ME3000-RPFS   WATER  BATCHING  SYSTEM   

 

Congratulations on choosing a 

ManuFlo

 

®

  (Manu Electronics)  preset batch control system. 

You will now join many thousands of satisfied customers worldwide. 

 

Your system comprises: 
 

 

 
 
 

 

Information sheets included: 

1.  ME3000 preset Batch Controller  specification and options. 
2.  Installation Guide (plumbing/commissioning). 
3.  Basic electrical wiring guide. 
4.  Flowmeter brochure spec (chosen flowmeter normally RPFS) 
5.  (if ordered) PLC/computer interface spec brochure 
6.  ME3000 complete user manual 
 

 

 

Prior to installation: 

A.  Consider a good viewing AND operating position for the ME3000 Batch Controller. 

 

B. 

Remove the detachable 10-pin plug from the rear of the ManuFlo controller. Wire the 240vac supply. 
Wire  the  Active/contact  drive,  Neutral  and  Earth  from  the  solenoid  valve  or  return  from  the  external 
contactor if driving a pump. If starting a pump, make sure the contactor is of sufficient amperage rating 
to  handle  the  pump  current  draw.  Consider  wiring  an  override  button  (N.O.  with  spring  return)  for 
manual batching or top up of water, which will be counted by the controller display. See wiring 

 

C.  Install the flowmeter as per the installation guide found on the flowmeter brochure. 

Install the Rota Pulse paddlewheel sensor (RPFS-P) in a straight pipe section, with the same diameter pipe as 
the adaptor tee section, with 10x diameter before, and 5x diameter after, the sensor with no elbows, reducers, 
valves or restrictions within this pipe run. Where the sensor is housed, the pipe must be full when measuring.

 

 

D.  Use shielded cable only for connection between flowmeter and Batch Controller. 

 

E. 

On  pipe  sizes  over  50mm,  consider  using  an  air-assisted  solenoid  butterfly  or  angle  seat  valve,  as 
electrically-operated diaphragm valves can be very slow in closing (valves are available from 

ManuFlo

 

®

). Preferably, use a 240vac solenoid coil, as the Manu controller provides 240vac to the coil when 

started. Otherwise, consult 

ManuFlo 

®

 for options.

F.  The ME3000 Batch Controllers, when used with flowmeters, have internal preset calibration 

factory  calibrated  with  water.  When  using  other  varying  viscosity  liquids  with  some 
flowmeters, a calibration test will need to be performed, and the K-factor re-programmed to 
the corresponding result.  A calibration check must be performed prior to continuous use and 
commissioning  of  the  system  (see  installation  guide).  Recalibration  may  be  necessary  for 
flowmeters other than PD or Magflow flowmeters. See page 13 of the manual. 

 

 

If unsure on any aspect of installation or operation, call ManuFlo or your local installer. 

 

 

 

 

 

Happy batching !!!!!!!!!!!!! 

 
 
 

Summary of Contents for ManuFlo ME3000-RPFS

Page 1: ...flowmeter as per the installation guide found on the flowmeter brochure Install the Rota Pulse paddlewheel sensor RPFS P in a straight pipe section with the same diameter pipe as the adaptor tee section with 10x diameter before and 5x diameter after the sensor with no elbows reducers valves or restrictions within this pipe run Where the sensor is housed the pipe must be full when measuring D Use s...

Page 2: ...nd continuously if an error occurs With the ME3000 Batch Controller using the same instrument housing and the same 10 pin Weidmuller receptacle plug as other ManuFlo Batch Controller models changeover or upgrade is instant with no rewiring necessary It can be easily interfaced with PLCs through the optional computer control interface thus incorporating the controller s safety features and providin...

Page 3: ...nfiguration value is diplayed entering a new value via the keypad causes the display value to change and flash Then pressing SET locks in the new value or pressing CANCEL reverts value to its original setting and the display digits stop flashing Use the up down arrows buttons to step through more configuration settings or press CANCEL for 2 seconds to exit to the SET RDY display CALIBRATION 1 The ...

Page 4: ...nel Eagle etc PLCs MC 4 pin PLC Computer Command Start Stop Reset interface plug MC2 2 pin plug for scaled open collector pulse output Includes 4 pin external command Start Stop Reset interface plug e g ME3000 is the standard Batch Controller 240vac powered without any of the options whereas ME3000 MC2 is an ME3000 Batch Controller with a scaled open collector pulse o p and external Start Stop Res...

Page 5: ...tion to larger size pipes is possible depending on pipe wall thickness alternatively the Long Stem LS versions with adaptors are then used With only one moving part and limited intrusion into the pipe and combined with its flow through design the RPFS allows accurate measurement of liquid flows with virtually no head losses Each of the 4 blades of the rotor paddlewheel extends approximately one ce...

Page 6: ...G 6 1 Unscrew the black PVC locking cap anti clockwise 2 Hold the neck of the Tee piece in your left hand grasp the RPFS body with your right hand and turn slowly anti clockwise until the sensor hydraulically raises out of slot then pull upwards out of the socket never by the cable When returning the sensor to nipple adaptor insert so the keyway and slots line up then then push down until they loc...

Page 7: ...e If mounted in horizontal or inclined pipe make sure insertion position of sensor is at top or 45 from top not on the underside Selection of pipe diameter For best results use the table below Pipe size Flowrange Litres min Pulses Litre mm Min Max approx 1 2 20 13 160 116 25 20 250 75 32 30 410 46 40 50 640 30 50 90 1000 20 63 132 1580 11 7 65 120 1690 12 75 180 2250 8 3 80 190 2560 7 3 90 244 324...

Page 8: ...25 LS 140 mm SC140 LS 150 mm PVC150SC LS SCP150 LS SC160 LS 160 mm SCPE160 LS SC160 LS 200 mm PVC200SC LS SCP200 LS SC200 LS 225 mm SCPE225 LS SC225 LS 250 mm SCP250 LS SC250 LS 280 mm SC280 LS 300 mm PVC300SC LS SCPE300 LS SC315 LS Galvanised iron threaded ends BSP female 2000 kPa Note 25mm can be supplied with straight pipe sections already fitted Part GAL25 T2 PVC T piece Class 18 Cat 19 Glue i...

Page 9: ...4 ME3000 ME995 wiring with RPFS or other powered flowmeters ...

Page 10: ...5 ME3000 ME995 wiring with RPFS or other powered flowmeters ...

Page 11: ...6 PLUMBING INSTALL options guide for RPFS or other ManuFlo flowmeters ...

Page 12: ...7 ...

Page 13: ...blem Calcium buildup on wheel soak in diluted acid Warn bushes Backflow alarm Non return valve faulty jammed open Clean service or replace after batch complete Solenoid valve not properly closed damaged seal faulty solenoid Batch target display counter Flowrate too fast excessive overflow Turn down gate valve to restrict flowrate counts past batch selection or set preact overflow deduct function t...