Gas hot-air heater MONZUN
|
instalation, operation instractions and maintenance manual
8
|
EN
INSTALATION
The minimum distance between the surface of the heater and oth-
er surfaces is indicated on the picture below. The minimum distance
between the non-insulated flue duct and flammable materials is
500 mm. From face side is minimum distance 3,000 mm.
It is not permitted to discharge flue gas through the wall/ceiling from
combustible materials.
The heater must be installed in accordance with applicable standards
and regulations.
Hot air heaters cannot be installed in places with a potential explo-
sion hazard such as storages of gasoline, solvents, oil, places with
presence of chlorine vapor, trichlorethylene, perchlor, or high flam-
mable dust and wood chips etc.
The equipment must be installed by qualified personnel, accord-
ing to the manufacturer’s instructions and applicable standards
(EN 1020, Art. 7.4.; EN 15001-1, TPG 704 01)
BEFORE INSTALLING, CHECK:
• Local conditions of fuel distribution, fuel characteristics, overpres-
sure, existing status heater settings in the production plate are
compatible.
• Main conditions of electrical power supply are compatible with
electrical data on the label.
•
The temperature of the flue gas at the outlet of the heater does
not exceed 200 °C!
The use of heaters in a corrosive environment is prohibited!
THE MANUFACTURER IS NOT RESPONSIBLE FOR DAMAGES CAUSED BY INCORRECT INSTALLATION
Installation principles
The conditions for connecting gas heaters to the for gas distribution
and to the electricity network are given in chapters Examples of typi-
cal design of flue gas exhaust and combustion air supply.
The amount of combustion air for heaters must comply with relevant
standards and regulations.
Recommended installation height Z (mm) of heaters MONZUN (with
outlet with tilting louvers on discharge) is listed in
Tab. 3
.
Minimum space for heater installation:
Free access (min. 500 mm) to the burner chamber and to the exchanger must be provided from the sides. Determination of the safety distance
of heaters and exhaust pipes from the surface of building materials must comply with the relevant standards. See
Pic. 5
and
Pic. 6
.
Pic 5:
Minimum space for installation on the wall
Pic 6:
Minimum space for installation under the ceiling