RECEIVING AND INSPECTION 

 

Upon receiving the product, check to make sure all items 

are accounted for by referencing the Bill of Lading to 

ensure all items were received. Inspect each carton for 

shipping damage before accepting delivery.  Notify the 

freight carrier if any damage is noticed. The carrier will 

make notification on the delivery receipt acknowledging 

any damage to the product. All damage should be noted 

on all copies of the Bill of Lading which is countersigned 

by the delivering carrier.  A  Carrier  Inspection  Report 

should be filled out by the carrier upon arrival and a report 

given to the Traffic Department. If damaged upon arrival, 

file a claim immediately with the carrier.  Any physical 

damage to the unit after acceptance is not the 

responsibility of Mars Air Systems. 

 

UNPACKING 

 

Verify that all parts, components and accessories, and 

the correct quantities of each have been received. If any 

items are missing, report shortages to Mars Air Systems 

directly to arrange for obtaining the missing items. Again, 

verify quantities received against those on the Bill of 

Lading only, as multiple shipments may be involved. 

 

INSTALLATION 

 

Typical Mounting  –  Wall  or Ceiling  Mounted 

Horizontally Above the Door Opening 

1.  Gently remove all packaging materials, hardware, and 

all other accessories from interior of unit prior to 

operating. Severe unit damage will occur if these items 

are not removed prior to operation. 

2.  The intake screen can be opened by removing the two 

screws on the bottom of the unit. The screen can be 

removed from the unit by pulling the spring-loaded 

piano hinges. (FIG. 1) 

3.  All Phantom series have the Motor  Fan Assembly 

(MFA) shipped internally mounted.  

4.  All units are equipped with (4) 3/8’’ threaded inserts on 

top for overhead installation (FIG. 2) 

5.  Determine the exact mounting locations to suspend the 

unit above the ceiling so that the unit is centered and 

parallel with the door opening. Use (4) threaded rods to 

suspend the enclosure to the ceiling. 

Note: 

When installed in the ceiling above the door, the 

air curtain must be moved 3/8” away from the wall for 

every 1" above the door height.

 

6.  If applicable,  extended wall mounting brackets are 

available for attaching the unit to a wall. 

7.  If applicable, for tandem installation (units longer than 

72”) of products mounted side by side, allow no more 

than 6” between the two units. Note that (4) sets of 

threaded rods are used to suspend each unit to the 

ceiling or center mounting brackets are to be used for 

joining and top mounting tandem units. 

8.  Mount the product such that the discharge is flush with 

the ceiling.  

9.  All wires must be connected internal of the unit and 

some knockouts are provided. However, it may be 

necessary to create your own knockout, as required. 

10. The unit must be wired per NEC and local codes. 

 

FIG 1 

 

FIG. 2 

Electrical Field Wiring 

 

1.  For  electric models, reference  the 

Heated Products 

Supplement

.  

2.  The unit and any optional accessories must be wired 

with the proper voltage to the junction box per the wiring 

diagram. (FIG. 3, unheated products only) 

3.  All 3 phase motors are bi-directional, which means they 

can rotate in either direction. Follow directional arrows 

on the blower wheel housings for proper rotation. If the 

motor is rotating incorrectly, switch two of the 3 phase 

power or motor leads and the motor will rotate the 

opposite direction. Make sure all motors are  

turning in the same and proper direction. (FIG. 3) 

 

 WARNING 

Precaution should be taken in explosive atmospheres. 

Summary of Contents for PH12 Series

Page 1: ...hout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA PH12 Electric Heated Series Phantom 12 Series Commercial Air Curtain Submittal Package Submitted by Mars Air Systems LLC 14716 S Broadway Gardena CA 90248 P O S Q Company Print Name Signature Date Company Seal or ...

Page 2: ...entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents Page Content 3 4 PH12 Electric Submittals 5 6 Typical Electric Heated Wiring Diagrams 7 Thermostat Submittals 8 9 Accessory Installation Supplement 10 13 Installation Operation and Maintenance 14 15 Heated Products Supplement 16 ...

Page 3: ......

Page 4: ...emand o INS 2S Unit mounted 2 speed switch 460 575V 3PH needs additional 115 230V 1PH power o BMS 300 BMS for monitor and control Note Dry contact provided in panel for monitoring motor and heater 24Vac signal provided from panel for controlling motor and heater Disconnects o 99 122 99 123 Non Fused Disconnect remote mounted 600V 32A 80A respectively 3 Pole IP65 o 99 Fused Disconnect remote mounte...

Page 5: ......

Page 6: ......

Page 7: ...models Low voltage 24V control Fan and Heat Control Switch Remote Wall Mounted by others Do not mount low voltage thermostat greater than 30ft from the air curtain Mounting the low voltage thermostat too far from the air curtain may cause a voltage drop and cause chattering Options and Accessories 2 Stage Line Voltage Thermostat Digital Programmable Low Voltage Thermostat Digital Low Voltage Therm...

Page 8: ...inged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical installation of the combination plunger roller type NEMA 1 door limit switch for all non hinged style doors FIG 2 3 All wiring must be per local and NEC National Electric Code codes 4 Panels or cont...

Page 9: ... 6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installation of units use in conjunction with the threaded holes provided on top of unit Note Angle brackets threaded rods and I Beams are provided by others FIGS 7 8 All optional brackets are not available ...

Page 10: ...e standard with an air intake screen s GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you have any questions contact the manufacturer Only qualified personnel should install this product Installing personnel should have a clear understanding of these instructions and should be aware of general safety precautions Improper installation can result in el...

Page 11: ...an Assembly MFA shipped internally mounted 4 All units are equipped with 4 3 8 threaded inserts on top for overhead installation FIG 2 5 Determine the exact mounting locations to suspend the unit above the ceiling so that the unit is centered and parallel with the door opening Use 4 threaded rods to suspend the enclosure to the ceiling Note When installed in the ceiling above the door the air curt...

Page 12: ...on any metal surface C Verify proper voltage prior to powering the product See product label for reference D Check all field wired components if supplied are wired correctly E Check that the inlet air supply and the discharge air supply are free of obstructions F Check that all air filter s and or air intake grille s are in place and installed properly as originally shipped G Verify voltage to the...

Page 13: ...the outdoor elements Contact factory for special construction and costing Freezer and Cooler Installation Air curtain must be mounted on the warm side for optimal performance Variable Frequency Drive VFD is strongly recommended to control the air curtain air flow velocity at the floor level High humid areas may require de humidifier or additional defrost cycle to minimize condensation and freezing...

Page 14: ... switch with terminals provided The thermostat should be mounted as close to the product s discharge air flow as possible in order to best sense the discharged air temperature around the door opening Connect proper voltage to the product per local and NEC codes Thermal overload protection is built into the heater coil assembly assemblies In the event of an overload condition electrical power will ...

Page 15: ...its Note Low Profile and Wind Stopping units require the removal of the coil to access the motor and or fans All piping should be done by a licensed pipe fitter and in accordance with local codes and regulations Connect the supply and return fittings as required All traps and valves are sized and field installed by others For Standard High Velocity and Extra Power units front intake screen must be...

Page 16: ...ion on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating below normal speed Apply proper voltage per unit requirement see unit label Adjust adjustable motor speed knob if applicable Fan rubbing against housing Free fan from housing Blower wheels clogged with dirt Clean and remove d...

Page 17: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black Motor Wire L1 Red Motor Wire L2 Black Motor Wire L1 White Motor Wire L3 Red Motor Wire L2 White Motor Wire L3 03 008 P55YYDHB 1527 US Nema 1 1 2 208 230 3 16 1 16 1 16 1 03 008 P55YYDHB 1527 US Nema ...

Page 18: ...tomer may be responsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any of the following 1 third party claims against you for damages 2 special incidental or indirect damages or 3 any economic consequential damages including lost profits and savings regard...

Page 19: ...for pedestrian entrances B Air curtains for vehicular entrances 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed steel support members B Section 06 10 00 Rough Carpentry C Section 05 41 00 Structural Metal Studs D Section 07 62 00 Sheet metal flashing E Section 07 92 00 Joint Sealants F Section 08 10 00 Metal Doors and Frames G Section 08 33 00 Overhead Coiling Doors H Section ...

Page 20: ...vices Listed for US and Canada F AHRI 410 2001 Standard for Forced Circulation Air cooling and Air Heating Coils G Electrical components UL CUL listed H AMCA 211 Certified I ELT J NEC National Electric Code K Meets NEC and CEC tested by ETL Certified to conform to UL2021 US and CSA22 2 Canada Standards L UL CUL listed M U S Green Building Council LEED Building Design and Construction BD C Version ...

Page 21: ...acturer s operation and maintenance manual including operation maintenance adjustment and cleaning instructions troubleshooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANCE A Manufacturer Qualifications Minimum ten years documented experience producing the products specified in this Section B Installer Qualifications Minimum five years documented experience installing prod...

Page 22: ...nance 1 Motor Totally enclosed air over TEAO cooled motor with sealed lifetime pre lubricated ball bearings motor starter and thermal overload protection a Wired for single speed operation b Wired for two speed operation c Wired for three speed operation d Provide wash down type motors NEC IP 54 for the locations indicated e Provide explosion proof type motors NEC Class 1 Division 1 Group D for th...

Page 23: ...dipped galvanized steel sheet housing conforming to ASTM A 591 and or ASTM A 653 b Provide type 304 stainless steel housing with brushed finish ASTM A 240 A 240M 4 Air Inlet Grille and or Filters Provide air inlet grille and or filters specified 5 Discharge Provide integral discharge nozzle specified 6 Finish and Color Provide with no VOC corrosion resistant polyurethane powder coated finish for s...

Page 24: ... d Four Motor Fan Units 75 dBA 2 3 COMPONENTS A Electric Heaters Provide complete with motor control panel factory mounted to air curtain housing and thermostat to be field installed 1 Temperature limit controller 2 Thermostat Wall mounted 24 Volt operation with heater on off selection 3 Heating Coils ETL approved as part of unit Meets NEC and CEC tested by ETL Certified to conform to UL2021 US an...

Page 25: ...n right hand side of air curtain housing 2 Mounting Factory mounted on left hand side of air curtain housing 3 Electrical components UL CUL listed 4 Optional Digital Programmable Controller a Remote Mounted High Resolution 5 Color LCD Display with Capacitive Touch technology b Fully programmable controller c Pre set and fully customizable programs d Time delay Passive Adaptive e 24 7 timer f Maint...

Page 26: ...ounted outdoor temperature sensors required F Motor Control Panels For Hot Water and Steam Heated Units Recommended for all three phase units and single phase units with combined motor capacities of more than 1HP whenever a door limit switch is used to automatically start and stop the air curtain Provide motor control panels as follows 1 Mounting Shipped loose to be field mounted 2 Mounting Factor...

Page 27: ...olled by a limit switch 1 Type Combination plunger roller switch for swing and sliding doors a Provide limit switches with NEMA 1 20 amps ratings in locations indicated b Provide limit switches with NEMA 4X 10 amps ratings in locations indicated c Provide limit switches with NEMA 4X 15 amps ratings in locations indicated d Provide limit switches with NEMA 7 10 amps ratings in locations indicated 2...

Page 28: ...services and utilities as specified in Section 22 10 00 and 23 21 00 3 3 FIELD QUALITY CONTROL A Adjust air curtains to function properly B Adjust air foil vanes located within the discharge nozzle as required for prevailing conditions at each opening C Check heated air curtain performance on a calm day by measuring air temperature 6 inches off the floor Optimal reading is halfway between the temp...

Page 29: ...Mars Phantom 12 CSI Spec Revised 2 3 2021 MARS AIR SYSTEMS LLC 23 34 33 11 3 6 SCHEDULES A Refer to Air Curtain Schedule appended to this section END OF SECTION ...

Page 30: ...revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description https marsair com Main website https marsair com document library Submittals for all Mars Air Curtains Accessories Installation and Brochures https www marsair com Content Downloads CSISpecs PH10 C...

Reviews: