4. Rain water might penetrate into pipeline during
construction.
Procedures of special vacuum drying are as follows:
1. Vacuum drying for 1 hour.
2. Vacuum damage, filling nitrogen to reach 0.5Kgf/cm
2
.
Because nitrogen is dry gas, vacuum damage could
achieve the effect of vacuum drying, but this method
could not achieve drying thoroughly when there is too
much moisture. Therefore, special attention shall be drawn
to prevent the entering of water and the formation of
condensate water.
3. Vacuum drying again for half an hour.
If the pressure reached -755mmHg, start to pressure
leakage test. If it cannot reached the value, repeat vacuum
damage and vacuum drying again for 1 hour.
4. Leakage test: After the vacuum degree reaches
-755mmHg, stop vacuum drying and keep the pressure for
1 hour. If the indicator of vacuum gauge does not go up,
it is qualified. If going up, it indicates that there is moisture
or leak source.
8. Additional Refrigerant Charge
•
After the vacuum drying process is carried out, the
additional refrigerant charge process need to be
performed.
•
The outdoor unit is factory charged with refrigerant.
The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe be-
tween indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid
pipe (mm(inch))
Formula
R410A(Throttling
part in the indoor
unit)
6.35(1/4)
V=30(0.32)g/m(oz/ft)×(L-
standard pipe length)
9.52(3/8)
V=65(0.69)g/m(oz/ft)×(L-
standard pipe length)
12.7(1/2)
V=115(1.23)g/m(oz/ft)×(L-
standard pipe length)
R410A(Throttling
part in the
outdoor unit)
6.35(1/4)
V=15(0.16)g/m(oz/ft)×(L-
standard pipe length)
9.52(3/8)
V=30(0.32)g/m(oz/ft)×(L-
standard pipe length)
12.7(1/2)
V=65(0.69)g/m(oz/ft)×(L-
standard pipe length)
R32
6.35(1/4)
V=12(0.13)g/m(oz/ft)×(L-
standard pipe length)
9.52(3/8)
V=24(0.26)g/m(oz/ft)×(L-
standard pipe length)
12.7(1/2)
V=40(0.42)g/m(oz/ft)×(L-
standard pipe length)
V:
Additional refrigerant charge volume.
L :
The length of the liquid pipe.
Note:
•
Refrigerant may only be charged after performed
the vacuum drying process.
•
Always use gloves and glasses to protect your hands
and eyes during the charge work.
•
Use electronic scale or fluid infusion apparatus to
weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid ham-
mer of the compressor or protections.
•
Use supplementing flexible pipe to connect refriger-
ant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state.
Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
•
After finished refrigerant recharge process, check
whether there is refrigerant leakage at the connec-
tion joint part.(Using gas leakage detector or soap
water to detect).
8. Additional Refrigerant Charge
Summary of Contents for Comfort-Aire Century A-VMH18SV-1
Page 30: ...Service Manual B VMHxxAV 1 ...
Page 37: ...Service Manual B VMHxxAV 1 Outdoor Unit 3 3 Panel Plate X430 Square grille ...
Page 38: ...Service Manual B VMHxxAV 1 Outdoor Unit 4 4 Panel Plate D30 Square grille ...
Page 39: ...Service Manual B VMHxxAV 1 Outdoor Unit 5 5 2 Service Place Minimim 4 Recommended 12 ...
Page 42: ...Service Manual B VMHxxAV 1 Outdoor Unit 8 8 A VMH18SV 1 A VMH24SV 1 ...
Page 45: ...Service Manual B VMHxxAV 1 ...
Page 103: ...Service Manual B VMHxxAV 1 Troubleshooting 15 ...