16
8.3 Electrical connection condensate pump
Pump running time (standard)
Pump float switch (special)
8.4 Mounting
The FBA Ultra must be installed absolutely horizontal or with a slight slope of 1mm for the
condensate pump.
8.5 Commissioning
Free the condensate tray of dust and other contaminants. Before commissioning the operation of
the condensate pump must be checked. For this, remove the removable louvres, pour distilled water
into the tray and remove the pump. Only after making sure that the pump is working properly, the
device can be put into operation.
8.6 Maintenance
Regularly (at least every six months) and before the cooling down period, the condensate tray must
be subjected to a visual inspection. Existing deposits (dust, mud, vermin, etc.) must be removed.
For a correct operation of the pump, the round filter that is placed in the supply of the pump must
be cleaned or replaced regularly. The frequency for cleaning and replacing the filter depends on the
operating conditions. After an extended period, the filter must definitely be cleaned or if necessary
replaced.
In the abscence of maintenace the warranty expires!
9 Maintenance
9.1 Warranty
Our warranty does not cover damage caused by improper use or maintenance. Moreover,
experience shows that with increasing age of the products, lack of maintenance leads to greater
damage.
Inspections of the safety equipment should only be performed by trained and qualified personnel!
Please contact the service department of your supplier.
2
U2
V2
V1
W1
T K
T K
P E
1
65
10
9
43
87
12
11
14
13
20
19
W2
U1
L1
N
18
17
24
23
16
15
22
21
Isolator switch
TK = Thermocontact
Y - Position: low speed
Engine 001
2 speeds, with isolator switch
bro
wn
∆
- Position: high speed
blue
blac
k
or
ang
e
red
brown
blue
blac
k
red
grey
whit
e
whit
e
Condensate pump
Float switch
Level switch emergency stop
50 VA ohmse load
(Alarm) 250 V
2
U2
V2
V1
W1
TK
TK
PE
1
5
6
9
01
3
4
7
8
11
21
31
41
91
02
W2
U1
L
N
71
81
32
42
51
61
12
22
L1
N
PL
PN
C
NC
Isolator switch
TK = Thermocontact
Y - Position: low speed
Engine 001
2 speeds, with isolator switch
brow
n
∆
- Position: high speed
blue
blac
k
orange
re
d
gre
y
whit
e
whit
e
1
ws
2
ws
3
ws
4
ws
Connection box
Float switch
brow
n
blue
Condensate pump
Summary of Contents for 0662551
Page 1: ...Technical manual EN MARK TANNER FBA ULTRA 0662551...
Page 2: ...2...