MONZUN [kW]
Dimensions [mm]
A
B
C
M
T
15, 20
785
533
700
458
2,200
30, 40
995
533
755
668
2,500
50, 60
1,200
533
776
668
3,000
Tab 3:
Mounting dimensions – MONZUN Z(V)
The MONZUN heater has four suspension points on the upper panel
and four suspension points on the lower panel, which are fitted with
M8 bolts, for which it is attached to a supporting structure, e.g. on
a bracket. Select the location of the MONZUN heaters so that the en-
tire space is ventilated.
Pic 7:
Example of installation of MONZUN heaters in heated space
A
Flue gas exhaust
B
Air supply for combustion
C
Grommet PG 13.5 (4 pcs)
D
Service switch
E
Earthing clamp
F
Gas connection
Pic 8:
Connection points of the MONZUN heater
Gas connection installation
Connection of heaters with output power up to 50 kW is solved
according to EN1775 Gas supply – gas pipelines in buildings – op-
erational requirements; connection of heaters over 50 kW is solved
according to EN 15001-1 Gas supply – Gas pipelines with operating
pressure higher than 0.5 bar for industrial use and gas pipelines with
operating pressure higher than 5 bar for industrial and non-industri-
al use. In the piping, a stable non-fluctuating gas pressure must be
guaranteed during operation of the heater. See
Tab. 2
.
The gas line must be terminated with a gas ball valve near the
heater connection (Pic 9)
The actual connection of the heater to
the gas through a flexible gas hose or through a screw connection.
The gas inlet pipe is terminated with an external thread G3/4”, the
minimum gas hose diameter is 15 mm. The ball valve and gas hose
are not part of the heater.
A
Thread G ¾“
B
Ball valve
C
Gas hose
Pic 9:
Connection MONZUN heater to the gas distribution