background image

Owner’s Manual -  

PTAC/PTHP130-150B/BSC

14

13

TROUBLESHOOTING

POSSIBLE CAUSES

SOLUTIONS

UNIT DOES NOT START

• Unit may be unplugged

• Fuse may have blown

• Circuit breaker may have tripped

• Unit may be off or in wall thermostat mode.

Check  section  on dipswitch  settings  to  verify dipswitches

are set properly.

• Unit may be in a  protection or diagnostic failure mode. See

section on diagnostic codes.

• Check that plug is plugged securely in wall receptacle.

Note:

 Plug has a test/reset button on it. Make  sure that the

plug has not tripped.

• Replace the fuse.

• Reset circuit breaker.

• Turn unit on (bottom right button  on keypad).

DISPLAY HAS STRANGE NUMBERS/CHARACTERS ON IT

• The unit  may  be in a diagnostic condition. Check diagnostic

codes --- checking Control section to determine if unit has had

a failure.

• The unit  may be set for °C (instead of °F), see the 

SET UP

OPERATION.

UNIT MAKING NOISES

• Clicking, gurgling and whooshing noises are normal during

operation of unit.

UNIT NOT COOLING / HEATING ROOM

• Unit air discharge section is blocked

• Temperature setting is not high or low enough

Note:

 Setpoint limits may not allow the unit to heat or cool  the

room to the temperature desired. Check section on SET UP

OPERATION settings.

• Unit air filters are dirty.

• Room is excessively hot or cold when unit is started

• Vent door left open

• Unit may be in a protection or diagnostic failure mode. Check

section on Intelligent Self --- checking Control.

• Compressor is in time delay. There is a protective time delay

(approx. 3 minutes) on starting the compressor after a power

outage (or restarting  after it has  been turned off), to prevent

tripping of the compressor overload.

• Make sure  that  curtains, blinds or furniture are not restricting

or blocking unit airflow.

• Reset to a lower or higher temperature setting.

• Remove and clean filters.

• Allow sufficient amount of lime for unit to heat or cool

the room. Start heating or cooling early before outdoor

temperature, cooking heat or gatherings of people make room

uncomfortable.

• Close vent door.

• Check dipswitch settings for desired comfort.

• Wait approximately 3 minutes for compressor to start

WATER DRIPPING INSIDE

WATER DRIPPING INSIDE

• Wall sleeve is not installed level

ICE OR FROST  FORMS ON INDOOR COIL

• Low outdoor temperature

• Dirty filters

COMPRESSOR PROTECTION

• Power may have cycled, so compressor is in a restart

protection.

• Random Compressor restart-Whenever the unit is plugged  in,

or power has been restarted, a  random compressor restart will

occur.  After  a power  outage, the compressor will restart after

approximately 3 minutes.

• Compressor Protection-To prevent short cycling of the

compressor, there  is a startup delay of 3 minutes and a

minimum compressor run time of 3 minutes.

• When outdoor temperature  is  approximately 55°F (12.8 °C) or 

below, frost  may  form on the indoor  coil when unit is in Cooling

mode.   Switch  unit to FAN operation until ice or frost meIts.

• Remove and clean filters.

• Wall sleeve must be installed level for proper drainage of

condensation. Check that installation is level and make any

necessary adjustments.

• If a drain kit has not been  installed, condensation run off during

very hot and humid  weather is normal. See Note 2. If a drain

kit has been  installed and is connected to a drain system,

check  gaskets and fittings around drain  for leaks and plugs.

Summary of Contents for Comfort-Aire Century PTAC07A130B

Page 1: ...g PTAC07A130B PTAC09A130B PTAC12A130BSC PTAC12A130B PTAC12A150BSC PTAC12A150B PTAC15A130BSC PTAC15A130B PTAC15A150BSC PTAC15A150B Heat Pump w Electric Heat Heat Pump w Electric Heat with seacoast coat...

Page 2: ...CING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 CONTENTS UNIT FEATURES 3 INSTALLATION INSTRUCTION 5 WIRING 9 OP...

Page 3: ...fter the compressor turns off the unit will restart when the pressure turns back below 551 psi This protection can effectively avoid the burst and leakage of pipes lessen the system failures and prolo...

Page 4: ...ontroller or the control panel Special control functions for DIP switches The DIP switches are on main board No 5 auto heating for units with heat When unit is connected to the power supply and room t...

Page 5: ...rated and maintained according to these installation and operating instructions and all local codes and ordinances or in their absence with the latest edition of the National Electric Code or CEC for...

Page 6: ...ove the wall sleeve The sleeve can not support the load of bricks blocks For existing construction wall opening must be created the proper dimensions are necessary to avoid use of fillers or additiona...

Page 7: ...compressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty FRONT REMOVAL 1 Grasp the cabinet front 3 Slide the chassis into the wall sleeve until the chass...

Page 8: ...TIPLE POWER SOURCES BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE POWER TO THE UNIT FROM THE CIRCUIT BREAKER AN...

Page 9: ...tal Displayer On normal operation indicates room temperature When pressing or button indicates setting temperature On time operation indicates timer time On failure operation indicates fault code Warm...

Page 10: ...ONTROL The ventilation control lever is located at left side of unit behind front panel NOTE The vent door shipping tape must be removed before using vent control lever See Fig 9 and Fig 10 When set t...

Page 11: ...sitions Location of 7 Screws 15 Discharge Air 55 Discharge Air Use the following procedure to change the angle of the discharge air flow 1 Remove the front cabinet see Front Removal 2 Position the fro...

Page 12: ...enings around the sleeve are properly sealed The wall sleeve s level should also be rechecked Proper leveling for most installations are a 1 4 bubble tilt to the outside and level from right to left C...

Page 13: ...n and operational status including present modes failures airflow restriction warnings operating temperatures and past failures To enter Diagnostic Status Report mode press and hold the down arrows an...

Page 14: ...starting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher...

Page 15: ...uring brown out conditions or circuit interruptions Air flow around any section of the unit has not been restricted Unit remains in the original installation Unit was not purchased over the internet D...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: