Insulated wall construction (e.g. KINGSPAN - type KS1150 FR)
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Anchor for damper collar (threaded rod and nuts M8)
Fixing part of the pipe between wall and pipe (only recommended)
Hanging ring (e.g. FISCHER - type LGS)
Permeation shielding (sheet metal element is not included in supply of manufacturer)
Inspection hole for camera covered with removable air-tight rubber cap
View B:
Ø
D
Fire classification:
≥
100
Before the fire seal is installed, it is
necessary to cover the opening with
sheet metal element/cover. This part
covers the insulation in the panel and
connects the panel sheets.
Connecting surface between damper collar
and wall fulfil with fire resistant sealant before
instalation of the damper (recommended type
of sealant - e.g. PROMAT K84 or HILTI CFS-S)