DOC-FW562-UM-R1.0
INSTALLATION MANUAL
© 2021. MAPLE ARMOR FIRE ALARM DEVICE CO., LTD.
8866, boulevard du Quartier, Brossard, Quebec, Canada, J4Y 0R2
All rights reserved. www.maplearmor.com
Page
3
of
5
Figure 4 Duct Detector Installation
4.
Remove any rough edges from the holes.
5.
Seal the opening around the tube with an
approved duct sealant.
6.
Verify that all field wiring is free of opens, shorts,
and ground faults.
7.
Make all wiring connections as shown in Figure
5.
L1
L2
(N/A)
KEY
IN
KEY
TEST
LED-
LED+
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
Figure 5 Wiring Diagram
8.
Set the internal smoke detector address via the
handheld programmer FW412 or via panel
FW106. Refer to individual manuals for details.
Note: The duct FW562-A/B/C/ or FW562C-A/B/C
share the same address with the smoke
detector model FW511.
9.
You must perform an air differential pressure
test by using an Air Velocity Meter ex: Dwyer
model 460 or Reed R3001 or equivalent. Wright
down the air pressure differential value, next
you must select the appropriate model that falls
in the specified operating range.
10.
Duct detector assembly contains all 3 models in
a kit, the technician must set up the duct
detector per 1 of 3 figures. See below for proper
operation and certification.
11.
The FW562-A/B/C can be configured in 3 ways.
For model, FW562-A see figure 6, for model
FW562-B see figure 7 and for model FW562-C
see figure 8; the FW562C-A/B/C can be
configured 3 ways also, for model FW562C-A see
figure 9, for model FW562C-B see figure 10 and
for the model, FW562C-C see figure 11.
Figure 6
Figure 7