background image

Owner’s Manual -  

CMA12-48SD 

 

  

 

5

GENERAL PRODUCT INFORMATION

UNPACKING AND INSPECTION:

The condensing unit is shipped completely 

assembled and in it’s own package. All goods are 

inspected at the factory and released to the freight 

company in good condition. When received at the 

site, a visual inspection of all packages should be 

made immediately. Any evidence of rough handling 

or apparent damage should be noted on the 

delivery receipt and the material inspected in the 

presence of the carrier’s representative. If 

damage

d

 a claim should be immediately file

d

 with 

the 

freight company.

COOLING OPERATION 

TEMPERATURE LIMITS:

Heat Controller Condensing units are designed 

to operate in cooling at outside temperatures 

between 65°F (18°C) and 109°F (43°C). If 

the condensing unit will be used to cool at 

temperatures below 65°F (18°C), a low ambient 

control must be field installed. Operation below 

65°F (18°C) without low ambient control will void 

the warranty.

INDOOR UNIT USE 

AND SYSTEM EFFICIENCY:

Heat Controller condensing units are designed to 

be compatible with most major brands of domestic 

evaporator coils/air handlers. Imported ductless air 

handlers maybe used but often do not include an 

expansion device. 

Appropriately-sized piston or 

similar metering devices are acceptable for use, 

but bleed-style thermostatic expansion valves 

should be used where specific AHRI-Match ratings 

require, or where oversized coils or other 

application-specific problems may present 

performance issues.

THERMOSTAT AND INDOOR 

FAN TIME DELAY:

All indoor units should include a fan time delay. 

This may be accomplished by using a digital wall 

thermostat or installation of a

 

different fan time 

delay designed to work with your specific 

furnace/

air handler. As follow

s

Most brands of electronic thermostats include a 

fan delay. Properly specified thermostats are the 

responsibility of the installer. Proper temperature 

control and unit operation depends on proper 

thermostat selection and location. Refer to the 

thermostat manufacturer’s installation instructions 

for specified recommendations. Good practice is 

to avoid outside walls, locations where the sun 

may shine directly on the thermostat, and locations 

where the air from supply registers or unit outlets 

blow on the thermostat. Also avoid locations where 

the thermostat could be jarred by a closing door or 

high traffic area.

WARNING:  An in-line filter drier is required 

when the unit is installed.  The filter drier is 

not provided by the factory, therefore a locally 

purchased filter drier must be used to remove 

any particulates or moisture that may be 

present in the system.  Installations without an 

in-line filter drier may void the warranty.

Summary of Contents for COMFORT-AIRE CMA12SD-0

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL Horizontal Side Discharge Condensing Units Models CMA12SD 0 CMA18SD 1 CMA24SD 1 CMA30SD 1 CMA36SD 1 CMA48SD 1 517 787 2100 www marsdelivers com...

Page 2: ...ance TABLE OF CONTENTS Safety Precautions 3 General Operating Instructions 4 General Product Information 5 Outdoor Unit Installation 6 7 Unit Wiring 8 Wiring Diagrams 9 12 Refrigerant Piping 13 Leak T...

Page 3: ...uit Otherwise it will cause lower capacity abnormal high pressure in the refrigeration cycle explosion and injury 1 This equipment must be properly grounded and installed with a ground leakage circuit...

Page 4: ...e frequent starts call your service contractor 4 For energy conservation reasons you may want to set your thermostat at a higher temperature when you are away Do not raise the temperature setting by m...

Page 5: ...ar metering devices are acceptable for use but bleed style thermostatic expansion valves should be used where specific AHRI Match ratings require or where oversized coils or other application specific...

Page 6: ...of onto the unit In climates where snow is a consideration locate the unit away from areas prone to drifting Ensure the location of the unit will not be subject to snow drifts heavy accumulation of sn...

Page 7: ...and outlets are not obstructed See Fig 4 Anchor the outdoor unit with a 10mm 3 8 inch diameter bolt and nut tightly on a concrete or rigid surface See Fig 5 Anchoring is especially recommended in seas...

Page 8: ...compressor and other electrical components and voids the warranty NOTE The supply voltage must be consistent with the rated voltage of the air conditioner not to exceed 10 Ensure the unit is properly...

Page 9: ...48SD 9 Owner s Manual CMA12 48SD 9 OUTDOOR UNIT WIRING CONNECTION continued NOTE Please refer to the installation instructions of the 24V thermostat used in conjunction with this unit for additional...

Page 10: ...Owner s Manual CMA12 48SD 10 Owner s Manual CMA12 48SD 10 OUTDOOR UNIT WIRING CONNECTION continued...

Page 11: ...Owner s Manual CMA12 48SD 11 Owner s Manual CMA12 48SD 11 OUTDOOR UNIT WIRING CONNECTION continued...

Page 12: ...Owner s Manual CMA12 48SD 12 Owner s Manual CMA12 48SD 12 OUTDOOR UNIT WIRING CONNECTION continued...

Page 13: ...s service valves are shipped in the closed position and should not be opened until final connections leak testing and evacuation are completed The recommended procedure for leak test evacuation and r...

Page 14: ...temperature and humidity all have an effect on the system pressures and superheat conditions Charge must be added for the interconnecting tubing Use of piston style metering device is typical Where T...

Page 15: ...original consumer The consumer must retain a receipted bill of sale as proof of warranty period Without this proof the express warranty begins on the date of shipment from the factory REMEDY PROVIDED...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: