MAINTENANCE

 

 

Routine maintenance is required to keep this product 
operating at its peak performance and efficiency.  Over 
time, the housing, air intake grille, air intake filter, blower 
wheels and motor(s) will accumulate a build up of dust, 
debris and other residue. It is imperative to keep these 
components clean. Failure to do so will not only lower 
operational efficiency and performance, but also reduce 
the useful life of the product. The time between cleanings 
depends on the application, location, and daily hours of 
use. On average, under normal use conditions, the 
product should require a thorough cleaning once every 
six (6) months.  
 

To clean the product, perform the following: 
 

1.  Verify the product has been disconnected from the 

power source. 

2.  Use a damp cloth and either a warm mild soapy water 

solution or bio-degradable degreaser, to wipe down the 
exterior components of the housing. 

3.  To access the interior of the product, remove the air 

intake grille(s)  and/or air intake filter(s).  This is 
accomplished by removing the screws on the face of the 
air intake grille(s)/filter(s). 

4.  Thoroughly clean the air intake grille(s)/filter(s). 
5.  Thoroughly wipe down the motor, blower wheels and 

blower wheel housings.  Be careful not to spray the 
motor with a water hose.  

6.  The motor(s) require no additional lubrication. They are 

permanently lubricated and feature double sealed ball 
bearings. 

7.  To re-install the product, reverse the procedures above. 
8.  Reconnect the power source to the product. 
9.  If you have any questions regarding the maintenance of 

the product, contact the manufacturer. 

 

SPECIAL APPLICATIONS 
 
Outdoor Installation 
 

For outdoor unit special consideration  may be required 
for enclosure and other components to minimize damage 
caused by exposure to the outdoor elements. Contact 
factory for special construction and costing. 
 

Freezer and Cooler Installation 
 

Air curtain must be mounted on the warm side for optimal 
performance. LPV2 series with variable speed switch is 
strongly recommended to control the air curtain air flow 
velocity at the floor level. 
 
High humid areas may require de-humidifier or additional 
defrost cycle to minimize condensation and freezing for 
freezer applications. We recommend the air curtain unit 
to not replace doors but work in conjunction with door 
opening sequence cycle. Contact factory for details. 

 
 
CAUTION

 

 
The appliance is not to be used by persons (including 
children) with reduced physical, sensory,  or mental 
capabilities, or lack of experience and knowledge, unless 
they have been given supervision or instruction. Children 
are not to play with the appliance. 

 
DISCLAIMER 
 

Mars reserves the right to change specifications and 
product design without notice. Such revisions do not 
entitle the buyer to corresponding changes, 
improvements, additions, or replacements for previously 
purchased equipment.

 

 

I. 

For products with control panels, turn the HOA (Hand-
On-Auto) selector switch to “On” position and open the 
door to energize the product. For products without a 
control panel or an On/Off switch, open the door to 
energize the product. 

J.  If heated products are installed, reference 

Heated 

Products Supplement

K.  For three phase units, verify direction of rotation of 

blower wheels (note direction arrows on the blower 
wheel housing). Correct if needed by changing 
polarity of three phase power. 

L. 

VERY IMPORTANT

  Using a clamp meter, measure 

the amperage to each motor and ensure that they do 
not exceed the amperage listed on the product label. 

M.  If applicable, adjust the air intake grille(s) such that the 

output air stream reaches the floor.  For temperature 
control and environmental separation applications, the 
air stream should reach the floor with sufficient 
strength to create an air seal around the door opening 
without creating turbulent mixing of the inside and 
outside air.  For flying insect control applications, the 
air stream should reach the floor with maximum 
strength.  If after proper installation and adjustment, 
the product appears to be producing too little or too 
much air for the application, contact the manufacturer.  

 

    WARNING 

To reduce the risk of fire, electrical shock, or injury to 
persons, observe the following: 
A.  Maintenance is to be performed only by qualified 

personnel who are familiar with local codes and 
regulations and are experienced with this type of 
product. 

B.  Before servicing or cleaning the product switch power 

off at service panel and lock service panel to prevent 
power from being switched “ON” accidentally.

 

Summary of Contents for LoPro 2 Series

Page 1: ...esign without notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA LPV2...

Page 2: ...ithout notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Co...

Page 3: ......

Page 4: ...ends without intermediate support up to 72 Models 84 to 144 require intermediate support in the center Adjustable air directional vane with 40 sweep front to back Standard color is Obsidian Black Rust...

Page 5: ......

Page 6: ...in power from circuit breaker at 115v 1MTR Door SW C NC LPV2 Wiring PUR BLK WHT YEL ORG GRN 1MTR Door SW C NC PUR BLK WHT YEL ORG GRN LPV2 LPN2 115V Unheated Wiring diagram with Door switch LPN2 Wirin...

Page 7: ...ower from circuit breaker at 208 230v 1MTR Door SW C NC LPV2 Wiring PUR WHT BLK ORG GRN 1MTR Door SW C NC PUR WHT BLK ORG GRN LPV2 LPN2 208 230V Unheated Wiring diagram with Door switch LPN2 Wiring YE...

Page 8: ...nged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical...

Page 9: ...6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installa...

Page 10: ...stamped air intake screen s The LPV2 models can be configured with an aluminum mesh filter s as an option The LPN2 models 25 and all LPN F models come standard with an aluminum mesh air intake filter...

Page 11: ...l other accessories from interior of unit prior to operating Severe unit damage will occur if these items are not removed prior to operation 2 Lay unit on its top with directional vanes pointing up an...

Page 12: ...uing with the start up it is important to recognize the safety controls furnished with the unit WARNING The following items must all be completed by a qualified installer and checked off when complete...

Page 13: ...nimize condensation and freezing for freezer applications We recommend the air curtain unit to not replace doors but work in conjunction with door opening sequence cycle Contact factory for details CA...

Page 14: ...in this manual Obstruction on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating be...

Page 15: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black...

Page 16: ...sponsible for transportation charges associated with replacement of failed part Mars does not warrant uninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any...

Page 17: ...edestrian entrances B Air curtains for countertop and drive through windows 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed steel support members B Section 06 10 00 Rough Carpentr...

Page 18: ...Alloy Coated Galvannealed by the Hot Dip Process E AHRI 410 2001 Standard for Forced Circulation Air cooling and Air Heating Coils F NSF ANSI 37 Air Curtains for entranceways in food and food service...

Page 19: ...anufacturer s operation and maintenance manual including operation maintenance adjustment and cleaning instructions troubleshooting guide parts list and electrical wiring diagrams 1 5 QUALITY ASSURANC...

Page 20: ...ir over TEAO cooled motor with sealed lifetime pre lubricated ball bearings motor starter and thermal overload protection a LPN2 Units Wired for single speed operation b LPV2 Units Wired for variable...

Page 21: ...lows 1 UV UVC UVV germicidal and odor elimination 4 UV section with disposable UV bulbs 5 Discharge Provide integral discharge nozzle specified 6 Finish and Color Provide with no VOC corrosion resista...

Page 22: ...c Single Motor Fan Units LPV2 48 52 dBA d Single Motor Fan Units LPV2 60 LPV2 72 53 dBA e Two Motor Fan Units LPV2 84 LPV2 96 53 dBA f Two Motor Fan Units LPV2 108 LPV2 144 54 dBA D Insect Control Ai...

Page 23: ...Units LPV2 108 to LPV2 144 54 dBA 2 3 COMPONENTS A Electric Heaters Provide complete with motor control panel factory mounted to air curtain housing and thermostat to be field installed 1 Temperature...

Page 24: ...h to control air curtain s as follows Automatic on off control activates air curtain when door is opened and turns off when door is closed Provide limit switch for direct control one 1 HP or up to two...

Page 25: ...for the opening PART 3 EXECUTION 3 1 EXAMINATION A Verify that required utilities are in correct location and are of correct capacities for specified products B Verify openings to receive air curtain...

Page 26: ...performance on a calm day by measuring air temperature 6 inches off the floor Optimal reading is halfway between the temperature inside and outside the building 3 4 CLEANING A Clean air curtains prom...

Page 27: ...evisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Descriptio...

Reviews: