Service Manual -
B-VMHxxAV-1
Troubleshooting 34
7.11 PC 02/LC 06(Top temperature protection of compressor or High temperature
protection of IPM module diagnosis and solution)
Description:
For some models with overload protection, If the sampling voltage is not 5V, the LED will display the failure.
If the temperature of IPM module is higher than a certain value, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• IPM module board
• High pressure protector
• System blockages
Troubleshooting and repair:
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the temperature of
compressor Top
Is more than 90
℃?
No
Check if the refrigerant
system
is normal?
Repair the refrigerant
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
No
Summary of Contents for Comfort-Aire Century A-VMH18SV-1
Page 30: ...Service Manual B VMHxxAV 1 ...
Page 37: ...Service Manual B VMHxxAV 1 Outdoor Unit 3 3 Panel Plate X430 Square grille ...
Page 38: ...Service Manual B VMHxxAV 1 Outdoor Unit 4 4 Panel Plate D30 Square grille ...
Page 39: ...Service Manual B VMHxxAV 1 Outdoor Unit 5 5 2 Service Place Minimim 4 Recommended 12 ...
Page 42: ...Service Manual B VMHxxAV 1 Outdoor Unit 8 8 A VMH18SV 1 A VMH24SV 1 ...
Page 45: ...Service Manual B VMHxxAV 1 ...
Page 103: ...Service Manual B VMHxxAV 1 Troubleshooting 15 ...