background image

DOC-FW562-UM-R1.0 

INSTALLATION MANUAL 
 

© 2021. MAPLE ARMOR FIRE ALARM DEVICE CO., LTD.  

8866, boulevard du Quartier, Brossard, Quebec, Canada, J4Y 0R2  

All rights reserved. www.maplearmor.com 

Page 

5

 of 

5

 

 

 

Figure 12 Label check 

 

12.

 

To verify the air pressure differential 

To verify air pressure differential, air must be moving 
through the HVAC system.  

Connect  a  suitable  air  pressure  differential 

meter  model  Reed  R3001  or  equivalent  to  the 
sampling tube and exhaust  tube openings as shown 
in Figure 13.

 

 

Figure 13 Air Pressure measure 

 

13.

 

Verify  that  the  air  pressure  differential 
measured  falls  within  the  specified 
operating range of the detector.  

Model  

Air pressure 

FW562C-A 

0.36 to 1.53 iwg (inches of water) 
90 to 380 Pa (Pascals) 

FW562C-B 

0.04 to 0.4 iwg (inches of water) 
9 to 100 Pa (Pascals) 

FW562C-C 

0.004 to 0.06 iwg (inches of water) 
1 to 15 Pa (Pascals) 

FW562-A 

0.32 to 1.41 iwg (inches of water) 
80 to 350 Pa (Pascals) 

FW562-B 

0.1  to 0.4 iwg (inches of water) 
25 to 100 Pa (Pascals) 

FW562-C 

0.004 to 0.14 iwg (inches of water) 
1 to 35 Pa (Pascals) 

14.

 

If  the  air  pressure  differential  measured 
does not  fall within the specified operating 
range  of  the  detector,  make  sure  the 
sampling  tube  air  holes  are  not  obstructed 
and are facing the HVAC system airflow.   

15.

 

After  completing  the  installation  of  the  duct 
smoke detector, test the detector to ensure it is 
operating correctly. 
 

Main function 

Models FW562-A/B/C and FW562C-A/B/C Duct 
Smoke Detectors utilize photoelectric smoke 
detectors for the detection of smoke. When 
sufficient smoke is sensed, an alarm signal is 
initiated.  
 

Test function 

 

Alarm simulation: Pressing the TEST SW can 
simulate an alarm condition.  

 

Cover tightness monitor: When the JUMPER 
switch is on the NORMAL side, a trouble event 
will be annunciated when the cover is not 
secured properly. When the JUMPER switch is 
on the TEST side, this feature will be bypassed. 
Note the TEST mode should only be used in 
installation and field testing.  

 

To clean the duct smoke detector 

1.

 

Disable  the  detector/zone  to  prevent  false 
alarms.  

2.

 

Remove the detector

s cover then power down 

the detector by disconnecting the SLC wiring.  

3.

 

Using a vacuum cleaner, or clean compressed air, 
with a  soft  bristle brush, remove loose dirt and 
debris  from  inside  the  detector  housing  and 
cover.  

4.

 

Remove  dirt  and  other  contaminants  from  the 
gasket  on  the  detector

s  cover  using  isopropyl 

alcohol and a lint-free cloth.  

5.

 

Squeeze  the  retainer  clips  on  both  sides  of  the 
optic  housing  then  lift  the  housing  away  from 
the printed circuit board.  

6.

 

Gently remove dirt  and debris from around the 
optic plate and inside the optic housing.  

7.

 

Replace  the  optic  housing  and  detector  cover, 
and then connect the SLC wiring. 

 
Return the product for reparation if it fails to flash or 
alarm during testing. Do not disassemble the 
product without permission. 
 

Summary of Contents for FW562-A

Page 1: ...he product for use in promotional or advertising claims or for any other use including a description of the product s application operation installation and testing is the sole responsibility of the user Maple Armor will not assume any liability for such use In no case will Maple Armor s liability exceed the purchase price paid for a product SPECIFICATION Nominal Voltage 24V dc SLC Voltage Range 1...

Page 2: ...as long as the diameter is 12 inches or more Step 5 If possible try to install the duct detector in an accessible location Step 6 If the duct detector is hidden in a ceiling you will need to install a remote indicating light in the ceiling under the detector to show the location Step 7 It can be installed horizontally on a duct as narrow as 6 inches and vertically on a duct as wide as 16 inches St...

Page 3: ... for details Note The duct FW562 A B C or FW562C A B C share the same address with the smoke detector model FW511 9 You must perform an air differential pressure test by using an Air Velocity Meter ex Dwyer model 460 or Reed R3001 or equivalent Wright down the air pressure differential value next you must select the appropriate model that falls in the specified operating range 10 Duct detector ass...

Page 4: ...LTD 8866 boulevard du Quartier Brossard Quebec Canada J4Y 0R2 All rights reserved www maplearmor com Page 4 of 5 Figure 8 Figure 9 Figure 10 Figure 11 When the part number is determined use the blank sticker to cover the additional part numbers shown on the label See Figure 12 ...

Page 5: ...test the detector to ensure it is operating correctly Main function Models FW562 A B C and FW562C A B C Duct Smoke Detectors utilize photoelectric smoke detectors for the detection of smoke When sufficient smoke is sensed an alarm signal is initiated Test function Alarm simulation Pressing the TEST SW can simulate an alarm condition Cover tightness monitor When the JUMPER switch is on the NORMAL s...

Reviews: