Mars Phantom 12-CSI-Spec
Revised 2/3/2021
MARS AIR SYSTEMS, LLC
23 34 33 – 7
C.
Hot Water Heaters: Provide finned tube water coils for field mounting on air intake side
of the air curtain cabinet with opposite end connections.
1.
Meets NEC and CEC tested by ETL Certified to conform to UL1995(US) and
CSA22.2 (Canada) Standards.
2.
Output: Air curtain manufacturer's standard, one-row coils.
3.
Output: Air curtain manufacturer's standard, two-row coils.
4.
Coils: Certified in accordance with AHRI 410.
5.
Connections: Opposite end.
6.
Connections: Same end, right hand.
7.
Connections: Same end, left hand.
8.
Casing: One-piece unpainted galvanized steel, bolted to air curtain housing.
9.
Supply and return fittings on ends of casing.
10.
Thermostat: Wall-mounted, 110-Volt operation, with heater on/off selection.
D.
Motor Control Panels for Unheated Units: Recommended for all three-phase units and
single-phase units with combined motor capacities of more than 1 HP whenever a door
limit switch is used to automatically start and stop the air curtain. Provide motor control
panels as follows:
1.
Mounting: Factory mounted on right hand side of air curtain housing.
2.
Mounting: Factory mounted on left hand side of air curtain housing.
3.
Electrical components UL/CUL listed.
4.
Optional Digital Programmable Controller:
a.
Remote Mounted High Resolution 5” Color LCD Display with
Capacitive Touch technology
b.
Fully programmable controller
c.
Pre-set and fully customizable programs
d.
Time delay (Passive & Adaptive)
e.
24/7 timer
f.
Maintenance schedule alerts
g.
Status display showing date, time, temperature, and air curtain mode
h.
Multi-unit control capability
i.
English (IP) or Metric (SI) display readings
j.
Password protected
k.
Auto Lock display
l.
Emergency shut-off button
m.
Low voltage control signal for door activation
n.
Integrated BMS controls
o.
VFD compatible with 0-10VDC output
p.
Optional BACnet option
q.
Optional adaptive fan speed control based on existing
E.
Motor Control Panels for Electric Heated Units:
Recommended for all units whenever a
door limit switch is used to automatically start and stop the air curtain. Thermostat is
included with optional motor control panel for field installation. Provide motor control
panel as follows
1.
Mounting: Factory mounted on right hand side of air curtain housing.
2.
Mounting: Factory mounted on left hand side of air curtain housing.
3.
Electrical components UL/CUL listed.