TPM 092/13

7

Position:

1

Damper casing

5

Terminal switch

2

Damper blade

6

Inspection hole covering

3

Shutting spring

7

Actuating mechanism

4

Thermal protective fuse

8

BAE 72B-S thermoelectrical starting
mechanism

Tab. 3.2.1.  Weights and effective area

Size

  D

Weight [kg]

Effective area S

ef

 [m

2

]

Actuating

 mechanism

mechanical 

control

actuating 

mechanism

100

1,2

3,3

0,0032

BLF

125

1,4

3,7

0,0063

BLF

140

1,6

3,9

0,0086

BLF

150

1,7

4,0

0,0102

BLF

160

1,8

4,1

0,0122

BLF

180

2,1

4,4

0,0164

BLF

200

2,6

4,7

0,0213

BLF

3.2.  

Weights and effective area

4.1.  

Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages 
of  fire  separating  constructions.  Damper  assembly  procedures  must  be  done  so  as  all  load 
transfer  from  the  fire  separating  constructions  to  the  damper  body  is  absolutely  excluded. 
Back-to-back air-conditioning piping must be hung or supported so as all load transfer from the 
back-to-back piping to the damper is absolutely excluded.

Fig. 3   Fire damper FDMD - design with actuating mechanism

4. Placement and Assembly

Summary of Contents for alnor FDMD

Page 1: ... 0 1 0 A L N O RS y s t e myWe n t y l a c j i S p z o o A l e j aK r a k o w s k a1 0 0 5 5 5 2Wo l aMr o k o w s k a t e l 2 27 3 7 4 0 0 0 f a x 2 27 3 7 4 0 0 4 w w w a l n o r c o m p l F I R E D A MP E R F D MD ...

Page 2: ...atement of installations 9 III TECHNICAL DATA 10 6 Pressure loss 10 7 Coefficient of local pressure loss 11 8 Noise data 11 9 Electrical Components Connection Diagrams 13 IV ORDERING INFORMATION 16 10 Ordering key 16 V DATA OF PRODUCT 16 11 Data label 16 VI MATERIAL FINISHING 17 12 Material 17 VII INSPECTION TESTING 17 12 Inspection testing 17 VIII TRANSPORTATION AND STORAGE 17 14 Logistic terms 1...

Page 3: ...er blade is bedded in a material which enlarges its capacity and air proofs the air duct 1 5 Operation of the dampers does not depend on the direction of air circulation The dampers can be located in an arbitrary position 1 6 Dampers have one inspection hole since the shutting device and the inspection hole can be set into the most advantageous position with respect to the operation and manipulati...

Page 4: ...etween the terminals 3 and 4 A green LED pilot light on BKN 230 24 is on when voltage is present in the drive AC 24V If the button on BAE 72 S is switched on or if the power supply e g by a signal from ELECTRICAL FIRE SIGNALISATION is disconnected the fire damper position will be FAILURE 2 2 3 Signaling damper blade position OPEN and CLOSED is secured by two built in firmly set terminal switches 2...

Page 5: ...controlled and tested only as a group BKS 24 9A is intended for use in the distribution board and displays the operation situations and failure reports of the connected fire dampers It is possible to signalise functions such as the damper position and failure reports or to transmit them further to the system by means of integrated auxiliary switches BKS 24 9A receives signals from BKN 230 24 throu...

Page 6: ...g mechanism BLF 230 T 40 With actuating mechanism BLF 24 T 50 With communication and supply device BKN 230 24 and actuating mechanism BLF 24 T ST 60 Tab 2 4 1 Dampers design communication and supply device BKN 230 24 has to be placed near the damper It is necessary for easy connection of actuating system equipped by BKN 230 24 device 3 Dimestions weights 3 1 Dimensions ...

Page 7: ...0 0 0102 BLF 160 1 8 4 1 0 0122 BLF 180 2 1 4 4 0 0164 BLF 200 2 6 4 7 0 0213 BLF 3 2 Weights and effective area 4 1 Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions Damper assembly procedures must be done so as all load transfer from the fire separating constructions to the damper body is absolutely excluded Back...

Page 8: ...n one fire separating construction min 200 min 75 min 75 4 4 After installation has to be damper blade placed in position CLOSED inside of fire separating construction 4 5 The control mechanism has to be protected covered against damage and pollution during installation process All fire dampers has to be closed during installation process The damper body should not be deformed in the course of bri...

Page 9: ... Space between damper and wall is filled by system Weichshott notice 1 EIS 90 12 Damper installed in a gypsum wall construction classification EI 90 Space between damper and wall is filled by system Weichshott EIS 90 13 Damper installed in a solid ceiling construction min thickness 150 mm Space between damper and wall is filled by mortar gypsum notice 2 EIS 90 14 Damper installed in a solid ceilin...

Page 10: ...ffing box mineral stone wool min density 140 kg m3 3 Fire protection mastic min thickness 1 mm 2 1 3 3 Used materials example 2 Promapyr Rockwool Steprock HD 3 Promastop P K Stuffing box and fire protection mastic can be replaced by another approved fire sealing system for damper installation with equivalent material properties 1 2 POSITION 1 Fire damper FDMD 2 Fire resistant board 3 Fire stop coa...

Page 11: ... Rockwool Steprock HD 3 Promastop P K Stuffing box and fire protection mastic can be replaced by another approved fire sealing system for damper installation with equivalent material properties 1 2 POSITION 1 Fire damper FDMD 2 Fire resistant board 3 Fire stop coating thickness 1 mm 2 1 3 3 Used materials example 2 Hilti CP673 PF 3 Hilti CP673 Fig 14 Installation in a solid ceiling construction 1 ...

Page 12: ...another approved fire sealing system for damper installation with equivalent material properties Fig 16 Installation in a solid ceiling construction 1 3 POSITION 1 Fire damper FDMD 2 Fire resistant board 3 Fire stop coating thickness 1 mm 2 1 3 2 Used materials example 2 Hilti CP673 PF 3 Hilti CP673 6 Pressure loss 6 1 Pressure loss calculation III TECHNICAL DATA p w2 2 p Pa presure loss w m s 1 a...

Page 13: ...corrected with filter A 8 2 Level of acoustic output in octave ranges LWA dB A level of acoustic output corrected with filter A LW1 dB level of acoustic output LW1 related to the 1 m2 section see Tab 8 3 1 S m2 effective area of the damper KA dB correction to the weight filter A see Tab 8 3 2 LWA LW1 10 log S KA LWoct dB spectrum of acoustic output in octave range LW1 dB level of acoustic output L...

Page 14: ...0 10 48 1 53 5 56 6 58 9 62 0 64 3 66 0 69 1 71 4 73 1 74 5 75 7 11 50 6 56 0 59 1 61 4 64 5 66 7 68 5 71 6 73 9 75 6 77 0 78 2 12 52 8 58 2 61 4 63 6 66 8 69 0 70 7 73 9 76 1 77 9 79 3 80 5 Tab 8 3 2 Correction to the weight filter A w m s 1 2 3 4 5 6 7 8 9 10 11 12 KA dB 15 0 11 8 9 8 8 4 7 3 6 4 5 7 5 0 4 5 4 0 3 6 Tab 8 3 3 Relative level expressing the shape of the spectrum Lrel f Hz w m s 1 ...

Page 15: ...T Actuating mechanism BELIMO BLF 24 T ST 24 ST BLF230 T Nominal voltage AC 24V 50 60Hz DC 24 V AC 230 V 50 60Hz Power consumption motoring holding 5 W 2 5 W 5W 3W Dimensioning 7 VA Imax 5 8 A 5 ms 7 VA Imax 150 mA 10 ms Protection Class III II Degree of protection IP 54 Running time motor spring return 40 75 s 20 s Ambient Temperature normal duty safety duty non operating temperature 30 C 50 C The...

Page 16: ... voltage AC 230V 50 60Hz Power consumption 3 5 W operating position Dimensioning 11 VA including actuating mechanism Protection Class II Degree of protection IP 42 Ambient Temperature Storage Temperature 30 C 50 C 40 C 50 C Connection mains drive terminal board Cable 0 9 m with EURO plug of 26 type 6 pole plug 3 pole plug screw terminals for conductor 2x1 5 mm2 9 2 Communication and Supply Device ...

Page 17: ... Control Device BKS 24 9A Communication and Control Device BKS 24 9A Nominal voltage AC 24 V 50 60Hz Power consumption 3 5 W operating position Dimensioning 5 5 VA Protection Class III safe small voltage Degree of protection IP 30 Ambient Temperature 0 50 C Connection Terminals for conductor 2 x 1 5 mm2 9 3 Communication and Control Devices ...

Page 18: ...4 V 50 60Hz Power consumption 2 5 W operating position Dimensioning 5 VA Protection Class III safe small voltage Degree of protection IP 30 Ambient Temperature 0 50 C Connection Into ZSO 11 connector which is not a part of BKS 24 1B ZSO 11 connector has screw terminals 11 x 1 5 mm2 Fig 22 Communication and Control Device BKS 24 1B ...

Page 19: ...a label 12 Material VI MATERIAL FINISHING 12 1 Damper bodies are supplied in the design made of galvanized plate without any other surface finish 12 2 Damper blades are made of fire resistant asbestos free boards made of mineral fibres 12 3 Fasteners is galvanized VII INSPECTION TESTING 13 Inspection testing 13 1 The appliance is constructed and preset by the manufacturer its operation is dependen...

Page 20: ...n of the electrical components must be done After entering into operation these revisions must be done according to requirement set by national regulations 16 1 1 In case that dampers are found unable to serve for their function for any cause it must be clearly marked The operator is obliged to ensure so that the damper is put into condition in which it is able to function and meanwhile he is obli...

Page 21: ... o o A l e j a K r a k o w s k a 1 0 0 5 5 5 2Wo l a M r o k o w s k a P o l s k a T e l 4 82 2 7 3 7 4 0 0 0 F a x 4 82 27 3 7 4 0 0 4 E M a i l a l n o r a l n o E M a i l a l n o r a l n o r c o m p l w w w a l n o r c o m p l Wy ł ą c z n y D y s t r y b u t o r ...

Reviews: