Internal Condenser Volume
The multi-circuit condenser internal
volume must not be less than or exceed
that used by Manitowoc. Do not exceed
internal volume and try to add charge to
compensate, as compressor failure will
result.
Model
Minimum
ft
3
(cm
3
)
Maximum
ft
3
(cm
3
)
IT0500N
IF0500N
0.020
(566)
0.030
(850)
IF0600N/IF0900N
IT1200N
0.045
(1274)
0.060
(1699)
IT1500N/IT1900N
0.085
(2407)
0.105
(2973)
Heat of Rejection
Model
Peak
Average
IF0500N
6900
6100
IT0500N
6900
6100
IF0600N
13900
9000
IF0900N
16000
13000
IT1200N
24500
20700
IT1500N
27000
23000
IT1900N
30500
26100
Refrigerant Charge
The ice machine model/serial tag lists the
refrigerant amount. Remote condensers
and line sets contain a vapor charge only.
Model
Amount
Type
IF0500N
6.0 lbs - 2.72 kg
R404A
IT0500N
6.0 lbs - 2.72 kg
R410A
IF0600N
6.5 lbs - 2.95 kg
R404A
IF0900N
7 lbs - 3.18 kg
R404A
IT1200N
7.5 lbs - 3.40 kg
R410A
IT1500N
7.5 lbs - 3.40 kg
R410A
IT1900N
8.0 lbs - 3.63 kg
R410A
Model/serial plate information overrides all data
listed in this chart.
Quick Connect Fittings
The ice machine and line sets come with
quick connect fittings. It is recommended
that matching quick connects (available
through Manitowoc Distributors K00129)
be installed in the multi-circuit condenser,
and that a vapor “holding” charge, 5 oz.
(150 ml), of proper refrigerant be added to
the condenser prior to connection of the
ice machine or line set to the condenser.