background image

Owner’s Manual -  

PTAC/PTHP130-150B/BSC

13

12

4. Tilt the non-compressor side of the unit up no higher

than 45 degrees and allow water to drain out the other

side of the unit.

5. Remove excess water left in the base pan by wiping 

the base pan with a dry cloth.

6. Remove the water-tight seal from the motor and

control panel area.

7. Reinstall unit back into wall sleeve.

8. Allow unit to dry for 24 hours before reapplying

power. When power is reapplied test unit for proper

operation.

9. Place a non-acidic algaecide in the base pan to inhibit

bacteria growth. Ensure the algaecide is compatible

with wet coil operation and is not corrosive to the coil.

Air sounds

The fan cycle switch sets the operational mode of the 

fan. In the ON position the fan will run continuously 

whenever power is applied in this mode. In the 

AUTO position, the fan will cycle on and off with the 

compressor or electric heater.

Starting delay

You may notice a few minutes delay in the starting if  

you try to restart the unit too soon after turning it off or if  

you adjust the thermostat right after the compressor has

shut off. This is due to a built-in delay to protect the 

compressor.

Buzzer  Response

The buzzer will chime (0.1 sec) as response when 

receiving an order from key pad control and remote 

control.

DIAGNOSTIC CODES

The Diagnostic Maintenance provides detailed 

information on PTAC control operation and operational 

status including present modes, failures, airflow 

restriction warnings, operating temperatures, and past 

failures.

To enter Diagnostic Status Report mode,press and 

hold the down arrows and,while holding press the FAN 

SPEED key for a period of five (5) seconds.
The meaning of figure on display pad is as below: 

X.X---(0~4: time of protection)
L---is protection mode(1: anti-frost; 2: overheat; 3: high 

pressure; 4: anti-freezing)

Failure 

code

Content or detect

E2

Indoor temperature sensor failure

E3

Indoor coil temperature sensor failure

E5

Outdoor coil temperature sensor failure

E8

Overheating protectlon/defrostlng

E9

High pressure protection

CAUTION 

HIGH PRESSURE AND HIGH TEMPERATURE CLEANING IS 

NOT RECOMMENDED.

DOING SO COULD DAMAGE THE ALUMINUM FIN STOCK 

AND ELECTRICAL COMPONENT.

!

Clearance Check

Clearances around the unit should also be checked to 

make sure that the intake air and discharge air paths 

have not become blocked or restricted. A minimum of 

eight inches clearance is needed from unit to furniture, 

beds, or other objects for proper operation. Restricted 

discharge or intake air will reduce the unit’s operational 

performance. In severe airflow restrictions, damage 

can occur to unit components such as the compressor, 

electric heater or fan motor.

NORMAL OPERATING SOUNDS 

AND CONDITIONS

Water trickling sounds

Water is picked up  and  distributed over the coil. This 

improves the efficiency and helps with water removal.

Water dripping

Water will collect in the base pan during high humidity 

days. This can cause overflow and drip from the outside 

of the unit.

Summary of Contents for Comfort-Aire Century PTAC07A130B

Page 1: ...g PTAC07A130B PTAC09A130B PTAC12A130BSC PTAC12A130B PTAC12A150BSC PTAC12A150B PTAC15A130BSC PTAC15A130B PTAC15A150BSC PTAC15A150B Heat Pump w Electric Heat Heat Pump w Electric Heat with seacoast coat...

Page 2: ...CING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 CONTENTS UNIT FEATURES 3 INSTALLATION INSTRUCTION 5 WIRING 9 OP...

Page 3: ...fter the compressor turns off the unit will restart when the pressure turns back below 551 psi This protection can effectively avoid the burst and leakage of pipes lessen the system failures and prolo...

Page 4: ...ontroller or the control panel Special control functions for DIP switches The DIP switches are on main board No 5 auto heating for units with heat When unit is connected to the power supply and room t...

Page 5: ...rated and maintained according to these installation and operating instructions and all local codes and ordinances or in their absence with the latest edition of the National Electric Code or CEC for...

Page 6: ...ove the wall sleeve The sleeve can not support the load of bricks blocks For existing construction wall opening must be created the proper dimensions are necessary to avoid use of fillers or additiona...

Page 7: ...compressor may cycle on and off rapidly This could damage the compressor or possibly void the warranty FRONT REMOVAL 1 Grasp the cabinet front 3 Slide the chassis into the wall sleeve until the chass...

Page 8: ...TIPLE POWER SOURCES BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE POWER TO THE UNIT FROM THE CIRCUIT BREAKER AN...

Page 9: ...tal Displayer On normal operation indicates room temperature When pressing or button indicates setting temperature On time operation indicates timer time On failure operation indicates fault code Warm...

Page 10: ...ONTROL The ventilation control lever is located at left side of unit behind front panel NOTE The vent door shipping tape must be removed before using vent control lever See Fig 9 and Fig 10 When set t...

Page 11: ...sitions Location of 7 Screws 15 Discharge Air 55 Discharge Air Use the following procedure to change the angle of the discharge air flow 1 Remove the front cabinet see Front Removal 2 Position the fro...

Page 12: ...enings around the sleeve are properly sealed The wall sleeve s level should also be rechecked Proper leveling for most installations are a 1 4 bubble tilt to the outside and level from right to left C...

Page 13: ...n and operational status including present modes failures airflow restriction warnings operating temperatures and past failures To enter Diagnostic Status Report mode press and hold the down arrows an...

Page 14: ...starting after it has been turned off to prevent tripping of the compressor overload Make sure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher...

Page 15: ...uring brown out conditions or circuit interruptions Air flow around any section of the unit has not been restricted Unit remains in the original installation Unit was not purchased over the internet D...

Page 16: ...DOOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQ...

Reviews: