To adjust temperature set point, follow the next steps:
Push enter key an hold for three seconds and the next menu appears:
Then push index key two times and next display appears:
By pressing down arrow key or up arrow key, is possible to change temperature set point the
required value.
7.2
PID control parameters adjusting
If is required, from temperature adjusting display, is possible to access to PID control parameters:
•
If index key is pushed once, then is possible to adjust proportional band in % (by using arrow keys), in
the next display.
•
If index key is pushed twice, then is possible to adjust integration time in seconds (by using arrow keys),
in the next display.