INSTALLATION MANUAL 
 

© 2021. MAPLE ARMOR FIRE ALARM DEVICE CO., LTD.  

8866, boulevard du Quartier, Brossard, Quebec, Canada, J4Y 0R2  

All rights reserved. www.maplearmor.com 

Page 

3

 of 

5

 

 

 

 

Figure 4 Duct Detector Installation 

 
4.

 

Remove any rough edges from the holes.  

5.

 

Seal  the  opening  around  the  tube  with  an 
approved duct sealant. 

6.

 

Verify that all field wiring is free of opens, shorts, 
and ground faults. 

7.

 

Make all wiring connections as shown in Figure   
5. 
 

L1

L2

(N/A)

KEY
IN

KEY
TEST

LED-

LED+

(N/A)

(N/A)

(N/A)

(N/A)

(N/A)

(N/A)

(N/A)

 

           Figure 5 Wiring Diagram 

 

8.

 

Set the internal smoke detector address via the 
handheld  programmer  FW412  or  via  panel 
FW106.  Refer to individual manuals for details. 
Note: The duct FW562-A/B/C/ or FW562C-A/B/C 
share  the  same  address  with  the  smoke 
detector model FW511.  

9.

 

You  must  perform  an  air  differential  pressure 
test  by  using  an  Air  Velocity  Meter  ex:  Dwyer 
model 460 or Reed R3001 or equivalent. Wright 
down  the  air  pressure  differential  value,  next 
you must select the appropriate model that falls 
in the specified operating range.  
 

10.

 

Duct detector assembly contains all 3 models in 
a  kit,  the  technician  must  set  up  the  duct 
detector per 1 of 3 figures. See below for proper 
operation and certification.  

11.

 

The  FW562-A/B/C  can  be  configured  in  3  ways. 
For  model,  FW562-A  see  figure  6,  for  model 
FW562-B  see  figure  7  and  for  model  FW562-C 
see  figure  8;  the  FW562C-A/B/C  can  be 
configured 3 ways also, for model FW562C-A see 
figure 9, for model FW562C-B see figure 10 and 
for the model, FW562C-C see figure 11.  

 

Figure 6 

 

 

Figure 7 

Summary of Contents for FW562-A

Page 1: ...he product for use in promotional or advertising claims or for any other use including a description of the product s application operation installation and testing is the sole responsibility of the user Maple Armor will not assume any liability for such use In no case will Maple Armor s liability exceed the purchase price paid for a product SPECIFICATION Nominal Voltage 24V dc SLC Voltage Range 1...

Page 2: ...as long as the diameter is 12 inches or more Step 5 If possible try to install the duct detector in an accessible location Step 6 If the duct detector is hidden in a ceiling you will need to install a remote indicating light in the ceiling under the detector to show the location Step 7 It can be installed horizontally on a duct as narrow as 6 inches and vertically on a duct as wide as 16 inches St...

Page 3: ... for details Note The duct FW562 A B C or FW562C A B C share the same address with the smoke detector model FW511 9 You must perform an air differential pressure test by using an Air Velocity Meter ex Dwyer model 460 or Reed R3001 or equivalent Wright down the air pressure differential value next you must select the appropriate model that falls in the specified operating range 10 Duct detector ass...

Page 4: ...LTD 8866 boulevard du Quartier Brossard Quebec Canada J4Y 0R2 All rights reserved www maplearmor com Page 4 of 5 Figure 8 Figure 9 Figure 10 Figure 11 When the part number is determined use the blank sticker to cover the additional part numbers shown on the label See Figure 12 ...

Page 5: ...test the detector to ensure it is operating correctly Main function Models FW562 A B C and FW562C A B C Duct Smoke Detectors utilize photoelectric smoke detectors for the detection of smoke When sufficient smoke is sensed an alarm signal is initiated Test function Alarm simulation Pressing the TEST SW can simulate an alarm condition Cover tightness monitor When the JUMPER switch is on the NORMAL s...

Reviews: