background image

• To pierce the tubing, turn the Valve Handle

fully clockwise (inward). A small amount of
water may escape from the outlet until it is
fully pierced. 

When you feel the Valve Handle firmly seated
in the clockwise direction, the copper tube is
pierced and the valve is closed. 

2b. To install on (hard) Steel or Brass Tubing

supply line. 

• The supply line should now be drained. Use a

battery powered or properly grounded drill to
avoid shock hazard.

• Drill a 3/16" hole in the supply line; (do not drill

through the opposite wall). 

• Turn the handle to expose the lance no more

than 3/16" beyond the rubber gasket. 

• Place the body of the valve over the hole so

that the lance fits into the hole. 

• Assemble and tighten the brass screw. 

• Turn the Valve Handle clockwise (inward) until

firmly seated. The valve is closed. 

3. With the Feed Water Saddle Valve closed, open

the sink faucet and the water supply and allow
the water to run for a few minutes to flush any
debris caused by the installation. 

•Close the faucet and check the Feed Water

Saddle Valve for leaks.

C. Drain Clamp Installation 

Choose the drain outlet location per Sec. III, C.5,
page 5. 

The following are instructions for discharging into
the sink drain pipe. (Refer to Fig. 1, page 1.) 

1. Position the Drain Clamp on the sink drain pipe

above the drain trap. Allow room for drilling.
Tighten securely. 

2. Use a battery powered or properly grounded

drill. Using the Clamp port as a drill guide, drill a
7/32" hole through the wall of the drain pipe. Do
NOT penetrate the opposite side of the pipe. 

3. Locate the 3/8" Black Drain Tubing which is

shipped loose in the box. 

NOTE:

When cutting the polytubing make

clean, square cuts, failing to do so could result
in poor connections and possible leaks. 

Drain Pipe

1/4" Screw

Drain Clamp

Front Plate

Insert

Compression

Nut

 Black Drain

Tubing

1/4" Nut

Drain Clamp
Back Plate

3/8" DRAIN CLAMP ASSEMBLY

Figure 4

Summary of Contents for TFC-25

Page 1: ...his system shall only be used for arsenic reduction on chlorinated water supplies containing detectable residual free chlorine at the system inlet Water systems using an in line chlorinator should pro...

Page 2: ...s is not 100 immunosuppressed individuals should take the extra precaution of boiling their drinking water According to the CDC EPA bringing water to a rolling boil for one minute is the most certain...

Page 3: ...to drain the Reject Water The membrane is specially constructed fully aromatic polyamide film and is classified as a Thin Film Composite T F C The spiral wound construction of the R O Membrane provide...

Page 4: ...OM R O MANIFOLD TO DISPENSING FAUCET AS SHORT AS POSSIBLE NOTE FOR BEST FLOW RATE KEEP TUBING FROM HOLDING TANK TO R O MANIFOLD AS SHORT AS POSSIBLE PLEASE NOTE IF AIR GAP ON FAUCET IS NOT USED IN BAS...

Page 5: ...ollowing should be used for comparison purposes only U S Metric Membrane Production 1 25 4 gpd 79 110 lpd Membrane TDS Reduction 1 95 minimum 95 minimum System Production 2 8 gpd 30 lpd TDS Reduction...

Page 6: ...ent wrench with jaws taped to hold faucet 13 Basin wrench or 10 pipe wrench 14 Teflon tape 15 Wide masking tape or duct tape 16 Plastic tubing cutter 17 Extra plastic tubing 18 Low range air pressure...

Page 7: ...ap While the system is producing water the drain water flows from the R O through the air gap and then to the household drain The purpose of the air gap is to prevent water in the drain from backing u...

Page 8: ...n location Do NOT connect to a hot water feed line If you are not sure of the supply run the hot water and feel the supply piping Water over 100 F may cause permanent damage to the R O Membrane Refer...

Page 9: ...open the sink faucet and the water supply and allow the water to run for a few minutes to flush any debris caused by the installation Close the faucet and check the Feed Water Saddle Valve for leaks C...

Page 10: ...le Valve trim to length Refer to Fig 1 page 1 Refer to Fig 3 page 6 To the end of the red polytube install the Compression Nut the Plastic Ferrule and the Insert Connect to the Feed Water Saddle Valve...

Page 11: ...ose the Faucet Let stand for 15 minutes NOTE During this time check the system carefully for leaks At the end of 15 minutes CLOSE the Feed Water Saddle Valve and open the Dispensing Faucet Allow the H...

Page 12: ...ve gloves to avoid direct contact with the exhaust ed filters The recommended interval for changing the filters not the R O Membrane is every six 6 months Typical T F C Membrane life expectancy is thr...

Page 13: ...he product water and is reported as Percent Rejection If the feed water contained 100 ppm of TDS and the product water contained 10 ppm of TDS 90 ppm have been rejected and the reject ratio is 90 Perc...

Page 14: ...the Membrane which tries to push the water through the pressure in the Holding Tank which tries to push the water backwards and the osmotic pres sure which also tries to push the water backwards The...

Page 15: ...50 11 9 45 0 15 5 58 7 19 2 72 7 22 8 86 3 26 4 99 9 30 1 113 9 33 7 127 6 500 10 2 38 6 13 9 52 6 17 5 66 2 21 2 80 2 24 8 93 9 28 5 107 9 32 1 121 5 1000 8 4 31 8 12 0 45 4 15 7 59 4 19 3 73 1 23 0...

Page 16: ...Check the brine seal If Membrane life is unusually short find and correct the problem Replace Membrane Feed Water Saddle Valve is plugged or closed Clogged Sediment Carbon Prefilter or Activated Carbo...

Page 17: ...on Tastes and odors in the Product Water The Product Water and Drain Water lines are reversed No drain flow Drain Restrictor is clogged No drain flow the drain orifice in the Air Gap Faucet is plugged...

Page 18: ...MADE IN USA PUSH TO TEST 1 2 3 4 5 6 7 8 9 10 11 12 13 14 19 22 21 EXPLODED VIEW PARTS LIST 20A Water Quality Test Kit 23 Nitrate Nitrite Test Kit 15 17 20 18 16 15A 16...

Page 19: ...ality Monitor Board w Probes 15A PK A4TPL 1 4 Plug 16 PK A6TEU4 MG 1 4 Post X 3 8 Polytube Elbow 17 S2116 6 Drain Restrictor 60 GPD 227 lpd Yellow 18 S2119 01NN Cover 19 S7025 Activated Carbon Post Fi...

Page 20: ...ver This warranty does not cover the disposable sediment and carbon filters whose service life depends on feed water conditions In addition the membrane is only warranted if the required feed water co...

Reviews: