TPM 092/13

5

2.3.  

Communication and control devices

2.3.1. 

BKS 24-1B communication and control device is used for control and checks of fire flap valves 
with  the  BLF  24-T-ST  actuating  mechanism  in  conjunction  with  the  BKN  230-24  supply  and 
communication  device.  BKS  24-1B  receives  information  about  the  situation  of  the  fire  damper 
through the BKN 230-24 supply and communication device and issues controlling commands.

 

The device is intended for building in into the distribution board. Light diodes on the front side of 
the device signalise the operating situations of the damper and breakdowns of the whole system. 
Nonpotential auxiliary contacts enable connection to the master control system (signalisation of 
the damper position, failure reports, release of the ventilators etc.).

 

While a flashing green LED pilot light signalises flap blade motion towards the given position, the 
same pilot light reports reaching the required position when shining constantly. If the damper, with 
respect to the given time, does not reach the required position, then a red LED pilot light starts to 
flash and at the same time, the failure contact is active. Once the damper blade reaches the given 
position,  this  contact  is  deactivated.  The  LED  pilot  light  keeps  flashing  unless  the  failure  is 
unblocked by means of the RESET button.

2.3.2. 

BKS 24-9A communication and control device is used for group control and checks of 1 to 9 fire 
dampers  with  the  actuating  mechanism  BLF  24-T-ST  in  connection  with  the  supply  and 
communication  device  BKN  230-24.  Signalisation  of  the  damper  position  is  individual;  the 
dampers  can  be  controlled  and  tested  only  as  a  group.  BKS  24-9A  is  intended  for  use  in  the 
distribution board and displays the operation situations and failure reports of the connected fire 
dampers. It is possible to signalise functions such as the damper position and failure reports or to 
transmit  them  further  to  the  system  by  means  of  integrated  auxiliary  switches.  BKS  24-9A 
receives  signals  from  BKN  230-24  through  the  two-conductor  wiring  and  issues  control 
commands. Proper damper operation is indicated by two light LED diodes:

  

  

Control ON = position OPERATION

 

  

Control OFF = position FAILURE

 

If the fire dampers do not reach the given position in time tolerable for displacing, the appropriate 
light diode FAILURE starts to flash and K1 contact is opened (current failure). In case that the 
faulty damper finally reaches its given position, K1 is closed and the failure report light shines (the 
failure is saved in memory).

 

K2 - the auxiliary contact - is used for signalisation of the flap position to the master device. Function

 

of this auxiliary contact can be programmed through the terminal 14 according to the Tab. 2.2.1.

Tab. 2.3.1.  BKS 24 -9A contacts K1 and K2

K1 Function Contact

Situation

State

Current Failure

15                     16

No Failure

15                     16

Programming K2 Auxiliary Contact

Function

Interconnection

State

K2  contact  is  on  if  all  the 
damperss are open

14                     11

17                     18

K2 contact is on if the damper
No. 1 is open

14                     12

K2 contact is on if all the
dampers are closed

14    open

Function  check  can  be  done  in  the  position  OPERATION  by  means  of  pushing  the  TEST 
button. While the button is pushed, the flap blade is turning into the position FAILURE. Fault 
function is indicated by a report "FAILURE".

2.4.  

Design of the FDMD in terms of design. It shall be marked with the first and second additional digit 
after the dot in the ordering key.

Summary of Contents for alnor FDMD

Page 1: ... 0 1 0 A L N O RS y s t e myWe n t y l a c j i S p z o o A l e j aK r a k o w s k a1 0 0 5 5 5 2Wo l aMr o k o w s k a t e l 2 27 3 7 4 0 0 0 f a x 2 27 3 7 4 0 0 4 w w w a l n o r c o m p l F I R E D A MP E R F D MD ...

Page 2: ...atement of installations 9 III TECHNICAL DATA 10 6 Pressure loss 10 7 Coefficient of local pressure loss 11 8 Noise data 11 9 Electrical Components Connection Diagrams 13 IV ORDERING INFORMATION 16 10 Ordering key 16 V DATA OF PRODUCT 16 11 Data label 16 VI MATERIAL FINISHING 17 12 Material 17 VII INSPECTION TESTING 17 12 Inspection testing 17 VIII TRANSPORTATION AND STORAGE 17 14 Logistic terms 1...

Page 3: ...er blade is bedded in a material which enlarges its capacity and air proofs the air duct 1 5 Operation of the dampers does not depend on the direction of air circulation The dampers can be located in an arbitrary position 1 6 Dampers have one inspection hole since the shutting device and the inspection hole can be set into the most advantageous position with respect to the operation and manipulati...

Page 4: ...etween the terminals 3 and 4 A green LED pilot light on BKN 230 24 is on when voltage is present in the drive AC 24V If the button on BAE 72 S is switched on or if the power supply e g by a signal from ELECTRICAL FIRE SIGNALISATION is disconnected the fire damper position will be FAILURE 2 2 3 Signaling damper blade position OPEN and CLOSED is secured by two built in firmly set terminal switches 2...

Page 5: ...controlled and tested only as a group BKS 24 9A is intended for use in the distribution board and displays the operation situations and failure reports of the connected fire dampers It is possible to signalise functions such as the damper position and failure reports or to transmit them further to the system by means of integrated auxiliary switches BKS 24 9A receives signals from BKN 230 24 throu...

Page 6: ...g mechanism BLF 230 T 40 With actuating mechanism BLF 24 T 50 With communication and supply device BKN 230 24 and actuating mechanism BLF 24 T ST 60 Tab 2 4 1 Dampers design communication and supply device BKN 230 24 has to be placed near the damper It is necessary for easy connection of actuating system equipped by BKN 230 24 device 3 Dimestions weights 3 1 Dimensions ...

Page 7: ...0 0 0102 BLF 160 1 8 4 1 0 0122 BLF 180 2 1 4 4 0 0164 BLF 200 2 6 4 7 0 0213 BLF 3 2 Weights and effective area 4 1 Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions Damper assembly procedures must be done so as all load transfer from the fire separating constructions to the damper body is absolutely excluded Back...

Page 8: ...n one fire separating construction min 200 min 75 min 75 4 4 After installation has to be damper blade placed in position CLOSED inside of fire separating construction 4 5 The control mechanism has to be protected covered against damage and pollution during installation process All fire dampers has to be closed during installation process The damper body should not be deformed in the course of bri...

Page 9: ... Space between damper and wall is filled by system Weichshott notice 1 EIS 90 12 Damper installed in a gypsum wall construction classification EI 90 Space between damper and wall is filled by system Weichshott EIS 90 13 Damper installed in a solid ceiling construction min thickness 150 mm Space between damper and wall is filled by mortar gypsum notice 2 EIS 90 14 Damper installed in a solid ceilin...

Page 10: ...ffing box mineral stone wool min density 140 kg m3 3 Fire protection mastic min thickness 1 mm 2 1 3 3 Used materials example 2 Promapyr Rockwool Steprock HD 3 Promastop P K Stuffing box and fire protection mastic can be replaced by another approved fire sealing system for damper installation with equivalent material properties 1 2 POSITION 1 Fire damper FDMD 2 Fire resistant board 3 Fire stop coa...

Page 11: ... Rockwool Steprock HD 3 Promastop P K Stuffing box and fire protection mastic can be replaced by another approved fire sealing system for damper installation with equivalent material properties 1 2 POSITION 1 Fire damper FDMD 2 Fire resistant board 3 Fire stop coating thickness 1 mm 2 1 3 3 Used materials example 2 Hilti CP673 PF 3 Hilti CP673 Fig 14 Installation in a solid ceiling construction 1 ...

Page 12: ...another approved fire sealing system for damper installation with equivalent material properties Fig 16 Installation in a solid ceiling construction 1 3 POSITION 1 Fire damper FDMD 2 Fire resistant board 3 Fire stop coating thickness 1 mm 2 1 3 2 Used materials example 2 Hilti CP673 PF 3 Hilti CP673 6 Pressure loss 6 1 Pressure loss calculation III TECHNICAL DATA p w2 2 p Pa presure loss w m s 1 a...

Page 13: ...corrected with filter A 8 2 Level of acoustic output in octave ranges LWA dB A level of acoustic output corrected with filter A LW1 dB level of acoustic output LW1 related to the 1 m2 section see Tab 8 3 1 S m2 effective area of the damper KA dB correction to the weight filter A see Tab 8 3 2 LWA LW1 10 log S KA LWoct dB spectrum of acoustic output in octave range LW1 dB level of acoustic output L...

Page 14: ...0 10 48 1 53 5 56 6 58 9 62 0 64 3 66 0 69 1 71 4 73 1 74 5 75 7 11 50 6 56 0 59 1 61 4 64 5 66 7 68 5 71 6 73 9 75 6 77 0 78 2 12 52 8 58 2 61 4 63 6 66 8 69 0 70 7 73 9 76 1 77 9 79 3 80 5 Tab 8 3 2 Correction to the weight filter A w m s 1 2 3 4 5 6 7 8 9 10 11 12 KA dB 15 0 11 8 9 8 8 4 7 3 6 4 5 7 5 0 4 5 4 0 3 6 Tab 8 3 3 Relative level expressing the shape of the spectrum Lrel f Hz w m s 1 ...

Page 15: ...T Actuating mechanism BELIMO BLF 24 T ST 24 ST BLF230 T Nominal voltage AC 24V 50 60Hz DC 24 V AC 230 V 50 60Hz Power consumption motoring holding 5 W 2 5 W 5W 3W Dimensioning 7 VA Imax 5 8 A 5 ms 7 VA Imax 150 mA 10 ms Protection Class III II Degree of protection IP 54 Running time motor spring return 40 75 s 20 s Ambient Temperature normal duty safety duty non operating temperature 30 C 50 C The...

Page 16: ... voltage AC 230V 50 60Hz Power consumption 3 5 W operating position Dimensioning 11 VA including actuating mechanism Protection Class II Degree of protection IP 42 Ambient Temperature Storage Temperature 30 C 50 C 40 C 50 C Connection mains drive terminal board Cable 0 9 m with EURO plug of 26 type 6 pole plug 3 pole plug screw terminals for conductor 2x1 5 mm2 9 2 Communication and Supply Device ...

Page 17: ... Control Device BKS 24 9A Communication and Control Device BKS 24 9A Nominal voltage AC 24 V 50 60Hz Power consumption 3 5 W operating position Dimensioning 5 5 VA Protection Class III safe small voltage Degree of protection IP 30 Ambient Temperature 0 50 C Connection Terminals for conductor 2 x 1 5 mm2 9 3 Communication and Control Devices ...

Page 18: ...4 V 50 60Hz Power consumption 2 5 W operating position Dimensioning 5 VA Protection Class III safe small voltage Degree of protection IP 30 Ambient Temperature 0 50 C Connection Into ZSO 11 connector which is not a part of BKS 24 1B ZSO 11 connector has screw terminals 11 x 1 5 mm2 Fig 22 Communication and Control Device BKS 24 1B ...

Page 19: ...a label 12 Material VI MATERIAL FINISHING 12 1 Damper bodies are supplied in the design made of galvanized plate without any other surface finish 12 2 Damper blades are made of fire resistant asbestos free boards made of mineral fibres 12 3 Fasteners is galvanized VII INSPECTION TESTING 13 Inspection testing 13 1 The appliance is constructed and preset by the manufacturer its operation is dependen...

Page 20: ...n of the electrical components must be done After entering into operation these revisions must be done according to requirement set by national regulations 16 1 1 In case that dampers are found unable to serve for their function for any cause it must be clearly marked The operator is obliged to ensure so that the damper is put into condition in which it is able to function and meanwhile he is obli...

Page 21: ... o o A l e j a K r a k o w s k a 1 0 0 5 5 5 2Wo l a M r o k o w s k a P o l s k a T e l 4 82 2 7 3 7 4 0 0 0 F a x 4 82 27 3 7 4 0 0 4 E M a i l a l n o r a l n o E M a i l a l n o r a l n o r c o m p l w w w a l n o r c o m p l Wy ł ą c z n y D y s t r y b u t o r ...

Reviews: