background image

EXAMPLE: The product water rate is 14 

gpd and the drain water rate is 56 gpd. 

Feed Rate = 14 gpd + 56 gpd = 70 gpd

% Recovery = 14 gpd x 100%

70 gpd 

% Recovery = 0.20 x 100% or 20% 

C. Net Pressure Differential

Most R.O. Membranes are rated at a standardized
condition of 77˚F (25˚C) and 65 psig (450kPa) dis-
charging to atmospheric pressure. 

Product water quality and quantity greatly depend
upon the 

Net Pressure Differential 

(

p)

across

the R.O. Membrane. This pressure differential is a
summation of the feed water pressure at the
Membrane, which tries to push the water through,
the pressure in the Holding Tank, which tries to
push the water backwards and the osmotic pres-
sure, which also tries to push the water backwards. 

The 

Osmotic Pressure

is in proportion to the dis-

NOTES:

solved minerals in the water and can be approxi-
mated by 1 psig for each 100 ppm of TDS. 

EXAMPLE: A feed water with 1500 ppm of TDS 
would exert a backward pressure of about 15 psig
on the membrane. 

Net Pressure Differential = 
Feed Water Pressure – Holding Tank Pressure – 
Osmotic Pressure

The higher the net pressure differential, the higher
the quantity and quality of water produced. Some
loss of production is normal when using a pressur-
ized Holding Tank.

Summary of Contents for TFC-25

Page 1: ...his system shall only be used for arsenic reduction on chlorinated water supplies containing detectable residual free chlorine at the system inlet Water systems using an in line chlorinator should pro...

Page 2: ...s is not 100 immunosuppressed individuals should take the extra precaution of boiling their drinking water According to the CDC EPA bringing water to a rolling boil for one minute is the most certain...

Page 3: ...to drain the Reject Water The membrane is specially constructed fully aromatic polyamide film and is classified as a Thin Film Composite T F C The spiral wound construction of the R O Membrane provide...

Page 4: ...OM R O MANIFOLD TO DISPENSING FAUCET AS SHORT AS POSSIBLE NOTE FOR BEST FLOW RATE KEEP TUBING FROM HOLDING TANK TO R O MANIFOLD AS SHORT AS POSSIBLE PLEASE NOTE IF AIR GAP ON FAUCET IS NOT USED IN BAS...

Page 5: ...ollowing should be used for comparison purposes only U S Metric Membrane Production 1 25 4 gpd 79 110 lpd Membrane TDS Reduction 1 95 minimum 95 minimum System Production 2 8 gpd 30 lpd TDS Reduction...

Page 6: ...ent wrench with jaws taped to hold faucet 13 Basin wrench or 10 pipe wrench 14 Teflon tape 15 Wide masking tape or duct tape 16 Plastic tubing cutter 17 Extra plastic tubing 18 Low range air pressure...

Page 7: ...ap While the system is producing water the drain water flows from the R O through the air gap and then to the household drain The purpose of the air gap is to prevent water in the drain from backing u...

Page 8: ...n location Do NOT connect to a hot water feed line If you are not sure of the supply run the hot water and feel the supply piping Water over 100 F may cause permanent damage to the R O Membrane Refer...

Page 9: ...open the sink faucet and the water supply and allow the water to run for a few minutes to flush any debris caused by the installation Close the faucet and check the Feed Water Saddle Valve for leaks C...

Page 10: ...le Valve trim to length Refer to Fig 1 page 1 Refer to Fig 3 page 6 To the end of the red polytube install the Compression Nut the Plastic Ferrule and the Insert Connect to the Feed Water Saddle Valve...

Page 11: ...ose the Faucet Let stand for 15 minutes NOTE During this time check the system carefully for leaks At the end of 15 minutes CLOSE the Feed Water Saddle Valve and open the Dispensing Faucet Allow the H...

Page 12: ...ve gloves to avoid direct contact with the exhaust ed filters The recommended interval for changing the filters not the R O Membrane is every six 6 months Typical T F C Membrane life expectancy is thr...

Page 13: ...he product water and is reported as Percent Rejection If the feed water contained 100 ppm of TDS and the product water contained 10 ppm of TDS 90 ppm have been rejected and the reject ratio is 90 Perc...

Page 14: ...the Membrane which tries to push the water through the pressure in the Holding Tank which tries to push the water backwards and the osmotic pres sure which also tries to push the water backwards The...

Page 15: ...50 11 9 45 0 15 5 58 7 19 2 72 7 22 8 86 3 26 4 99 9 30 1 113 9 33 7 127 6 500 10 2 38 6 13 9 52 6 17 5 66 2 21 2 80 2 24 8 93 9 28 5 107 9 32 1 121 5 1000 8 4 31 8 12 0 45 4 15 7 59 4 19 3 73 1 23 0...

Page 16: ...Check the brine seal If Membrane life is unusually short find and correct the problem Replace Membrane Feed Water Saddle Valve is plugged or closed Clogged Sediment Carbon Prefilter or Activated Carbo...

Page 17: ...on Tastes and odors in the Product Water The Product Water and Drain Water lines are reversed No drain flow Drain Restrictor is clogged No drain flow the drain orifice in the Air Gap Faucet is plugged...

Page 18: ...MADE IN USA PUSH TO TEST 1 2 3 4 5 6 7 8 9 10 11 12 13 14 19 22 21 EXPLODED VIEW PARTS LIST 20A Water Quality Test Kit 23 Nitrate Nitrite Test Kit 15 17 20 18 16 15A 16...

Page 19: ...ality Monitor Board w Probes 15A PK A4TPL 1 4 Plug 16 PK A6TEU4 MG 1 4 Post X 3 8 Polytube Elbow 17 S2116 6 Drain Restrictor 60 GPD 227 lpd Yellow 18 S2119 01NN Cover 19 S7025 Activated Carbon Post Fi...

Page 20: ...ver This warranty does not cover the disposable sediment and carbon filters whose service life depends on feed water conditions In addition the membrane is only warranted if the required feed water co...

Reviews: