-4-
PRODUCT SELECTION
Combinations of indoor unit and condensing/heat pump unit can be chosen to give either air conditioning or heat pump
systems.
UNIT COMBINATIONS
Air Conditioning Systems
Heat Pump Systems
HL/HLR
MCU(+)
HL/HLR
MCU(+)
HLR
MHPUE
380
100
380
90
380
90
460
130
460
100
460
100
540
165
540
130
540
130
AIR CONDITIONER PERFORMANCE DATA
(All duties in kW)
UK CONDITIONS
ROOM 21°C/15°C
AMBIENT 27°C/19°C
EUROVENT (NEMA)
ROOM 27°C/19°C
AMB 35°C/24°C
TROPICAL
ROOM 29°C/19°C
AMB 46°C/24°C
MODEL
COMBINATIONLOW
MIN SPEED
MAX SPEED
MAX SPEED EVAP
MAX SPEED EVAP
HL/HLR+ MCU(+)
TO
SHR SENS
TOT
SH
SEN
TOTAL
SHR
SENS
TOTAL
SHR
SENS
380 + 90
6.95 0.75
5.19
7.39
0.83
6.14
7.9
0.83
6.6
7.00
1.00
7.00
380 + 100
7.16 0.74
5.29
7.69
0.82
6.27
8.5
0.80
6.8
7.47
1.00
7.47
460 + 100
8.49 0.71
6.05
9.37
0.82
7.64
10.0
0.82
8.2
8.73
1.00
8.73
460 + 130
10.4 0.68
7.02
11.48 0.75
8.60
12.3
0.78
9.6
10.86
0.93
10.04
540 + 130
11.0 0.69
7.63
12.02 0.79
9.46
12.8
0.83
10.6
11.15
0.92
10.27
540 + 165
11.9 0.68
8.14
13.19 0.76 10.00
13.8
0.80
11.0
12.26
0.95
11.66
For medium speed duties, interpolate between minimum speed and maximum speed duties.
Rating conditions are to BS2852: Part 1: 1982: UK condition C; NEMA condition A; Tropical condition B.
HEAT PUMP PERFORMANCE DATA
a. Cooling,
(kW, max speed outdoor unit fan).
UK CONDITIONS
EUROVENT (NEMA)
ROOM 21°C/15°C
AMBIENT 27°
C/19
°
C
ROOM 27°C/19°C AMBIENT 35°
C/24
°
C
MIN SPEED INDOOR FAN
MAX SPEED INDOOR FAN
MAX SPEED INDOOR FAN
HL/HLR
TOTAL
SHR
SENS
TOTAL
SHR
SENS
TOTAL
SHR
SENS
380
6.95
0.75
5.19
7.39
0.83
6.14
7.9
0.83
6.6
460
8.49
0.71
6.05
9.37
0.82
7.64
10.0
0.82
8.2
540
11.02
0.69
7.63
12.02
0.79
9.46
12.8
0.83
10.6
b. Heating,
(Room 20°C/12°C with outdoor unit fan running at maximum speed).
HEATING OUTPUT AT 7
°
C AMBIENT
HEATING OUTPUT AT -1
°
C AMB
IENT
MAX SPEED INDOOR FAN
MAX SPEED INDOOR FAN
HL/HLR
kW
COP
kW
COP
380
9.1
2.9
7.8
3.0
460
11.6
3.7
10.0
3.5
540
13.2
4.0
10.6
3.4
Summary of Contents for 526 HL Series
Page 13: ... 13 ...
Page 16: ... 16 HL WIRING DIAGRAM HLR WIRING DIAGRAM ...
Page 17: ... 17 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 18: ... 18 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Page 19: ... 19 MHPUE WIRING DIAGRAMS 1 Phase MHPUE 90 3 Phase MHPUE 90 ...
Page 20: ... 20 3 Phase MHPUE 100 to 130 ...