Malm Fireplaces Imperial Carousel Assembly And Installation Instructions Manual Download Page 4

Imperial Carousel  - Page 4

Hood Assembly

Position the hood on the basic unit.  Secure hood to basic 
unit using the 13 sheet metal screws provided.  

IMPORTANT:

  Failure to install these screws will result in 

permanet damage to the unit and void the warranty.

Hood

Sheet Metal Screws
13- 14 x 1/2 Hex.

Basic Unit

All Screws Must Be Installed

Hearth Requirements

A  fl oor  protector  is  required  to 
protect  the  fl oor  in  front  of  the 
fi replace  opening  from  sparks.  
The  fl oor  protector  must    be  a 
minimum of 2 1/2 inch thick com-
mon solid brick over 26 gauge 
sheet metal or equivalent.

The fl oor protector must extend 
a minimum of 16 inches in front 
of  the  fi replace  opening  and 
8  inches  to  either  side  of  the 
fi replace  and  8  inches    behind 
the  back  of  the  unit.    Refer  to 
Figure #3.

8"

8"

48"

54"

16"

Figure 3

54" Diameter Circle Hearth.
8" Minimum is measured from 
the fi re-box

8"

8"

8"

16" From Door

Fire Bowl

Door

8"

DO NOT CONNECT THIS UNIT TO A CHIMNEY 
FLUE SERVING ANOTHER APPLIANCE.

This stove must be connected to (1) a chimney com-
plying with the requirements for Type HT chimneys in 
the Standard for Chimneys, Factory-Built, Residential 
Type and Building Heating Appliance, UL 103, or (2) a 
code-approved masonry chimney with a fl ue liner.

Chimney Connector Installation

It is required to install a 8 inch all-fuel class "A" chim-
ney system prior to the chimney connector installa-
tion.  The connector pipe included with the Imperial is 
1 - 8" x 30" starter pipe, and 1 - 8" x 30" slip connec-
tor.  The slip connector is identifi ed by 3 holes at the 
top of the pipe.  The slip connector has one fl air at 
the top with the 3 holes.  The bottom is smooth.  The 
starter pipe section has fl airings at both ends.  The 
male end is always at the bottom.

Simpson Dura-Vent Chimney System

It is required to use a Dura-Vent Universal Connector 
part number 

8DVL-ADC or 8878 Adapter

 to install the 

chimney connector.   

1. The universal connector is installed into the support 

box.  The 8" x 30" slip pipe is then connected to the 
universal connector. 

2. The  8" x 30" starter pipe section is then slid over the 

slip connector pipe.  Slide the 30 inch pipe over the 
slip pipe only far enough as necessary to facilitate 
installation of the  8" x 30" starter pipe in to the unit. 

3. There must be a minimum of 2 inches of overlap be-

tween the 8" x 30" and 8" x 30" slip connector pipe.

Metalbestos or Security ICC EXCEL

When using Metalbestos or Security chimney systems it 
is required to use the Metalbestos DS-CPA Single Wall 
Conector pipe.  Security users must use the EX adapter. 

1. Installation of the Metalbestos DS-CPA or the Secu-

rity EX adapter must be done fi rst. 

2.  Attach the 8" x 30" slip connector to the DS-CPA or 

EX adapter with 3 - #8 x 3/8 inch screws. 

3.  The 8" x 30" starter pipe section is then slid into the 

slip connector pipe.  Slide the 30 inch pipe into the 
slip pipe only far enough as necessary to facilitate 
installation of the 8" x 30" starter pipe into the unit. 

4.  Slide the 8" x 30" pipe down onto the Imperial. 
5.  There must be a minimum of 2 inches of overlap be-

tween the 8" x 30" and 8" x 30" slip connector pipe.

Other Chimney Systems

There are many other manufacturer's of chimney sys-
tems.  It is beyond the scope of this publication to cover 
installation  with all of the diff erent systems available.  
Most systems have a method of connection to the Impe-
rial's connector pipe.  Confi rm installation procedures 
with your dealer or the manufacturer of the chimney 
system you have purchased. 

Summary of Contents for Imperial Carousel

Page 1: ...ry mixture to much water in the mix may cause the refractory to crack excessively and will reduce the strength of the refrac tory To test for proper water content cut vertically into the mixture with...

Page 2: ...the screws in the hinges snug ly DO NOT OVER TIGHTEN Re adjust as necessary for proper alignment 6 Note that two panels have gasket material on one edge These pieces go on either side of the door Make...

Page 3: ...the chimney the measurement is 45 from the backwall and 45 to the sidewall See gure 1 page 2 For corner installation the center of the chimney is 45 See gure 2 page 2 Clearance to Non combustibles The...

Page 4: ...ter pipe section has airings at both ends The male end is always at the bottom Simpson Dura Vent Chimney System It is required to use a Dura Vent Universal Connector part number 8DVL ADC or 8878 Adapt...

Page 5: ...e the pipe and enter the room This is not how the system will work The vacum in the chimney system will always pull air into the chim ney If you experience a downdraft with your installation it indica...

Page 6: ...terioration It is best to have the chimney inspected by a professional Make certain the chimney is cleaned prior to installation of this replace The size of the chimney should be between 36 and 96 squ...

Page 7: ...air reg ister in the vicinity of the unit would be acceptable Combustion air must be supplied in conformance with the Uniform Mechanical Code 6 CAUTION NEVERUSEGASOLINE GASOLINE TYPE LANTERN FUEL KER...

Page 8: ...t should be removed to reduce the chance of a chimney re HOW TO REMOVE CREOSOTE 1 Clean the chimney with brushes and equipment avail able at local replace shops 2 Chemical chimney cleaners are used by...

Page 9: ...d eau dans le m lange peut provoquer le r fractaire casser trop et permettra de r duire la force du r fractaire Pour tester la teneur en eau propre couper verticalement dans le m lange la truelle pou...

Page 10: ...un jeu de 1 8 au poste de porte gauche serrer les vis dans les charni res parfaitement NE PAS TROP SERRER Re ajuster si n cessaire pour un bon alignement 6 Notez que deux panneaux ont mat riau d tanch...

Page 11: ...sure est de 1143mm de la paroi arri re et 1143mm la paroi lat rale Voir gure 1 page 2 Pour coin l installation du centre de la chemin e est de 1143mm Voir la gure 2 page 2 D gagement des Non Combustib...

Page 12: ...met du tuyau Le connecteur de glissement a un air au sommet avec les 3 trous Le fond est lisse La section de tuyau de d part a airings aux deux extr mit s L extr mit m le est toujours au fond Simpson...

Page 13: ...JAMAIS PASSER PAR UN COMBUSTIBLE DU PLAFOND OU AU MUR premi re vue vous pouvez devenir pr occup s que de la fum e s chapper du tuyau et entrer dans la salle Cela ne veut pas comment le syst me va fonc...

Page 14: ...able d avoir la chemin e inspect par un professionnel Assurez vous que la chemin e est nettoy e avant l installation de ce foyer La taille de la chemin e doit tre comprise entre 36 et 96 pouces carr s...

Page 15: ...registre d air dans le voisinage de l unit il est acceptable L air de combustion doit tre fournie en conformit avec le Code m canique uniforme 6 ATTENTION NE JAMAIS UTILISER D ESSENCE type essence LAN...

Page 16: ...r osote est ac cumul e elle doit tre enlev e pour r duire le risque d un feu de chemin e COMMENT SUPPRIMER CR OSOTE 1 Nettoyez la chemin e avec des brosses et quipements disponibles dans les magasins...

Reviews: