COMPRESSOR TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Compressor will
not start
Faulty
control board
.
Measuring from C on the terminal
strip, verify there is voltage at Y,
HP1, HP2, LP1, LP2, and both flow
pins but no voltage present at out-
put.
Replace
control board
.
Faulty run capacitor.
(Single phase only)
Check value with capacitance meter.
Should match label on capacitor.
Compressor will hum while trying to
start and then trip its overload.
Replace if faulty.
Loose or faulty wiring.
Check all compressor wiring, includ-
ing inside compressor electrical box.
Fix any loose connections. Re-
place any damaged wires.
Faulty compressor
contactor.
Voltage on line side with contactor
held closed, but no voltage on one
or both terminals on the load side.
Points pitted or burned.
Or, 24VAC across coil but contactor
will not engage.
Replace contactor.
Thermal overload on
compressor tripped.
Ohmmeter shows reading when
placed across R and S terminals
and infinity between C & R or C & S.
A valid resistance reading is present
again after the compressor has
cooled down.
Proceed to Operation Trouble-
shooting to determine the cause
of the thermal overload trip.
Burned out motor
(open winding)
Remove wires from compressor.
Ohmmeter shows infinite resistance
between any two terminals Note: Be
sure compressor overload has had a
chance to reset. If compressor is hot
this may take several hours.
Replace the compressor.
Burned out motor
(shorted windings)
Remove wires from compressor.
Resistance between any two termi-
nals is below the specified value.
Replace the compressor.
Motor shorted to ground.
Remove wires from compressor.
Check for infinite resistance be-
tween each terminal and ground.
If any terminal to ground is not
infinite replace the compressor.
Seized compressor due to
locked or damaged
mechanism.
Compressor attempts to start but
trips its internal overload after a few
seconds. (Run capacitor already
verified)
Attempt to “rock” compressor free.
If normal operation cannot be
established, replace compressor.
Compressor
starts hard
Start capacitor faulty.
(Single phase only)
Check with capacitance meter.
Check for black residue around
blowout hole on top of capacitor.
Replace if faulty.
Remove black residue in electrical
box if any.
Potential Relay faulty.
(Single phase only)
Replace with new one and verify
compressor starts properly.
Replace if faulty.
Compressor is “tight” due
to damaged mechanism
Compressor attempts to start but
trips its internal overload after a few
seconds. Run capacitor has been
verified already.
Attempt to “rock” compressor free.
If normal operation cannot be es-
tablished, replace compressor.
Summary of Contents for WH-Series
Page 9: ...1 Oct 2015 Page 9 002028MAN 01...
Page 11: ...1 Oct 2015 Page 11 002028MAN 01...
Page 12: ...Page 12 002028MAN 01 1 Oct 2015...
Page 13: ...1 Oct 2015 Page 13 002028MAN 01...
Page 16: ...Page 16 002028MAN 01 1 Oct 2015...
Page 19: ...1 Oct 2015 Page 19 002028MAN 01...
Page 43: ...1 Oct 2015 Page 43 002028MAN 01 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...Page 56 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 230 1 60...
Page 57: ...1 Oct 2015 Page 57 002028MAN 01 ELECTRICAL DIAGRAMS 208 230 1 60 continued...
Page 58: ...Page 58 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 220 1 50...
Page 59: ...1 Oct 2015 Page 59 002028MAN 01 ELECTRICAL DIAGRAMS 220 1 50 continued...
Page 60: ...Page 60 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 3 60...
Page 61: ...1 Oct 2015 Page 61 002028MAN 01 ELECTRICAL DIAGRAMS 208 3 60 continued...
Page 62: ...Page 62 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 380 3 50...
Page 63: ...1 Oct 2015 Page 63 002028MAN 01 ELECTRICAL DIAGRAMS 380 3 50 continued...
Page 64: ...Page 64 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 460 3 60...
Page 65: ...1 Oct 2015 Page 65 002028MAN 01 ELECTRICAL DIAGRAMS 460 3 60 continued...
Page 66: ...Page 66 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 575 3 60...
Page 67: ...1 Oct 2015 Page 67 002028MAN 01 ELECTRICAL DIAGRAMS 575 3 60 continued...
Page 68: ...Page 68 002028MAN 01 1 Oct 2015 REFRIGERATION CIRCUIT DIAGRAMS...
Page 69: ...1 Oct 2015 Page 69 002028MAN 01 DIMENSIONS WH 25 45 55 DIMENSIONS WH 65 75 80...