
units: if no extra refrigerant is to be added
REMOVE
link
JP6
(in the electrics box, outdoor unit, identified by a white
label), otherwise the unit will always run at full speed
.
ADDING REFRIGERANT
Each outdoor unit is charged with refrigerant, as below:-
MCU(+)90
MCU(+) 100 MCU(+) 130 MCU(+) 165
MHPUE 90
MHPUE 100
MHPUE 130
FACTORY CHARGE (g)
(sufficient for up to 7.5m
runs at UK conditions)
R407C
2060
2520
4170
4540
2260
3380
4470
R22
1960
2400
3970
4320
2330
3490
4610
1.
Ensure the refrigerant being added is the same refrigerant that the system was originally charged with.
2.
Refrigerant should be introduced with the system in the
AIR CONDITIONING MODE
(including heat pumps).
3.
Refrigerant should be charged through the Schrader valve on the indoor unit, or the service port on the suction
service valve on the outdoor unit.
4.
Indoor and outdoor units should be run at maximum fan speed during charging:
Set the indoor unit to operate in cooling mode at maximum speed.
MHPUE
are supplied with link JP6 fitted on the outdoor unit pcba; this is only for charging, overriding alarms
and running the MHPUE fan at maximum speed during the charging process.
(Do not forget to remove it once charging is complete: see 10)
MCU+
outdoor units are fitted with head pressure control; before charging, isolate the unit and transfer the
blue wire on the head pressure control from terminal 4 to terminal 1.
(Do not forget to transfer it back once charging is complete: see 10)
5.
All systems with pipe runs longer than 7.5m (UK or NEMA) require added refrigerant.
As a guide, add:-
1/2" Expansion line add 30 g/m;
5/8" Expansion line add 48 g/m.
6.
Further refrigerant needs to be added if the system is to be run at NEMA conditions (27°C/19°C indoor, 35°C
ambient) :-
MCU(+)90
MCU(+) 100 MCU(+) 130 MCU(+) 165
MHPUE 90
MHPUE 100
MHPUE 130
Extra refrigerant required
for NEMA conditions (g)
R407C
115
145
250
200
180
250
200
R22
110
140
240
190
190
260
210
7.
Run the system for a few minutes to allow it to stabilize.
8.
If a sight glass is fitted, it should be just clear of bubbles (flooded).
9.
Indications of incorrect charge are:-
Undercharged unit:
The top few tubes of the evaporator are dry and there are (possibly) slight signs of
frosting at the inlet to the evaporator coil.
Overcharged unit:
The suction line 'sweats' all the way back to the compressor.
10. MHPUE
units: once refrigerant has been added,
REMOVE
link
JP6
(in the electrics box, outdoor unit, identified by a
white label), otherwise the unit will always run at full speed
.
MCU(+)
units: once refrigerant has been added, transfer the blue wire on the head pressure control back
from terminal 1 to terminal 4.
11. MHPUE
units: a random start delay of up to 1 minute occurs when mains is first applied. A 3 minute delay occurs
between successive compressor operations on all systems incorporating MHPUE units, or MCU(+) units fitted with a
3 minute timer kit.
Summary of Contents for 526 HL Series
Page 13: ... 13 ...
Page 16: ... 16 HL WIRING DIAGRAM HLR WIRING DIAGRAM ...
Page 17: ... 17 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 18: ... 18 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 19: ... 19 MHPUE WIRING DIAGRAMS 1 Phase MHPUE 90 3 Phase MHPUE 90 ...
Page 20: ... 20 3 Phase MHPUE 100 to 130 ...