TROUBLESHOOTING 

PROBLEM 

CAUSE 

SOLUTION 

NO AIR BLOWING 
OUT OF DISCHARGE 
NOZZLE 

- No power being supplied to the unit  

from the electrical power source 

 - Confirm power source / check if in on position 

  

 -Circuit breaker is tripped 

 - Reset circuit breaker 

  

 - Blown fuses on power supply  

 - Replace fuses 

  

 - Motor overload is open or tripped 

 - Allow the motor to cool down; motor has auto reset 

internal overload; if unit is panel equipped, press 
reset button on overload inside panel, or replace 
motor overload if overload remains tripped 

  

 - Motor contactor / relay defective  

(if applicable) 

 - Check voltage to coil; check contacts to see if they 

are pulling in 

  

 - Failed switch 

 - Replace or repair limit switch 

MOTOR IS RUNNING 
BUT FANS ARE NOT 
SPINNING 

 - Loose or broken coupling (belt drive) 

 - Replace or tighten coupling 

  

 - Loose set screws on wheel hubs 

 - Tighten set screws on motor shaft flats 

  

 - Fan spinning inside fan housing 

 - Tighten fan on shaft or replace fan 

  

 - Broken fan hub 

 - Replace fan wheels 

ELECTRICAL 
CONTROLS NOT 
WORKING WHEN 
DOOR IS OPEN 

 - Switch is in off position 

 - Turn unit's switch to the on position 

  

 - Door limit switch is not operating 

 - Repair or replace door limit switch 

UNIT WILL NOT TURN 
OFF 

 - Door limit switch is permanently 

closed or energized 

 - Position the door switch in a manner that turns off the 

unit when the door closes and turns on the unit when 
the door opens.  Only light pressure required. 

LOW AIR FLOW 

 - Discharge air vanes out of 

adjustment 

 - Adjust vanes to proper position                           

(Refer to Start-Up Section in this manual) 

  

 - Obstruction on intake or discharge 

 - Remove obstruction or move air curtain  

  

 - Power leads out of polarity                                       

 - Switch power leads to correct polarity                       

(3 phase models only) 

  

 - Blower motor rotating below normal 

speed 

 - Apply proper voltage per unit requirement             

(see unit label) / Adjust adjustable motor speed knob 
(if applicable) 

  

 - Fan rubbing against housing 

 - Free fan from housing 

  

 - Blower wheels clogged with dirt 

 - Clean and remove dirt from blower wheels 

EXCESSIVE AIR 
VELOCITY AT DOOR 
OPENING 

 - Nozzle out of adjustment and not 

angled far out enough (BD only) 

 - Adjust nozzle angle to outside 

  

 - Air temperature too cold 

 - Add auxiliary heat to overcome wind chill 

  

 - Air stream pushing air outside of the 

building 

 - Adjust discharge angle back into building 

  

 

  

AIR NOT HITTING 
THE FLOOR 

 -  Low air velocity  

 - Adjust vanes to proper position or check installation 

height (Refer to Start-Up Section in this manual) 

  

 -  Obstruction in the direction of air flow 

 - Remove obstruction or move air curtain              

(Move out 3/8" for every 1" up from the door) 

  

 -  Negative building pressure 

 - Provide a make-up air system to relieve negative 

building pressure 

UNEVEN AIR 

 - Shaft rotating inside fan 

 - Replace fan or tighten fan on shaft 

  

 - One motor not functioning 

 - Replace or repair motor 

EXCESSIVE NOISE 
AND OR VIBRATION 

 - Loose or broken coupling (belt drive) 

 - Replace or tighten coupling 

  

 - Loose set screws on wheel hubs 

 - Tighten set screws on motor shaft flats 

  

 - Fan spinning inside fan housing 

 - Tighten fan on shaft or replace fan 

  

 - Broken fan hub 

 - Replace fan wheels 

  

 - Bearing end caps worn 

 - Replace Bearing end caps 

  

 - Damaged blower wheel 

 - Replace Blower Wheel 

  

 - Bearing end caps worn 

 - Replace Bearing end caps 

  

 - Balancing clips missing 

 - Replace Blower Wheel 

Summary of Contents for LoPro 2 Series

Page 1: ...esign without notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA LPV2...

Page 2: ...ithout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Co...

Page 3: ......

Page 4: ...ends without intermediate support up to 72 Models 84 to 144 require intermediate support in the center Adjustable air directional vane with 40 sweep front to back Standard color is Obsidian Black Rust...

Page 5: ......

Page 6: ...in power from circuit breaker at 115v 1MTR Door SW C NC LPV2 Wiring PUR BLK WHT YEL ORG GRN 1MTR Door SW C NC PUR BLK WHT YEL ORG GRN LPV2 LPN2 115V Unheated Wiring diagram with Door switch LPN2 Wirin...

Page 7: ...ower from circuit breaker at 208 230v 1MTR Door SW C NC LPV2 Wiring PUR WHT BLK ORG GRN 1MTR Door SW C NC PUR WHT BLK ORG GRN LPV2 LPN2 208 230V Unheated Wiring diagram with Door switch LPN2 Wiring YE...

Page 8: ...nged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical...

Page 9: ...6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installa...

Page 10: ...stamped air intake screen s The LPV2 models can be configured with an aluminum mesh filter s as an option The LPN2 models 25 and all LPN F models come standard with an aluminum mesh air intake filter...

Page 11: ...l other accessories from interior of unit prior to operating Severe unit damage will occur if these items are not removed prior to operation 2 Lay unit on its top with directional vanes pointing up an...

Page 12: ...uing with the start up it is important to recognize the safety controls furnished with the unit WARNING The following items must all be completed by a qualified installer and checked off when complete...

Page 13: ...nimize condensation and freezing for freezer applications We recommend the air curtain unit to not replace doors but work in conjunction with door opening sequence cycle Contact factory for details CA...

Page 14: ...in this manual Obstruction on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating be...

Page 15: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black...

Page 16: ...sponsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any...

Page 17: ...edestrian entrances B Air curtains for countertop and drive through windows 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed steel support members B Section 06 10 00 Rough Carpentr...

Page 18: ...Alloy Coated Galvannealed by the Hot Dip Process E AHRI 410 2001 Standard for Forced Circulation Air cooling and Air Heating Coils F NSF ANSI 37 Air Curtains for entranceways in food and food service...

Page 19: ...anufacturer s operation and maintenance manual including operation maintenance adjustment and cleaning instructions troubleshooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANC...

Page 20: ...ir over TEAO cooled motor with sealed lifetime pre lubricated ball bearings motor starter and thermal overload protection a LPN2 Units Wired for single speed operation b LPV2 Units Wired for variable...

Page 21: ...lows 1 UV UVC UVV germicidal and odor elimination 4 UV section with disposable UV bulbs 5 Discharge Provide integral discharge nozzle specified 6 Finish and Color Provide with no VOC corrosion resista...

Page 22: ...c Single Motor Fan Units LPV2 48 52 dBA d Single Motor Fan Units LPV2 60 LPV2 72 53 dBA e Two Motor Fan Units LPV2 84 LPV2 96 53 dBA f Two Motor Fan Units LPV2 108 LPV2 144 54 dBA D Insect Control Ai...

Page 23: ...Units LPV2 108 to LPV2 144 54 dBA 2 3 COMPONENTS A Electric Heaters Provide complete with motor control panel factory mounted to air curtain housing and thermostat to be field installed 1 Temperature...

Page 24: ...h to control air curtain s as follows Automatic on off control activates air curtain when door is opened and turns off when door is closed Provide limit switch for direct control one 1 HP or up to two...

Page 25: ...for the opening PART 3 EXECUTION 3 1 EXAMINATION A Verify that required utilities are in correct location and are of correct capacities for specified products B Verify openings to receive air curtain...

Page 26: ...performance on a calm day by measuring air temperature 6 inches off the floor Optimal reading is halfway between the temperature inside and outside the building 3 4 CLEANING A Clean air curtains prom...

Page 27: ...evisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Descriptio...

Reviews: