-29-
LOW PRESSURE HOT WATER COIL KIT
This kit provides LPHW heating for HL (526) and HLR (527) indoor units.
A control valve is not provided in this kit.
Since the coil is upstream of the evaporator, a de-ice thermostat is not necessary on the LPHW coil. It is, however, highly
recommended to fit a de-ice thermostat to the evaporator to protect the LPHW coil.
UNIT SIZE
KIT PART NUMBER
Item
Qty
Description
HL/HLR 380
52600227
1
1
LPHW coil assembly
HL/HLR 460
52600226
2
7
Grommet strip
HL/HLR 540
52600224
Fitting the LPHW coil is best done prior to installing the unit.
1
Remove the unit cabinet and lay the unit on its backpanel.
2
Remove the three No. 10 electrics tray retaining screws and spring the tray free.
3
Remove the four No. 10 evaporator coil retaining screws and lift the coil away complete with sealing plates and the
insulation plate.
4
Remove and discard the blanking plate from the left hand hanger bracket.
5
Remove the tape covering the slots in the right hand hanger bracket and fit the grommet strips in place, (Fig. 1).
6
Position the end of the LPHW coil into these slots and secure the left hand end plate to the left hand hanger bracket,
(Fig. 2).
Fig. 1.
Fig. 2.
7
Replace the evaporator assembly and electrics plate.
8
If a valve is to be fitted, connect to the indoor unit as shown in either Fig. 3, (HL) or Fig. 4, (HLR).
Fig. 3 526 Models
Fig. 4 527 Models.
Summary of Contents for 526 HL Series
Page 13: ... 13 ...
Page 16: ... 16 HL WIRING DIAGRAM HLR WIRING DIAGRAM ...
Page 17: ... 17 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 18: ... 18 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 19: ... 19 MHPUE WIRING DIAGRAMS 1 Phase MHPUE 90 3 Phase MHPUE 90 ...
Page 20: ... 20 3 Phase MHPUE 100 to 130 ...