Mount the OIT to the Panel
Mount ing Clip Bracket Place ment
Model
Left Side
Right Side
Top
Bottom
HMI5056T
0
0
2
2
HMI5080T
0
0
2
2
HMI5104T/X
0
0
3
2
HMI5121T/X
2
2
2
2
HMI5150X
2
2
2
2
STEPS:
1. Set the OIT in the panel cutout and hold it in place until all clamps are in position.
2. Tighten the screw clamps until all are uniformly snug.
Caution:
Do not over-tighten the screws beyond snugness, or you may damage the
housing.
REINSTALLATION: Because the gasket will take a “set” to the panel, be sure to reinstall
the OIT to the same panel cutout when a NEMA 4 seal is required. For best results, also
replace the gasket itself.
10
Sil ver Plus Se ries
1010-1006, Rev 01
Screw clamp locking
tabs go through the
slots
Tighten all screw clamps until
they are uniformly snug
Ends of screws must not
protrude from the clamp
Screw Clamp Placement
Clamps Tightened
Hold the OIT against
the panel until all screw
clamps are in position
Panel
Panel
In stall ing Screws to the OIT