I.  Trouble Shooting 

 

PROBLEM 

INDICATIONS 

POSSIBLE CAUSES 

SUGGESTED SOLUTION 

Charger does not 
work   

LCD display not 
turn on   

No AC power 
 
AC input socket fuse blown   

Check AC connections are correct   
 
Replace with correct AC fuse by 
qualified electrician 

No DC output   

Output short circuit 
symbol displays 
 
 
 
Charger over 
temperature 
symbol displays 
 
Overload (OCP) 
symbol displays 
 
Reverse polarity 
symbol displays 
 
Fan stuck symbol 
displays 

Output short circuit   
 
 
 
 
Over temperature protection triggered   
 
 
 
Severe over loading charger 
 
 
Reverse polarity connection 
 
 
DC fan locked by foreign object or 
malfunction 

Check DC connections between 
charger and battery. Charger can auto 
reset if remove the fault within 20 
seconds. 
 
Check air intake vent at bottom of 
charger is blocked or not. Check 
charger ambient ventilation. 
 
Check battery AH capacity within 
recommended range 
 
Check for correct polarity 
 
 
Check DC fan 

Battery does not 
get full charge 

LCD displays work 
normally and 
sequentially   
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Bad battery connection   
 
 
Battery type select switch in wrong 
setting 
 
Battery capacity too large 
 
 
Ambient temperature too low   
 
 
 
Battery has damaged cell or battery is 
too old   
 
Wrong set the lower power level 

Check for loose contact, right cable 
size, cable integrity 
 
Recheck battery type and change to 
correct battery selection 
 
Make sure charger rating matches 
battery capacity 
 
Move battery to a room temperature 
location, or get an optional 
temperature sensor   
 
Replace battery 
 
 
Recheck the current selection switch 
(5) to correct right setting 

Long charging 
time, float curve 
does not come on 
even after 20 
hours charging 
time. 

Absorption curve 
remains display all 
the time   

Charger internal fault   

Return the charger to distributor to 
repair   

Bulk curve is 
display all the time

 

Bulk curve 
remains on all the 
time   

Wrong battery type selection 
 
 
 
Battery is excessively depleted and 
the soft charging is triggered     
 
 
 
 
Battery temperature too high 

Check charged battery label and 
change battery type selection to 
correct setting 
 
Recharge the battery after a day, if 
bulk light remains after several hours, 
the battery is most likely damaged and 
cannot accept charge. Replace 
battery. 
 
Use accessory temperature sensor 

 
 
 
 

Summary of Contents for SBC-9138

Page 1: ...not charge the battery on boats Remove the battery and charge on shore Never attempt to charge a frozen battery Never attempt to charge a damaged battery Wear protective goggles and turn your face awa...

Page 2: ...ting The extensive protection with alarm and LED indications including the thermostatic decrease of charging current to shut down ensure a durable working life span even in harsh conditions for the ch...

Page 3: ...emovable temperature sensor RED battery clamp Battery positive pole BLACK battery clamp Battery negative pole 8 Removable temperature sensor To increase decrease charging voltage at low high battery t...

Page 4: ...de a constant voltage DC power 13 3V to the external load connected to the battery and at the same time without over charging the battery B1 Recommended Battery Capacity The following minimum AH capac...

Page 5: ...t GEL and Charging Current Selection Switch 5 for output current setting default at 100 When install in caravans and similar vehicles the connection to the supply mains is to be in accordance with nat...

Page 6: ...h slow flashing If the charger cannot go to Absorption mode within 20 hours the charger will automatically goes to Float mode so to prevent over charge the battery This is call safety timer Stage 4 AB...

Page 7: ...on mode in this charging cycle and the charging will be conducted after Absorption mode After entered into this mode the Recondition curve REC will display with slow flashing This will put the charger...

Page 8: ...hich is not affected by other cooling or heating source Or you can insert it into the power cable negative battery clamp factory pre mounted The reference temperature of this sensor is 25 C and compen...

Page 9: ...stuck or not working F5 Faulty battery F6 Battery temp over 60 C as detected by remote sensor F7 short circuit 5 sec shut down otherwise auto recover Remark F7 is for power supply only F8 Reverse pol...

Page 10: ...onnection Battery type select switch in wrong setting Battery capacity too large Ambient temperature too low Battery has damaged cell or battery is too old Wrong set the lower power level Check for lo...

Page 11: ...oise Peak to Peak 200mV Efficiency at WET 230VAC 85 Protections Short Circuit Protection Yes Overload Protection Yes Reverse Polarity Protection by Mosfet Yes Over Temperature Protection Yes OVP Outpu...

Reviews: