36
(placed on the casing of fire damper)
(placed on the casing of fire damper)
(placed on the casing of fire damper)
Before entering the dampers into operation after their assembly and by sequential checks, the following checks must be carried out. Visual
inspection of proper damper integration , inside damper area, damper blade, contact surfaces and silicon sealing. Check of thermal protective
fuse and closing mechanism. Check the closing function of the damper blade. This can be done by removing of thermal fuse from damper body.
Before entering the dampers with actuating mechanism into operation after their assembly and by sequential checks. Check of blade
displacement into the breakdown position "CLOSED" can be done after cutting off the actuating mechanism supply (e.g. by pressing the RESET
button at the thermoelectrical starting mechanism BAT or cutting off the supply from ELECTRICAL FIRE SIGNALISATION). Check of blade
displacement back into the "OPEN" position can be done after restoration of power supply (e.g. by releasing the RESET button or restoration of
supply from ELECTRICAL FIRE SIGNALISATION).
Without power supply, the damper can be operated manually and fixed in any required position. Release of the locking mechanism can be
achieved manually or automatically by applying the supply voltage. It is recommended to provide periodical checks, maintenance and service
actions on Fire Equipment by Authorized persons. The authorized persons can be trained by Producer, or by authorized Distributor. All effective
safety standards and directives must be observed during fire damper assembly.
For regular or exceptional inspection of interior of fire damper, micro-camera device can be used. On each fire damper is ispection hole. In the
case of inspection by camera, take out the black rubber cap, insert the camera inside the damper, check interior and at the end of inspection, put
the rubber cap back tightly to cover the empty hole.
WEIGHT (kg):
Dobříšská 550, 267 24 Hostomice, Czech Republic
MANDÍK, a.s.
ACTUATING SYSTEM:
YEAR/SER.NO.:
DIMENSION:
1391
EN 15650:2010
TPM 125/17
R
FIRE PROTEC. CLASS:
MANUAL
Cert. No.: 1391-CPR-2020/0131, DoP: PM/FDMS(FDMS-VAV)/01/20/2
Summary of Contents for FDMS
Page 1: ......
Page 14: ...14 50 50 41 575 146 125 D D1 2 x D min 2 x D min C...
Page 18: ...18 Fire classification 96 47 47 96 96...
Page 21: ...21 Fire classification 96 47 47 96 96...