Dimensions de foyer indiquées sont des exigences minimales. Il peut être souhaitable de exceede ces dimen-
sions minimales pour une installation plus décoratif. 

PAROI LATÉRALE ET BACKWALL INSTALLATION

Unit to Sidewall ------------------------------------------ 610mm
Unit to Backwall ----------------------------------------- 610mm
Connector to Sidewall --------------------------------1041mm
Center of Connector to Sidewall ------------------- 1143mm
Connector to Backwall --------------------------------1041mm
Center of connector to Backwall ------------------- 1143mm

1041

610

610

1041

Figure 2.

Figure 1.

CORNER INSTALLATION

Unit to Adjacent Walll ----------------------------------- 610mm
Connector to Adjacent Wall ------------------------- 1041mm
Center of Connector to Adjacent Wall -------------1143mm
Minimum Hearth Size ------------------ 1219mm x 1372mm
Or a Diameter of --------------------------------------- 1372mm

Système de 

Cheminée.

Connecteur de 

Tuyaux

Unité

Dégagements aux Combustibles

The Imperial nécessite une autorisation de murs combustibles 
de 610mm mesurées à l'arrière de l'appareil. Pour localiser le 
centre de la cheminée de la mesure est de 1143mm de la paroi 
arrière et 1143mm à la paroi latérale . Voir fi gure 1, page 2. Pour 
coin l'installation du centre de la cheminée est de 1143mm . 
Voir la fi gure 2 , page 2 .

Dégagement à des Non-Combustibles

La clairance Imperial à un mur combustible peut être réduite 
avec une protection adéquate de la paroi . Méthodes accep-
tées pour la protection de la paroi permettraient la réduction 
des dégagements . Pour l'apparence , si vous le souhaitez 
un revêtement mural peut non combustible placé sur le mur 
. Le revêtement devrait être composé d'un conseil de protec-
tion de la paroi cotée installé aux spécifi cations du fabricant 
. Panneaux de protection approuvés au moment de cette 
publication sont Wonderboard , Dura Rock and Homosote . 
Un matériau non-combustible peut ensuite être placé sur le 
panneau de protection de mur. Avec la plupart des panneaux 
de protection contre le jeu peut être reducedby 2/3 du mur 
combustible d'origine. Soyez certain de vérifi er auprès de vos 
responsables locaux de construction et ou inspecteur des 
incendies de méthodes acceptées dans votre région .

Summary of Contents for Imperial Carousel

Page 1: ...ry mixture to much water in the mix may cause the refractory to crack excessively and will reduce the strength of the refrac tory To test for proper water content cut vertically into the mixture with...

Page 2: ...the screws in the hinges snug ly DO NOT OVER TIGHTEN Re adjust as necessary for proper alignment 6 Note that two panels have gasket material on one edge These pieces go on either side of the door Make...

Page 3: ...the chimney the measurement is 45 from the backwall and 45 to the sidewall See gure 1 page 2 For corner installation the center of the chimney is 45 See gure 2 page 2 Clearance to Non combustibles The...

Page 4: ...ter pipe section has airings at both ends The male end is always at the bottom Simpson Dura Vent Chimney System It is required to use a Dura Vent Universal Connector part number 8DVL ADC or 8878 Adapt...

Page 5: ...e the pipe and enter the room This is not how the system will work The vacum in the chimney system will always pull air into the chim ney If you experience a downdraft with your installation it indica...

Page 6: ...terioration It is best to have the chimney inspected by a professional Make certain the chimney is cleaned prior to installation of this replace The size of the chimney should be between 36 and 96 squ...

Page 7: ...air reg ister in the vicinity of the unit would be acceptable Combustion air must be supplied in conformance with the Uniform Mechanical Code 6 CAUTION NEVERUSEGASOLINE GASOLINE TYPE LANTERN FUEL KER...

Page 8: ...t should be removed to reduce the chance of a chimney re HOW TO REMOVE CREOSOTE 1 Clean the chimney with brushes and equipment avail able at local replace shops 2 Chemical chimney cleaners are used by...

Page 9: ...d eau dans le m lange peut provoquer le r fractaire casser trop et permettra de r duire la force du r fractaire Pour tester la teneur en eau propre couper verticalement dans le m lange la truelle pou...

Page 10: ...un jeu de 1 8 au poste de porte gauche serrer les vis dans les charni res parfaitement NE PAS TROP SERRER Re ajuster si n cessaire pour un bon alignement 6 Notez que deux panneaux ont mat riau d tanch...

Page 11: ...sure est de 1143mm de la paroi arri re et 1143mm la paroi lat rale Voir gure 1 page 2 Pour coin l installation du centre de la chemin e est de 1143mm Voir la gure 2 page 2 D gagement des Non Combustib...

Page 12: ...met du tuyau Le connecteur de glissement a un air au sommet avec les 3 trous Le fond est lisse La section de tuyau de d part a airings aux deux extr mit s L extr mit m le est toujours au fond Simpson...

Page 13: ...JAMAIS PASSER PAR UN COMBUSTIBLE DU PLAFOND OU AU MUR premi re vue vous pouvez devenir pr occup s que de la fum e s chapper du tuyau et entrer dans la salle Cela ne veut pas comment le syst me va fonc...

Page 14: ...able d avoir la chemin e inspect par un professionnel Assurez vous que la chemin e est nettoy e avant l installation de ce foyer La taille de la chemin e doit tre comprise entre 36 et 96 pouces carr s...

Page 15: ...registre d air dans le voisinage de l unit il est acceptable L air de combustion doit tre fournie en conformit avec le Code m canique uniforme 6 ATTENTION NE JAMAIS UTILISER D ESSENCE type essence LAN...

Page 16: ...r osote est ac cumul e elle doit tre enlev e pour r duire le risque d un feu de chemin e COMMENT SUPPRIMER CR OSOTE 1 Nettoyez la chemin e avec des brosses et quipements disponibles dans les magasins...

Reviews: