20
Gypsum wall construction
Spiral pipe
Fire resistant fill (for recommended materials see separate table)
Threaded rod and anchor to the wall (or ceiling) (e.g. threaded rod M8 and anchor type according pipe weight)
Fire protection mastic min. thickness 1mm (e.g. PROMASTOP-P or K)
Fire damper FDMS
Anchor for damper collar (threaded rod and nuts M8 or e.g. anchor FISCHER - type KD8)
Fixing part of the pipe between wall and pipe (only recommended)
Hanging ring (e.g. FISCHER - type LGS)
Inspection hole for camera covered with removable air-tight rubber cap
View B:
Ø
D
Fire classification:
≥
100
Connecting surface between damper collar
and wall fulfil with fire resistant sealant before
instalation of the damper (recommended type
of sealant - e.g. PROMAT K84 or HILTI CFS-S)