Table 15

Maximum Run with Adjustable Length 

Between Two Fixed Points

Operating Temp. (°F)

Max Distance With One 

Adjustable Length (ft.)

200

200

300

133

400

100

500

80

800

50

1000

40

1200

33

1400

29

aDJuStaBLE LEngtH

1. The adjustable length (LA) is used for two 
functions, one is to make odd lengths and the 
other to serve as an expansion joint.

2. The adjustable length may be used when 
internal pressure do not exceed 6” water 
column or in well ventilated areas. See Figure 

65 for good positioning of the adjustable length.

3. The adjustable length assembly includes 
a sliding inner section, two containing rings, 
one compression band, a graphite packing 
gasket, an insulation band (DIS only) and 
a telescopic outer casing. There is a tool 
supplied with this assembly. (see Figure 66).

4. For proper installation, the adjustable 
length must have adequate overlap and 
sufficient allowance for thermal expansion. 
(see Figure 55 - Adjustable length (LA), and 

Table 15).

5. Installation steps (see Figure 56):
a. Adjust the length of the chimney as 
required. If outer casing or inner flue are too 
long, they may be cut to length. You must
keep the overlap of the outer casing to at 
least 1”. You are only authorised to cut on the 
outer casing section attached to the female 
coupling. See Figure 51.

b. Move up the sliding section of the outer 
wall to access inner wall. See Figure 52.

c. Tighten the compression band so that the 
graphite packing is firmly registered against 
the inner flue. See Figure 53.

d. Tighten all the bolts of the containing ring. 
For each bolt, use the supplied tool as a guide 
between the two containing rings (see  

Figure 54).

e. Fill the gap between the inner flue and 
outer casing with the supplied insulation 
band. See Figure 55 (DIS only).

f. Move down the sliding section of the outer 
wall to the flange of the female coupling 
and install the locking band as described 
in Section A: Chimney and Fitting Joint 

Assembly. See Figure 56.

Bellows Expansion Joint and adjustable 

Length in Horizontal runs
1. Same guidelines apply as for vertical run 
with respect to expansion estimate and 
proper support and guiding with the use 
of Bellows Expansion Joint and Adjustable 
Length.

BELLoWS EXpanSIon JoInt (LB)

1. Used in diesel or turbine exhaust installation 
for expansion and vibration movements.

2. Good for exhaust pressure up to 60 inches 
of water column, it will compensate for up 
to 3” max of expansion. See Table 14 for 
maximum run with one bellow.

3. Bellow joints comes with a liner to protect 
the bellow and to have a smooth flow.

4. We suggest to always install a 12” length 
chimney downstream and upstream the 
bellow to insure clearance for the liner and 
adding accessibility for supporting and 
guiding. See Figure 50 ‘’bellowjoint’’ for good 
positioning of the bellow expansion joint.

5. It is of the most important that the bellow 
joint be properly supported and guided in 
vertical and horizontal orientation.

6. Installation is done the same way as 
described in Section A: Chimney and

Fitting Joint Assembly.

Summary of Contents for DuraVent DIS

Page 1: ...DuraStack DIS DAS Installation Instructions A modular double wall positive pressure chimney Boiler Breeching and Stack Engine Exhaust Grease Duct DIS only...

Page 2: ...his venting system must be supported in accordance with these instructions Check for proper joint construction when joining pipe to fittings Check for unrestricted vent movement through walls ceilings...

Page 3: ...ing Information 4 Section A General Information 4 Section B Tees Elbows Increasers 12 Section C Structural Support and Guiding 16 Section D Roof and WAll Penetrations 22 Section E Terminations Startin...

Page 4: ...tructions comprise both general guidelines and special requirements for all parts in the product line Before specifying a design or beginning an installation please carefully review these instructions...

Page 5: ...ctions and National Fire Protection Association standard NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations Surroundings Enclosure DuraVent models DIS and DA...

Page 6: ...ilding is four stories or more the enclosure wall shall have a fire resistance rating of not less than two hours 4 Combustible roofs or roof ceiling assemblies may be penetrated as described in Sectio...

Page 7: ...0 Inside 8 Inside 8 12 36 Inside 8 Not Listed Table 4 DAS Minimum Openings Model Roof Floor C Wall C 5 10 Inside 12 Inside 12 12 36 Inside 12 Not Listed warning DO NOT INSTALL ANY TYPE OF INSULATION I...

Page 8: ...able 5 for approved sealants 2 Insert the female end of another section of chimney over male end with sealant see Figure 3 3 Insert the assembly band see Figure 4 around the joint of the two sections...

Page 9: ...R EXPANSION JOINT OBSERVE ADEQUATE SAFETY MEASURES WHEN USING A DEGREASER Table 6 Maximum Chimney Heights and Support Method for Model DIS and DAS Inside Diameter Anchor Plate Anchor PlateVentilated A...

Page 10: ...10 12 26 10 8 10 12 28 10 8 10 12 30 10 8 10 12 32 10 8 10 12 34 10 8 10 12 36 10 8 10 12 MVS MaximumVertical Spacing between two guides or a support and a guide in a vertical position H Maximum free...

Page 11: ...Example Model DIS 6 diameter section of 25 feet in length from table 8 weight in lb ft 8 Total weight 8 x 25 200 lbs CHIMNEY GUYING AND bRACING 1 Proper guying and bracing is essential for part of the...

Page 12: ...or each engine or turbine Check with your engine or turbine manufacturer prior to common exhaust system design Exhaust gas from operating units tends to flow to non operating units where condensation...

Page 13: ...12 45 TEE T45 1 For systems where flow resistance must be minimized like engine or turbine exhaust The use of a 45 tee is suggested It can be combined with a 45 elbow to make a smooth 90 turn See Figu...

Page 14: ...8 12 4 When removed the old silicone must be cleaned out and a new bed of sealant must be applied Drain Tee Cap DTC 1 Use as a drain for vertical stack 2 Connect to a suitable drain fitting to allow r...

Page 15: ...lynecessary 2 Sloped offsets require more expansion joints and secure bracing above and below elbows 3 With solid fuel burning appliance the slope must not be greater than 30 from the vertical Applian...

Page 16: ...Section C 12 Re supports such as those shown in Figure 30 must be securely anchored to walls posts or locally fabricated rigid framework This framework must be designed to assure stability of attache...

Page 17: ...der the weight of the assembled parts and make sure you have a safe manner of lifting the assembly Installation Steps for First Method refer to Figure 22 1 Place the part that will be upsteam of the s...

Page 18: ...the male coupling flange of the part before the support 3 Insert the male coupling of the part in the plate opening 4 You may hold it using two clamp flanges placed at 180 and bolted to the anchor pl...

Page 19: ...tbeabletomovewithoutinterfering withtheguidewhenthermalexpansionoccurs SeeFigure27 wallguidelocation 3 Thewallguidecanbeinstalledwithawallband Figure 26 extensionforgreaterclearancesupto4 1 4 for mode...

Page 20: ...28 Wall Guide Wall Guide Wall Support MVS MVS 2 to 4 51mm to 108mm DIS 5 to 7 127mm to 184mm DAS Freestanding H max 6 to 10 Do not install expansion length in this area Wall Guide Expansion Length I...

Page 21: ...cation ROOF BRACE RB 1 The roof brace is used to stabilize the chimney where it extends more than 15 above the roof 2 It consists of one band RB and two braces supplied by the installer 3 To minimize...

Page 22: ...le 3 Minimum openings for framing dimension 3 The radiant shield of the firestop may need to be trimmed to fit the height of the roof Nominal height is 10 inches 4 Roof floor penetration components ar...

Page 23: ...of combustible construction important Crossing a combustible wall is not permitted for diameters larger than 10 inside diameter Sealant Flashing Combustible roof floor Firestop Radiant Shield 2 Clear...

Page 24: ...Flange Adaptor FA is intended for use as a connection to a class 125 or 150 ANSI pipe flange 2 This type of connection requires a flange gasket and bolt set provided by the installer The gasket and bo...

Page 25: ...aining Band and a locking band over a shank type flue gas inlet 2 First slide the retaining band over the system inlet and tighten it with supplied bolt See Figure 37a Figure 43 Appliance Outlet Inser...

Page 26: ...ged outlet The Flange Adaptor comes with beam clamps to clamp the FFHA to the appliance See Figure 42 TERMINATIONS 4 Installation is done the same manner as a standard length except for model 3 For th...

Page 27: ...t of the exhaust system The best way to accomplish this is to locate an Anchor Plate AP support at the joint between the ANSI Flange adaptor and the adjacent fitting See Figure 49 5 It is crucial that...

Page 28: ...f the exhaust 10 Low pressure systems such as boilers up to 6 inches water column can effectively use the Adjustable Length LA 11 Spacing of guides and supports when a thermal expansion part is used s...

Page 29: ...lows Bellow Joint Wall Guide Wall Support 12 Long Length Minimum With Bellows Bellow Joint Wall Guide Wall Support Suspension Band 12 Long Length Minimum With Bellows Bellow Joint Fixed Support Suspen...

Page 30: ...aphite packing is firmly registered against the inner flue See Figure 53 d Tighten all the bolts of the containing ring For each bolt use the supplied tool as a guide between the two containing rings...

Page 31: ...r casing Inner flue sealant S 2000 or S 650 is necessary depending on the flue gaz temperature 3 Installation steps a Measure the distance required for the variable length See Figure 58 b Cut the inne...

Page 32: ...Then install the locking band over those flanges See Figure 62 f Install the insulation over the inner wall DIS only See Figure 63 Figure 57 X Min 1 Min Overlap Insulation Band DIS only Compression Ba...

Page 33: ...loor Figure 64 important ACCESS REQUIREMENTS ARE SUBJECT TO CHANGE IN ACCORDANCE WITH LOCAL CODE LOCAL AUTHORITIES SHOULD BE CONSULTED FOR EXACT REQUIREMENTS USE AND INSTALLATION OF INDIVIDUAL PARTS 1...

Page 34: ...inch w c Internal Pressure Adjustable Length Adjustable Length Fixed Support 45 Tee Tee Cap Length Locking Band Variable Length Starting Adapter 45 Elbow Increaser Suspension Band Wall Firestop Drain...

Page 35: ...or above the horizontal centerline of the chimney SQUARE TO ROUND ADAPTOR 1 When the hood is equipped with a square or rectangular collar a square to round adaptor is needed to connect the round DIS c...

Page 36: ...inspection See Figure 73 3 Remove the insulation pad and set it in a safe place during the inspection See Figure 73 4 Unscrew the eight 8 wing screws and set it in a safe place See Figure 74 5 Remove...

Page 37: ...Sealant Fan Adaptor Fan Curb 5 Replace the INSULATION PAD over the inner door 6 Replace the outer door 7 Put back the six 6 wing screws and tighten them with your hands FAN ADAPTOR PLATE FAN DIS ONLY...

Page 38: ...ase duct supported by the fan adaptor plate is 15 for all diameters warning DO NOT EXCEED THE MAXIMUM LOAD LIMIT OF THE ROOF CURB OR THE ROOF MAINTENANCE 1 Grease duct is required by NFPA 96 and many...

Page 39: ...39 Section H Markings Safety Listing Labels DIS and DAS...

Page 40: ...orm withinthechimneysystem The entire chimney or exhaust system was supplied by DuraVent Exposed Galvalume and galvanized surfaces are protected with a minimum of one base coat of primer and one finis...

Page 41: ...iot fire flood high wind or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance c damage resulting from f...

Reviews: