View—Alarms:
The alarms page has three tabs, the first shows the current alarm status, number of alarms, high and low refrigeration
alarm cutout values as well as the short cycle timer. The second tab shows a list of alarms that have occurred since the PC APP has
been operating (this will be lost when the PC is disconnected from the controller board.) The third tab is a list of board hardware faults.
RESET
button: This will reset all alarms and alarm counts, including a permanent alarm.
WARNING: Repeated resets can freeze and rupture the heat exchanger, ruining the heat pump and voiding the war-
ranty.
The source of the alarm should be determined before resetting the unit if possible or during operation after a reset.
!
ALARMS Tab (see screen shot on next page):
NOTE: Alarms that are greyed out are not applicable to the system setup and are not monitored by the control board.
NOTE: Refer to Alarms and Faults screenshot below to see which alarms have a count.
Alarms without a count:
These alarms only occur one time at which point they immediately create a
Permanent Alarm
.
Alarms with a count:
When an alarm occurs the compressor will stop, the alarm count will increase and the
Short Cycle Timer
will start. When the
SC Timer
expires the compressor will re-start. If no further alarms occur within
Count
Reduce
Time
, the alarm count will be reduced by 1. If another alarm occurs within
Count Reduce Time
(see
Configuration Page
) the count will increase by 1. If alarms continue to occur, when the alarm count
reaches
the
Maximum Count
value a
Permanent Alarm
will occur.
Master Alarm:
This alarm occurs when any alarm occurs. It is used to simply indicate that there is an alarm.
Permanent Alarm:
The compressor will be locked out until the
Permanent Alarm
is manually reset either by cycling the
power or clicking on the
RESET
button
Low Pressure:
A low pressure alarm occurs when the suction pressure drops to or below the
Low Pressure Cutout
value. The low pressure is checked just before a compressor start, if it is OK the compressor will start,
otherwise an alarm will occur. When the compressor starts, the low pressure alarm will be ignored for the
number
of
seconds
that
Low Pressure Ignore
is set to, after which the low pressure alarm will be
re-enabled. This allows a dip in suction pressure below the cutout point during startup without causing a
nuisance
alarm.
High Pressure:
A high pressure alarm occurs when the discharge pressure rises to or above the
High Pressure Cutout
Value.
Compressor Monitor:
This alarm occurs when the compressor protection module sends a fault signal to the control board,
generally due to the compressor windings overheating.
Compressor Status:
This alarm occurs when there is a current draw on the compressor but no call for the compressor to be on
(ie welded contactor) or when there is a call for the compressor to be on but there is no compressor current
draw (ie manual high pressure control is open or contactor failure). Requires current sensor accessory.
Phase Monitor:
This alarm occurs when the Phase Monitor detects a fault condition and sends a fault signal to the control
board. For three phase units only and requires Phase Monitor accessory.
Loss of Charge:
This alarm occurs if both the low pressure and high pressure sensors are below 30PSIG (207kPa).
Outdoor Flow:
This alarm is ignored on compressor start for the number of seconds the Outdoor Flow
Ignore on Start
is
set
to.
Alarm
monitoring
will begin when the timer expires.
Indoor Flow:
This alarm is ignored on compressor start for the number of seconds the Indoor Flow
Ignore on Start
is
set
to.
Alarm
monitoring
will begin when the timer expires.
Summary of Contents for WH-Series
Page 9: ...1 Oct 2015 Page 9 002028MAN 01...
Page 11: ...1 Oct 2015 Page 11 002028MAN 01...
Page 12: ...Page 12 002028MAN 01 1 Oct 2015...
Page 13: ...1 Oct 2015 Page 13 002028MAN 01...
Page 16: ...Page 16 002028MAN 01 1 Oct 2015...
Page 19: ...1 Oct 2015 Page 19 002028MAN 01...
Page 43: ...1 Oct 2015 Page 43 002028MAN 01 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...Page 56 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 230 1 60...
Page 57: ...1 Oct 2015 Page 57 002028MAN 01 ELECTRICAL DIAGRAMS 208 230 1 60 continued...
Page 58: ...Page 58 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 220 1 50...
Page 59: ...1 Oct 2015 Page 59 002028MAN 01 ELECTRICAL DIAGRAMS 220 1 50 continued...
Page 60: ...Page 60 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 3 60...
Page 61: ...1 Oct 2015 Page 61 002028MAN 01 ELECTRICAL DIAGRAMS 208 3 60 continued...
Page 62: ...Page 62 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 380 3 50...
Page 63: ...1 Oct 2015 Page 63 002028MAN 01 ELECTRICAL DIAGRAMS 380 3 50 continued...
Page 64: ...Page 64 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 460 3 60...
Page 65: ...1 Oct 2015 Page 65 002028MAN 01 ELECTRICAL DIAGRAMS 460 3 60 continued...
Page 66: ...Page 66 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 575 3 60...
Page 67: ...1 Oct 2015 Page 67 002028MAN 01 ELECTRICAL DIAGRAMS 575 3 60 continued...
Page 68: ...Page 68 002028MAN 01 1 Oct 2015 REFRIGERATION CIRCUIT DIAGRAMS...
Page 69: ...1 Oct 2015 Page 69 002028MAN 01 DIMENSIONS WH 25 45 55 DIMENSIONS WH 65 75 80...