Document Number: 000013527 Rev01  01/16

 

Subject: K00459 S Model Bin Thermostat

®

        

         

7.  Route thermistor wire out towards the back of the 

dispenser (lower the ice machine, if supported). 
Remove unused 7/8” diameter knockout on the back 
panel, snap fit the bushing over the exposed panel 
hole, and route wire into the ice machine control board 
compartment. Internally the cable must be routed as 
to avoid contact with high voltage, high heat, or sharp 
objects.

8.  Normally the controller can be mounted on the 

bulkhead flange. If not, a suitable area must be found 
for your model. Use controller bracket to locate 
mounting holes on the flange of the bulkhead. Drill 
two 9/32” diameter holes. Do not mount the controller, 
at this time.

9.  Route the four wires from the temperature control to 

the control box (insuring that the wires  will not come 
in contact with any refrigeration tubing).

Caution

The thermostat must be wired to match the voltage of 
the ice machine. The thermostat is factory wired for 115 
volts. Rewire thermostat, if your ice machine is 240 volts.

10.  The control box line voltage wiring offers two options:

•  Connect thermostat L1 (brown) and L2 (blue) 

wires to contactor (incoming line voltage side) 
L1 and L2.

OR

•  Disconnect incoming power line wire nuts. 

Remove quick-connect fittings from brown and 
blue wires and strip 1/2” of insulation from the 
wires.  Connect incoming power L1, ice machine 
L1, and thermostat L1 (brown) wires together 
with wire nut. Connect incoming power L2, ice 
machine L2, and thermostat L2 (blue) wires 
together with wire nut..

11. Connect bin switch wires:

Manitowoc Models

A.  Disconnect the red male/female connector bin 

switch wire and connect the red male wire from 
the controller to the red female bin switch wire.

B.  Connect the white male bin switch wire to the 

white female wire of the controller.

KoolAire Models

A.  Cut the red bin switch wire 3 inches from molex 

connector on bin switch.

B.  Strip wires and install male and female crimp 

connectors  supplied in kit.

C.  Connect male and female connectors from the bin 

thermostat into the newly installed terminals.

12. Restore all power to the ice machine and dispenser at 

the service-disconnect or fuse/breaker panel.

13. The factory setting on the thermostat will be correct for 

most applications.  Adjust only when necessary.

14. With two screws, secure the controller bracket 

assembly to the flange of the bulkhead.

15. Reinstall the control box cover and all panels.

Summary of Contents for K00459

Page 1: ...spenser away from the wall for easier access 2 Bracket selection A Dual evaporator ice machines Use bracket with the shorter top flange B Single evaporator ice machines Use bracket with the longer top flange 3 Remove all panels and control box cover from the ice machine 4 If an ice machine is already installed on the dispenser Remove the fasteners securing the ice machine to the adapter located on...

Page 2: ...ct thermostat L1 brown and L2 blue wires to contactor incoming line voltage side L1 and L2 OR Disconnect incoming power line wire nuts Remove quick connect fittings from brown and blue wires and strip 1 2 of insulation from the wires Connect incoming power L1 ice machine L1 and thermostat L1 brown wires together with wire nut Connect incoming power L2 ice machine L2 and thermostat L2 blue wires to...

Page 3: ...int to 38 F A Press and hold the Menu button until the display changes to flashing SP This will take about 2 seconds B Press the Menu button again The current set point is displayed C Press the Up or Down button to adjust the set point temperature D Press the Menu button to save The display then returns to the sensor temperature 3 Setting the Differential at 2 A Press and hold the Menu button unti...

Page 4: ...power source and input power wires for problems 2 Check for Fault Codes If the LCD displays an alarm or fault code SF or EE Fault Code Definition Solution SF flashing alternately with OP Open temperature sensor or sensor wiring See Step 3 Cycle power to reset control SF flashing alternately with SH Shorted temperature sensor or sensor wiring See Step 3 Cycle power to reset control EE Program failu...

Reviews: