67
2. Temperature swings should be minimal to
prevent condensation.
3. If stored in an unheated or damp building,
space heaters will be required to prevent
internal condensation.
4. Treat unpainted flanges, shafts, drive
discs, and fittings with a rust inhibitor.
5. Check insulation resistance of all
windings before starting the generator. If
readings are low, the windings must be
dried.
C.
Keep bearings lubricated.
1. Every six months rotate shaft
several turns to distribute grease in bearings.
2. If unit has been stored more than
one year, add grease before start-up.
D. Review and follow instructions in
Sections 3 and 4 before putting the gen-set
into service.
CAUTION
DO NOT ATTEMPT TO TRANSPORT
ANYGENERATOR WITHOUT
PROPER ROTOR
SUPPORT, EXTENSIVE
EQUIPMENTDAMAGE CAN OCCUR.