connections are fixed through tightening the nuts and hose clamps. If this doesn't
cure the problem - change hoses and fittings.
3.8 If the leakage can't be traced to the tubes and hoses, open up the valves to the
equipment one by one. Start by testing the hose connection between the valve
and the equipment. If the leakage can't be found here, there is a leakage in the
equipment (stove, oven etc.). If so contact a gas expert, to have the equipment
repaired and tested at 15 kPa (150 mbar).
3.9 Check again in accordance with 3.1 - 3.4.
3.10 To demonstrate the function and to test the detector turn one of the
burners on the stove on, and let it burn on low power. This simulates a leakage in the
system. Press and hold the red button on the leak detector. The bubbles now
appearing in the sight glass shows that the system is leaking (simulated by the
burning flame).
It is absolutely prohibited to use a leaking L.P.G. system!
Close the main valve till the leakage has been repaired!
By uncertainty
-
contact a professional, testing the system at
maximum 15 kPa (150 mbar).
GB
-
INSTRUCTIONS
4.0 EQUIPMENT WITH IGNITION SAFETY DEVICE
4.1 The leak detector can also be used for testing the ignition safety
device of the equipment. Two persons are required.
4.2 Turn on for instance a burner and let it burn on low power.
4.3 Press and hold the red button on the leak detector. It is now bubbling in the sight
glass constantly.
4.4 Blow out the burner and after 10 to 30 seconds the bubbling in the sight glass
should stop. If more than 60 seconds are required an expert has to be contacted.
5.0 REPAIRS I MAINTENANCE
5.1 The leak detector is virtually maintenance free. If the fluid level should drop below
the level mark propylene glycol must be refilled (Fig. 2c.).
6.0 WARRANTY
6.1 As per our current warranty regulations.
7.0 DISPOSAL AND RECYCLING
7.1 When the leak detector is not supposed to be used anymore, it has to be disposed
following the local environmental regulations. The leak detector 100 4000 is
approved by the Danish Governmental Gas Institute DGP (Notified Body for CE
approvals) Approval number DG-3795.