LOW VOLTAGE -
NO LOAD
Under speed Operation
Defective Voltmeter
Residual Voltage
Incorrect Generator
Connections
Defective Connections /
Wiring
Regulator Adjustments
Defective Diodes, Surge
Suppressor, Generator
Windings
Voltage Regulator not
Operating
Check speed using tachometers
and/or frequency meters.
Verify operation of panel meter
with another meter that is known to
be accurate.
Disconnect Fl and F2 leads at the
voltage regulator. If voltage goes
down continue on to next step, if
voltage does not change refer to
troubleshooting for symptoms of
“No Voltage - No Residual
Voltage”.
Verify generator connections refer
to drawings supplied V generator
set and section 3.
Inspect all wiring for grounds, open
circuits, short circuits, and loose
and dirty connections.
Adjust regulator. Refer to regulator
manual. Check exciter field volts.
Test generator with constant
excitation (12 volt battery test)
Adjust or replace regulator. Refer to
regulator manual. Properly