F822 Encoder 1 failure: signal amplitude wrong
The analog signals of a motor measurement system are used for high
resolution analysis of that measurement system. These are monitored
according to two criteria:
1.
The pointer length, which is calculated from the amplified sine
and cosine signals, must be at least 1 V.
2.
The maximum pointer length resulting from the sine and cosine
signals must not exceed 11.8 V.
2
2
cos
sin
length
pointer
+
=
Fig. 3-5:
Pointer length
Permissible signal amplitudes for sine and cosine signals
cosine signal amplitude
15
10
0
-5
-10
5
-15
-15
-10
-5
0
5
10
15
sine signal amplitude
Dg5004a1.fh7
nominal pointer length (9,2V)
minimum pointer length > 1,0V
maximum pointer length > 11,8V
=non-permissible range
Fig. 3-6:
Correct signal amplitude
Example:
Ucos = -6,5V
Usin = 6,5V
(
)
V
9.2
6.5V
6.5V
length