(placed on the casing of fire damper)

(placed on the casing of fire damper)

(placed on the casing of fire damper)

Before  entering  the  dampers  into  operation  after  their  assembly  and  by  sequential  checks,  the  following  checks  must  be  carried  out.  Visual
inspection of proper damper integration , inside damper area, damper blade, contact surfaces and silicon sealing.  Check of thermal protective
fuse and closing mechanism. Check the closing function of the damper blade. This can be done by removing of thermal fuse from damper body.

Before  entering  the  dampers  with  actuating  mechanism  into  operation  after  their  assembly  and  by  sequential    checks.  Check  of  blade
displacement into the breakdown position "CLOSED" can be done after cutting off the actuating mechanism supply (e.g. by pressing the RESET
button  at  the  thermoelectrical  starting  mechanism  BAT  or  cutting  off  the  supply  from  ELECTRICAL  FIRE  SIGNALISATION).  Check  of  blade
displacement back into the "OPEN" position can be done after restoration of power supply (e.g. by releasing the RESET button or restoration of
supply from ELECTRICAL FIRE SIGNALISATION).

Without  power  supply,  the  damper  can  be  operated  manually  and  fixed  in  any  required  position.  Release  of  the  locking  mechanism  can  be
achieved manually or automatically by applying the supply voltage. It is recommended to provide periodical checks, maintenance and service
actions on Fire Equipment by Authorized persons. The authorized persons can be trained by Producer, or by authorized Distributor. All effective
safety standards and directives must be observed during fire damper assembly.

For regular or exceptional inspection of interior of fire damper, micro-camera device can be used. On each fire damper is ispection hole. In the
case of inspection by camera, take out the black rubber cap, insert the camera inside the damper, check interior and at the end of inspection, put
the rubber cap back tightly to cover the empty hole.

WEIGHT (kg):

Dobříšská 550, 267 24 Hostomice, Czech Republic

MANDÍK, a.s.

ACTUATING SYSTEM:

YEAR/SER.NO.:

DIMENSION:

1391

EN 15650:2010 

TPM 125/17

R

FIRE PROTEC. CLASS:

MANUAL

Cert. No.: 1391-CPR-2020/0131, DoP: PM/FDMS(FDMS-VAV)/01/20/2

Summary of Contents for FDMS

Page 1: ......

Page 2: ...n accordance with one of the following standards EN 54 5 EN 54 7 EN 54 12 or EN 54 20 The damper must be controlled by an actuator connected to a higher level supervisory and constrol system Correct o...

Page 3: ...here must by installed inspection door externally on the duct next to the fire damper The damper is equipped with additional collar around the position of the blade On the collar there are positioned...

Page 4: ...ible connect to the building management system or superordinate control system by wires which are mounted to the switch Design with mechanical control can be complemented with a limit switch signaling...

Page 5: ...on OPEN to the position CLOSE takes maximal 20s In the case that the power supply is restored again the blade can be in arbitrary position the actuator starts re displacing the damper s blade position...

Page 6: ...ordinate system controls via the same wiring to the actuating mechanism To allow more simple connection the actuator BFL BFN 24 T ST is equipped with two connecting plugs one with three jacks and one...

Page 7: ...sition within the preset time the appropriate on board FAULT LED flashes and at the same time the fault contact K1 is activated K1 is group alarm for all 9 dampers This contact is overridden as soon t...

Page 8: ...8 AC 24 V 50 60Hz 3 5 W operating position 5 5 VA III safe small voltage IP 30 0 50 C Terminals for conductor 2 x 1 5 mm...

Page 9: ...of the blade from the position OPEN to the position CLOSE takes maximal 20s In the case that the power supply is restored again the blade can be in arbitrary position the actuator starts re displacing...

Page 10: ...the specified field of application It may only be installed by suitably trained personnel Any legal regulations or regulations issued by authorities must be observed during assembly BU blue BN brown...

Page 11: ...C Ri 100 k 50 k 0 4 20 mA Rext 500 0 2 10 VDC max 0 5 mA closed Vmin Vmax open normal duty storage temperature 0 C 50 C 20 C 80 C controller actuators screw terminals 4 pin 0 5 2 5 mm cable 1000 mm wi...

Page 12: ...DM3 Actuating mechanism flow direction Controller GUAC PM3 p Pa Static pressure difference between p duct and surrounding environment s s air outlet Room Actuating mechanism Controller GUAC PM3 p Pa...

Page 13: ...80 200 225 250 280 315 355 400 450 BFN24 T ST BFN230 T 500 560 630 98 190 113 313 405 12 70 163 123 215 113 353 445 2 32 90 163 158 250 113 398 490 24 5 54 5 112 5 163 178 270 2 5 113 448 540 49 5 79...

Page 14: ...14 50 50 41 575 146 125 D D1 2 x D min 2 x D min C...

Page 15: ...r and the construction wall ceiling must be minimum 75 mm In case that two or more dampers are supposed to be installed in one fire separating construction the distance between the adjacent dampers mu...

Page 16: ...lid ceiling construction 110 Concrete 125 Aerated concrete Wet Mortar or gypsum Outside solid ceiling construction with 110 Concrete 125 Aerated concrete insulation of the pipe between wall and dam pe...

Page 17: ...ness 1mm e g PROMASTOP P or K Fire damper FDMS Anchor for damper collar e g FISCHER type ZYKON FZA M8x30 Fixing part of the pipe between wall and pipe only recommended Hanging ring e g FISCHER type LG...

Page 18: ...18 Fire classification 96 47 47 96 96...

Page 19: ...00 Fire classification Connecting surface between wall and pipe insulation fulfil with fire resistant sealant before instalation of the insulation recommended type of sealant see instalation instructi...

Page 20: ...ire damper FDMS Anchor for damper collar threaded rod and nuts M8 or e g anchor FISCHER type KD8 Fixing part of the pipe between wall and pipe only recommended Hanging ring e g FISCHER type LGS Inspec...

Page 21: ...21 Fire classification 96 47 47 96 96...

Page 22: ...00 Fire classification Connecting surface between wall and pipe insulation fulfil with fire resistant sealant before instalation of the insulation recommended type of sealant see instalation instructi...

Page 23: ...KON FZA M8x30 Fixing part of the pipe between wall and pipe optional Hanging ring e g FISCHER type LGS Inspection hole for camera covered with removable air tight rubber cap Fire classification View A...

Page 24: ...24 Fire classification 96 47 47 96 96...

Page 25: ...anging ring e g FISCHER type LGS Inspection hole for camera covered with removable air tight rubber cap Installation of pipe insulation perform according instructions of the manufacturer This fixing p...

Page 26: ...nd pipe only recommended Hanging ring e g FISCHER type LGS Permeation shielding sheet metal element is not included in supply of manufacturer Inspection hole for camera covered with removable air tigh...

Page 27: ...ect Wired MAT 4 0 ALU1 PAROC hvac Fire Mat BlackCoat Fixing part of the pipe between wall and pipe optional Hanging ring e g FISCHER type LGS Permeation shielding sheet metal element is not included i...

Page 28: ...The insulation of the pipe must cover the damper collar from back side 1 0 10 0 100 0 10 100 1000 10000 Air flow m3 h Pressure drop Pa 200 14000 Air flow m3 h Pressure drop Pa 200 14000 Insulation ed...

Page 29: ...Pressure drop Pa 200 14000 Air flow m3 h Pressure drop Pa 200 14000 30 200 200 45 310 310 55 400 400 70 500 500 90 650 650 115 800 800 145 1000 1000 180 1250 1250 220 1550 1550 280 2000 2000 355 2500...

Page 30: ...normal 0 i 0 10 VDC invers 2 i 2 10 VDC invers Setting the nominal volumetric flow depending on the VAV box Through connecting the power supply to BU BN 1 2 and a reference signal Y to BK 3 in the ra...

Page 31: ...43 45 2 5 15 22 28 33 37 41 44 47 49 2 2 12 20 26 32 36 40 43 46 49 2 2 6 14 21 27 32 36 39 43 46 2 2 2 6 13 19 24 28 32 36 39 2 2 2 2 2 7 13 18 22 25 29 2 2 2 5 10 13 16 19 22 24 26 2 2 9 15 20 24 27...

Page 32: ...36 39 43 46 49 2 2 6 14 21 26 31 35 39 42 45 2 2 2 5 12 18 23 28 32 35 39 2 2 2 2 2 7 12 17 21 25 28 2 2 2 4 9 12 15 18 21 23 25 2 2 8 14 19 23 27 30 32 35 37 2 4 13 20 25 30 33 37 40 42 45 2 5 14 22...

Page 33: ...38 42 45 48 51 2 2 8 16 23 29 34 38 41 45 48 2 2 2 8 15 21 26 30 34 38 41 2 2 2 2 3 9 15 19 24 27 31 2 2 2 8 12 16 19 22 24 26 28 2 3 11 18 23 27 30 33 36 38 40 2 7 16 23 29 33 37 40 43 46 48 2 8 18 2...

Page 34: ...18 20 22 24 2 2 7 13 18 22 26 29 32 34 36 2 3 12 19 25 29 33 36 39 41 44 2 4 14 21 27 32 36 39 43 45 48 2 2 11 19 25 31 35 39 43 45 48 2 2 5 13 20 26 30 35 39 41 45 2 2 2 5 12 18 23 27 31 35 38 2 2 2...

Page 35: ...for all material variants of the dampers The thermal link is identical for all material variants of the dampers Upon specification by customer the thermal link may be made from A4 from stainless steel...

Page 36: ...after restoration of power supply e g by releasing the RESET button or restoration of supply from ELECTRICAL FIRE SIGNALISATION Without power supply the damper can be operated manually and fixed in an...

Page 37: ...th actuator by cable With actuating mechanism BFL BFN 230 T sensor BAT is not mounted on the damper s body only connected with actuator by cable With actuating mechanism BFL BFN 24 T ST and communicat...

Page 38: ...158 100 130 95 178 100 175 105 198 100 175 115 223 100 175 127 248 100 175 140 278 100 175 155 313 100 175 173 353 100 175 193 398 125 225 220 448 125 225 245 498 125 225 270 558 125 225 300 628 125 2...

Page 39: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: