GENERAL MAINTENANCE SCHEDULE
Item
Interval
Procedure
Contactor
1 year
Inspect for pitted or burned points. Replace if necessary.
Heat exchanger
As required*
Clean as per HEAT EXHCANGER FLUSING PROCEDURE below.
*Generally not required for closed loop systems. Whenever system performance is reduced for open loop.
General Maintenance
COAXIAL HEAT EXCHANGER FLUSHING PROCEDURE—GROUNDWATER
STEP 1
Isolate the heat exchanger by closing the valves in the IN and OUT ports to the heat exchanger.
STEP 2
Blow out the heat exchanger into a clean 5 gallon bucket using compressed air.
STEP 3
If a purge cart is not available, use a 5 gallon plastic bucket, a circulator and some plastic piping to create a
makeshift pump system. Connect a the inlet and outlet to the heat exchanger ports.*
STEP 4
Place 2 gallons of RYDLYME in the purge cart (or bucket). Circulate the fluid through the heat exchanger
for at least 2 hours (3 recommended).
STEP 5
Disconnect the purge system dispose of the solution. RYDLYME is non-toxic and biodegradable and as
such can be poured down a drain.
*
Depending on the plumbing, there should be either unions or boiler drains for to access the heat exchanger.
STEP 6
Connect fresh water and a drain to the heat exchanger ports and flush the exchanger for several minutes.
STEP 7
Return the plumbing to its original configuration and open the IN and OUT valves. Operate the system and
check for improved performance.
COAXIAL HEAT EXCHANGER FLUSHING PROCEDURE—GROUND LOOP
STEP 1
Isolate the heat exchanger by placing the pump module valves in the exchanger flushing position.
STEP 2
Connect a compressed air and a drain pipe to the pump module purge ports and blow the anti-freeze solu-
tion into a clean 5 gallon bucket.
STEP 3
Connect a purge cart to the pump module purge ports.
STEP 4
Place 2 gallons of RYDLYME in the purge cart. Circulate the fluid through the heat exchanger for at least 2
hours (3 recommended).
STEP 5
Disconnect the purge cart and dispose of the solution. RYDLYME is non-toxic and biodegradable and as
such can be poured down a drain. Clean the purge cart thoroughly.
*
Depending on the plumbing, there should be either unions or boiler drains for to access the heat exchanger.
STEP 6
Connect fresh water and a drain to the pump module purge ports and flush the exchanger for several
minutes.
STEP 7
Blow the heat exchanger out with compressed air as per STEP 2 and dump the water down a drain.
STEP 8
Connect the purge cart to the pump module purge ports. Re-fill and purge the heat exchanger with as per
standard procedures (the anti-freeze from STEP 2 can be re-used).
STEP 9
Disconnect the purge cart and set the pump module valves back to the original positions.
STEP 10
Operate the system and check for improved performance.
Summary of Contents for WH-Series
Page 9: ...1 Oct 2015 Page 9 002028MAN 01...
Page 11: ...1 Oct 2015 Page 11 002028MAN 01...
Page 12: ...Page 12 002028MAN 01 1 Oct 2015...
Page 13: ...1 Oct 2015 Page 13 002028MAN 01...
Page 16: ...Page 16 002028MAN 01 1 Oct 2015...
Page 19: ...1 Oct 2015 Page 19 002028MAN 01...
Page 43: ...1 Oct 2015 Page 43 002028MAN 01 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 56: ...Page 56 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 230 1 60...
Page 57: ...1 Oct 2015 Page 57 002028MAN 01 ELECTRICAL DIAGRAMS 208 230 1 60 continued...
Page 58: ...Page 58 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 220 1 50...
Page 59: ...1 Oct 2015 Page 59 002028MAN 01 ELECTRICAL DIAGRAMS 220 1 50 continued...
Page 60: ...Page 60 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 3 60...
Page 61: ...1 Oct 2015 Page 61 002028MAN 01 ELECTRICAL DIAGRAMS 208 3 60 continued...
Page 62: ...Page 62 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 380 3 50...
Page 63: ...1 Oct 2015 Page 63 002028MAN 01 ELECTRICAL DIAGRAMS 380 3 50 continued...
Page 64: ...Page 64 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 460 3 60...
Page 65: ...1 Oct 2015 Page 65 002028MAN 01 ELECTRICAL DIAGRAMS 460 3 60 continued...
Page 66: ...Page 66 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 575 3 60...
Page 67: ...1 Oct 2015 Page 67 002028MAN 01 ELECTRICAL DIAGRAMS 575 3 60 continued...
Page 68: ...Page 68 002028MAN 01 1 Oct 2015 REFRIGERATION CIRCUIT DIAGRAMS...
Page 69: ...1 Oct 2015 Page 69 002028MAN 01 DIMENSIONS WH 25 45 55 DIMENSIONS WH 65 75 80...