TPM 092/13
9
Fig. 8
Installation opening - system Weichschott
Tab. 5.1.1. Statement of installations
Size
FDMD installation
Classifi-
cation
Figure
100-200
Damper installed in a solid wall construction min. thickness 100 mm.
Space between damper and wall is filled by mortar, gypsum (notice 1)
EIS 90
9
Damper installed in a solid wall construction min. thickness 100 mm.
Space between damper and wall is filled by mineral stone wool min.
density 140 kg/m
3
). Surface is covered by fire protection
mastic min. thickness 1 mm (notice 1)
EIS 90
10
Damper installed in a gypsum wall construction, classification EI 90.
Space between damper and wall is filled by mineral stone wool min.
density 140 kg/m
3
). Surface is covered by fire protection
mastic min. thickness 1 mm
EIS 90
11
Damper installed in a solid wall construction min. thickness 100 mm.
Space between damper and wall is filled by system Weichshott (notice 1)
EIS 90
12
Damper installed in a gypsum wall construction, classification EI 90.
Space between damper and wall is filled by system Weichshott.
EIS 90
13
Damper installed in a solid ceiling construction min. thickness 150 mm.
Space between damper and wall is filled by mortar, gypsum (notice 2)
EIS 90
14
Damper installed in a solid ceiling construction min. thickness 150 mm.
Space between damper and wall is filled by mineral stone wool min.
density 140 kg/m
3
). Surface is covered by fire protection
mastic min. thickness 1 mm (notice 2)
EIS 90
15
Damper installed in a solid ceiling construction min. thickness 150 mm.
Space between damper and wall is filled by system Weichshott (notice 1)
EIS 90
16
NOTICE:
1) Solid wall construction: normal concrete/masonry or porous concrete with minimum thickness 100 mm
2) Solid ceiling construction: normal concrete/masonry or porous concrete with minimum thickness 150 mm
5. Statement of installations
5.1.
Statement of installations