background image

AF-JA/JZ-150129

Hold time:

this determines the time the fitting remains at 100% level on 
motion detection and is set with DIp switches at the sensor 
itself, refer to figure. 
the following settings are available:
 

I – 5s

 

II – 30s

 

III – 1 minutes

 

IV – 5 minutes

 

V – 10 minutes

 

VI – 30 minutes

Detection Area:

this determines the effective range of the motion detector 
and is set by DIp switches at the sensor itself, refer to figure. 
note that reducing the sensitivity will also narrow the detection 
range.
the following settings are available:
 

I – Detection range 100%

 

II – Detection range 75%

 

III – Detection range 50%

 

IV – Detection range 25%

 

V – Detection range 10%

Daylight sensor:

this setting holds off the 100% light output should there be 
sufficient daylight and is set using DIp switches at the sensor, 
refer to figure. the following settings are available:
 

I – 2 lux

 

II – 10 lux

 

III – 30 lux

 

IV – 50 lux

 

V – disable

SEttInGS

*In disable mode the lamp(s) will always be on with motion detected and operate at 100% light output, even in bright 
daylight.

Detection Area

1

2

3

I

100%

II

75%

III

50%

IV

25%

V

10%

Hold time

1

2

3

4

I

5s

II

30s

III

1min

IV

5min

V

10min

VI

30min

Daylight Sensor

1

2

3

I

2lux

II

10lux

III

30lux

IV

50lux

V

Disable

To connect several control gears with 1 sensor (ON-OFF function), the wiring should be:

this sensor is suitable for indoor use. Max. installation height is 6 meters.