background image

Owner’s Manual -  

CMA12-48SD

14

4/2014

INITIAL START-UP & CHECkS

Operation of the unit is automatic and will provide 

cooling depending on the setting of the thermostat.

IMPORTANT!

All panels must be installed, main power turned 

on and the thermostat properly connected before 

operating the unit.

1. System check - set thermostat system switch to

“Off” position and fan switch to “Auto” position.

Turn the power supply breaker on.

2. Set the fan switch to “On,” blower should

operate.

3. Return the fan switch to “Auto”. Blower should

shut off. Set the system switch to “Cool” and

lower thermostat set point to coldest setting.

The compressor, condenser fan, and evaporator

blower should all come on. Cool air will be

supplied after a couple of minutes of run time.

4. Proceed to the “FIELD CHARGING” section of

these instructions.

FIELD CHARGING

Unit performance, efficiency, and life depends, 

to a large extent, on a proper system charge. 

Time spent on getting the charge right at start-up 

will payoff in the long run. Operating conditions 

such as voltage, air flow, evaporator coil size, 

and indoor and outdoor temperature and humidity 

all have an effect on the system pressures and 

superheat conditions.

Charge must be added for the interconnecting 

tubing. 

Use of piston-style metering device is 

typical. Where TXVs are necessary due to AHRI-

match or performance-related applications, a 

15% bleed-type TXV is required.

 These units 

should be critically charged to ensure proper 

performance. Some systems may require 

additional charging of refrigerant, depending on 

line set lengths.

FINAL INSPECTION

Do a final visual inspection of the entire installation 

and complete any final details and clean up.

Review Unit Operation with the homeowner/user.

The pressure/temperature chart can be used as a 

reference to ensure performance.

2XWGRRU$PELHQW7HPSHUDWXUH963UHVVXUH

2XWGRRU7HPSHUDWXUH

1RWH

³,'7´ ,QGRRU7HPSHUDWXUH

³2'7´ 2XWGRRU7HPSHUDWXUH

5HPRYHUHIULJHUDQWLIWKHSUHVVXUHLVDERYHWKHFKDUWYDOXH

$GGUHIULJHUDQWLIWKHSUHVVXUHLVEHORZWKHFKDUWYDOXH

36,

R(oz): Additional refrigerant to be charged

L(ft):   The length of the liquid pipe

T(oz): The quantity of the charged refrigerant 

           per additional foot

Charging by Length of Pipe

Your condensing unit is pre-charged for the 

evaporator coil and 25 ft. of refrigerant line set. 

For lengths over 25 ft. use charging chart and 

formula below.

Summary of Contents for COMFORT-AIRE CMA12SD-0

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL Horizontal Side Discharge Condensing Units Models CMA12SD 0 CMA18SD 1 CMA24SD 1 CMA30SD 1 CMA36SD 1 CMA48SD 1 517 787 2100 www marsdelivers com...

Page 2: ...ance TABLE OF CONTENTS Safety Precautions 3 General Operating Instructions 4 General Product Information 5 Outdoor Unit Installation 6 7 Unit Wiring 8 Wiring Diagrams 9 12 Refrigerant Piping 13 Leak T...

Page 3: ...uit Otherwise it will cause lower capacity abnormal high pressure in the refrigeration cycle explosion and injury 1 This equipment must be properly grounded and installed with a ground leakage circuit...

Page 4: ...e frequent starts call your service contractor 4 For energy conservation reasons you may want to set your thermostat at a higher temperature when you are away Do not raise the temperature setting by m...

Page 5: ...ar metering devices are acceptable for use but bleed style thermostatic expansion valves should be used where specific AHRI Match ratings require or where oversized coils or other application specific...

Page 6: ...of onto the unit In climates where snow is a consideration locate the unit away from areas prone to drifting Ensure the location of the unit will not be subject to snow drifts heavy accumulation of sn...

Page 7: ...and outlets are not obstructed See Fig 4 Anchor the outdoor unit with a 10mm 3 8 inch diameter bolt and nut tightly on a concrete or rigid surface See Fig 5 Anchoring is especially recommended in seas...

Page 8: ...compressor and other electrical components and voids the warranty NOTE The supply voltage must be consistent with the rated voltage of the air conditioner not to exceed 10 Ensure the unit is properly...

Page 9: ...48SD 9 Owner s Manual CMA12 48SD 9 OUTDOOR UNIT WIRING CONNECTION continued NOTE Please refer to the installation instructions of the 24V thermostat used in conjunction with this unit for additional...

Page 10: ...Owner s Manual CMA12 48SD 10 Owner s Manual CMA12 48SD 10 OUTDOOR UNIT WIRING CONNECTION continued...

Page 11: ...Owner s Manual CMA12 48SD 11 Owner s Manual CMA12 48SD 11 OUTDOOR UNIT WIRING CONNECTION continued...

Page 12: ...Owner s Manual CMA12 48SD 12 Owner s Manual CMA12 48SD 12 OUTDOOR UNIT WIRING CONNECTION continued...

Page 13: ...s service valves are shipped in the closed position and should not be opened until final connections leak testing and evacuation are completed The recommended procedure for leak test evacuation and r...

Page 14: ...temperature and humidity all have an effect on the system pressures and superheat conditions Charge must be added for the interconnecting tubing Use of piston style metering device is typical Where T...

Page 15: ...original consumer The consumer must retain a receipted bill of sale as proof of warranty period Without this proof the express warranty begins on the date of shipment from the factory REMEDY PROVIDED...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: