TROUBLESHOOTING MOTOR 

 

To determine if the motor is  in  good  operating condition,  compare measured motor  resistance at the motor 

terminals to the values shown below. 

 

 

HIGH SPEED (1750) MEDIUM SPEED (1650) LOW SPEED (1450)

Applicable 

Air Curtain 

Series

Mars Part # Manufacturer Part #

Brand

Motor Rating

HP

Voltage

Phase

Black Motor Wire  & White 

Motor Wire

-

-

03-001

7190-1682

Fasco

Nema 1

1/6

115

1

11.5

-

-

03-002

7190-1903

Fasco

Nema 1

1/6

115

1

8.4

-

-

03-003

7190-1825

Fasco

Nema 1

1/6

230

1

64

-

-

03-004

7190-1904

Fasco

Nema 1

1/6

230

1

44.6

-

-

Applicable 

Air Curtain 

Series

Mars Part # Manufacturer Part #

Brand

Motor Rating

HP

Voltage

Phase

White Motor Wire (T1) 

Black Motor Wire (T3)

White Motor Wire (T1) 

Black Motor Wire (T5)

White Motor Wire (T1) 

Black Motor Wire (T2)

03-010

34G928X169

Baldor

Washdown (IP54)

1/2

115

1

1.2

-

-

03-010

34G928X169

Baldor

Washdown (IP54)

1/2

208/230

1

4.6

-

-

03-005

7124-1175

Genteq

Nema 1

1/2

115

1

2.6

3.8

5.2

03-006

7124-1560

Genteq

Nema 1

1/2

208/230

1

9.9

15.9

22.5

03-007

48S17T439

Marathon

Nema 1

1/2

277

1

7.7

-

-

03-005

K055PWM1736C13H

Nidec

Nema 1

1/2

115

1

2.1

3.7

5.2

03-005

K055PWM1736C13H

US

Nema 1

1/2

115

1

5.3

3.7

5.4

03-006

US

Nema 1

1/2

208/230

1

8.7

18.2

24.2

Applicable 

Air Curtain 

Series

Mars Part # Manufacturer Part #

Brand

Motor Rating

HP

Voltage

Phase

White Motor Wire (T1) 

Black Motor Wire (T2)

White Motor Wire (T1) 

Black Motor Wire (T3)

-

03-021

35T276R025G1

Baldor

Washdown (IP54)

1

115

1

0.7

-

-

03-015-Baldor

35M316S174

Baldor

Nema 1

1

115

1

0.6

-

-

03-015-Baldor

35M316S174

Baldor

Nema 1

1

208/230

1

2.2

-

-

03-021

35T276R025G1

Baldor

Washdown (IP54)

1

208/230

1

2.8

-

-

03-014

7124-0985

Genteq

Nema 1

1

115

1

1.6

2.4

-

03-015

7124-1096

Genteq

Nema 1

1

208/230

1

6.5

9.2

-

03-015

-

Nidec

Nema 1

1

208/230

1

4.3

6.5

-

03-014

K55BWJZB-2362

US

Nema 1

1

115

1

1

2.1

-

03-015

-

US

Nema 1

1

208/230

1

3.2

6.3

-

Black Motor Wire (L1) 

Red Motor Wire (L2)

Black Motor Wire (L1) 

White Motor Wire (L3)

Red Motor Wire (L2) 

White Motor Wire (L3)

03-008

P55YYDHB-1527

US

Nema 1

1/2

208-230

3

16.1

16.1

16.1

03-008

P55YYDHB-1527

US

Nema 1

1/2

460

3

63.6

63.6

63.6

03-009

48T17T135

Marathon

Nema 1

1/2

575

3

136

136

136

03-017

56T17T5541

Marathon

Nema 1

1

208-230

3

4.3

4.3

4.3

03-017

56T17T5541

Marathon

Nema 1

1

460

3

16.5

16.5

16.5

03-018

56T17T5544

Marathon

Nema 1

1

575

3

26.6

26.6

26.6

03-022

35N127S902

Baldor

Washdown (IP54)

1

208-230

3

5.1

5.1

5.1

03-022

35N127S902

Baldor

Washdown (IP54)

1

460

3

19.8

19.8

19.8

03-026

165716

Century

Nema 1

3

208-230

3

1.5

1.5

1.5

03-026

165716

Century

Nema 1

3

460

3

5.7

5.7

5.7

03-028

35E92Y26

Baldor

Nema 1

3

575

3

9.2

9.2

9.2

03-110

36H110-2211G1

Baldor

Nema 1

1,2,3

208-230

3

3.5

3.5

3.5

03-110

36H110-2211G1

Baldor

Nema 1

1,2,3

460

3

13.5

13.5

13.5

03-055

37F932W828G1

Baldor

Nema 1

5

230

3

0.7

0.7

0.7

03-055

37F932W828G1

Baldor

Nema 1

5

460

3

2.4

2.4

2.4

03-046

37F909X889G1

Baldor

Nema 1

7

230

3

0.6

0.6

0.6

03-046

37F909X889G1

Baldor

Nema 1

7

460

3

1.6

1.6

1.6

03-033

U639A - 215TTFC6027 Marathon

Nema 1

10

208-230

3

0.4

0.4

0.4

03-033

U639A - 215TTFC6027 Marathon

Nema 1

10

460

3

1.2

1.2

1.2

03-074

GT1128A 170118.60

Marathon

Nema 1

25

575

3

0.5

0.5

0.5

BD

HV2, NH2, 

PH12

EP2

WMI

WMH

STD2, N2, 

PH10, QP10

Applicable 

Air Curtain 

Series

Mars Part #

HP

Voltage

Brand

Motor Rating

Manufacturer Part #

Phase

LEAD WIRE OHM READINGS

MOTOR WIRES OR TERMINAL (T) OHM READINGS

Single Phase Motors

MARS MOTOR RESISTANCE READINGS

Three Phase Motors

LPV2, LPN2

STD2, N2, 

PH10, QP10

HV2, NH2, 

PH12

Summary of Contents for PH12 Series

Page 1: ...hout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA PH12 Electric Heated Series Phantom 12 Series Commercial Air Curtain Submittal Package Submitted by Mars Air Systems LLC 14716 S Broadway Gardena CA 90248 P O S Q Company Print Name Signature Date Company Seal or ...

Page 2: ...entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents Page Content 3 4 PH12 Electric Submittals 5 6 Typical Electric Heated Wiring Diagrams 7 Thermostat Submittals 8 9 Accessory Installation Supplement 10 13 Installation Operation and Maintenance 14 15 Heated Products Supplement 16 ...

Page 3: ......

Page 4: ...emand o INS 2S Unit mounted 2 speed switch 460 575V 3PH needs additional 115 230V 1PH power o BMS 300 BMS for monitor and control Note Dry contact provided in panel for monitoring motor and heater 24Vac signal provided from panel for controlling motor and heater Disconnects o 99 122 99 123 Non Fused Disconnect remote mounted 600V 32A 80A respectively 3 Pole IP65 o 99 Fused Disconnect remote mounte...

Page 5: ......

Page 6: ......

Page 7: ...models Low voltage 24V control Fan and Heat Control Switch Remote Wall Mounted by others Do not mount low voltage thermostat greater than 30ft from the air curtain Mounting the low voltage thermostat too far from the air curtain may cause a voltage drop and cause chattering Options and Accessories 2 Stage Line Voltage Thermostat Digital Programmable Low Voltage Thermostat Digital Low Voltage Therm...

Page 8: ...inged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical installation of the combination plunger roller type NEMA 1 door limit switch for all non hinged style doors FIG 2 3 All wiring must be per local and NEC National Electric Code codes 4 Panels or cont...

Page 9: ... 6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installation of units use in conjunction with the threaded holes provided on top of unit Note Angle brackets threaded rods and I Beams are provided by others FIGS 7 8 All optional brackets are not available ...

Page 10: ...e standard with an air intake screen s GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you have any questions contact the manufacturer Only qualified personnel should install this product Installing personnel should have a clear understanding of these instructions and should be aware of general safety precautions Improper installation can result in el...

Page 11: ...an Assembly MFA shipped internally mounted 4 All units are equipped with 4 3 8 threaded inserts on top for overhead installation FIG 2 5 Determine the exact mounting locations to suspend the unit above the ceiling so that the unit is centered and parallel with the door opening Use 4 threaded rods to suspend the enclosure to the ceiling Note When installed in the ceiling above the door the air curt...

Page 12: ...on any metal surface C Verify proper voltage prior to powering the product See product label for reference D Check all field wired components if supplied are wired correctly E Check that the inlet air supply and the discharge air supply are free of obstructions F Check that all air filter s and or air intake grille s are in place and installed properly as originally shipped G Verify voltage to the...

Page 13: ...the outdoor elements Contact factory for special construction and costing Freezer and Cooler Installation Air curtain must be mounted on the warm side for optimal performance Variable Frequency Drive VFD is strongly recommended to control the air curtain air flow velocity at the floor level High humid areas may require de humidifier or additional defrost cycle to minimize condensation and freezing...

Page 14: ... switch with terminals provided The thermostat should be mounted as close to the product s discharge air flow as possible in order to best sense the discharged air temperature around the door opening Connect proper voltage to the product per local and NEC codes Thermal overload protection is built into the heater coil assembly assemblies In the event of an overload condition electrical power will ...

Page 15: ...its Note Low Profile and Wind Stopping units require the removal of the coil to access the motor and or fans All piping should be done by a licensed pipe fitter and in accordance with local codes and regulations Connect the supply and return fittings as required All traps and valves are sized and field installed by others For Standard High Velocity and Extra Power units front intake screen must be...

Page 16: ...ion on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating below normal speed Apply proper voltage per unit requirement see unit label Adjust adjustable motor speed knob if applicable Fan rubbing against housing Free fan from housing Blower wheels clogged with dirt Clean and remove d...

Page 17: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black Motor Wire L1 Red Motor Wire L2 Black Motor Wire L1 White Motor Wire L3 Red Motor Wire L2 White Motor Wire L3 03 008 P55YYDHB 1527 US Nema 1 1 2 208 230 3 16 1 16 1 16 1 03 008 P55YYDHB 1527 US Nema ...

Page 18: ...tomer may be responsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any of the following 1 third party claims against you for damages 2 special incidental or indirect damages or 3 any economic consequential damages including lost profits and savings regard...

Page 19: ...for pedestrian entrances B Air curtains for vehicular entrances 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed steel support members B Section 06 10 00 Rough Carpentry C Section 05 41 00 Structural Metal Studs D Section 07 62 00 Sheet metal flashing E Section 07 92 00 Joint Sealants F Section 08 10 00 Metal Doors and Frames G Section 08 33 00 Overhead Coiling Doors H Section ...

Page 20: ...vices Listed for US and Canada F AHRI 410 2001 Standard for Forced Circulation Air cooling and Air Heating Coils G Electrical components UL CUL listed H AMCA 211 Certified I ELT J NEC National Electric Code K Meets NEC and CEC tested by ETL Certified to conform to UL2021 US and CSA22 2 Canada Standards L UL CUL listed M U S Green Building Council LEED Building Design and Construction BD C Version ...

Page 21: ...acturer s operation and maintenance manual including operation maintenance adjustment and cleaning instructions troubleshooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANCE A Manufacturer Qualifications Minimum ten years documented experience producing the products specified in this Section B Installer Qualifications Minimum five years documented experience installing prod...

Page 22: ...nance 1 Motor Totally enclosed air over TEAO cooled motor with sealed lifetime pre lubricated ball bearings motor starter and thermal overload protection a Wired for single speed operation b Wired for two speed operation c Wired for three speed operation d Provide wash down type motors NEC IP 54 for the locations indicated e Provide explosion proof type motors NEC Class 1 Division 1 Group D for th...

Page 23: ...dipped galvanized steel sheet housing conforming to ASTM A 591 and or ASTM A 653 b Provide type 304 stainless steel housing with brushed finish ASTM A 240 A 240M 4 Air Inlet Grille and or Filters Provide air inlet grille and or filters specified 5 Discharge Provide integral discharge nozzle specified 6 Finish and Color Provide with no VOC corrosion resistant polyurethane powder coated finish for s...

Page 24: ... d Four Motor Fan Units 75 dBA 2 3 COMPONENTS A Electric Heaters Provide complete with motor control panel factory mounted to air curtain housing and thermostat to be field installed 1 Temperature limit controller 2 Thermostat Wall mounted 24 Volt operation with heater on off selection 3 Heating Coils ETL approved as part of unit Meets NEC and CEC tested by ETL Certified to conform to UL2021 US an...

Page 25: ...n right hand side of air curtain housing 2 Mounting Factory mounted on left hand side of air curtain housing 3 Electrical components UL CUL listed 4 Optional Digital Programmable Controller a Remote Mounted High Resolution 5 Color LCD Display with Capacitive Touch technology b Fully programmable controller c Pre set and fully customizable programs d Time delay Passive Adaptive e 24 7 timer f Maint...

Page 26: ...ounted outdoor temperature sensors required F Motor Control Panels For Hot Water and Steam Heated Units Recommended for all three phase units and single phase units with combined motor capacities of more than 1HP whenever a door limit switch is used to automatically start and stop the air curtain Provide motor control panels as follows 1 Mounting Shipped loose to be field mounted 2 Mounting Factor...

Page 27: ...olled by a limit switch 1 Type Combination plunger roller switch for swing and sliding doors a Provide limit switches with NEMA 1 20 amps ratings in locations indicated b Provide limit switches with NEMA 4X 10 amps ratings in locations indicated c Provide limit switches with NEMA 4X 15 amps ratings in locations indicated d Provide limit switches with NEMA 7 10 amps ratings in locations indicated 2...

Page 28: ...services and utilities as specified in Section 22 10 00 and 23 21 00 3 3 FIELD QUALITY CONTROL A Adjust air curtains to function properly B Adjust air foil vanes located within the discharge nozzle as required for prevailing conditions at each opening C Check heated air curtain performance on a calm day by measuring air temperature 6 inches off the floor Optimal reading is halfway between the temp...

Page 29: ...Mars Phantom 12 CSI Spec Revised 2 3 2021 MARS AIR SYSTEMS LLC 23 34 33 11 3 6 SCHEDULES A Refer to Air Curtain Schedule appended to this section END OF SECTION ...

Page 30: ...revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description https marsair com Main website https marsair com document library Submittals for all Mars Air Curtains Accessories Installation and Brochures https www marsair com Content Downloads CSISpecs PH10 C...

Reviews: