Side Wall Protection

Adjacent combustible side walls that are within mini-
mum dimensions shown in Figure 23 of the fireplace 
opening  must be protected with CFM Corporation Wall 
Shield Model SP40 or a specifically built wall shield 
described in Figure 20.
The special wall shield design described in Figure 20 is 
an alternate method of adding protection to side walls 
and can be used in place of the SP40 with the same 
wall clearances specified for the SP40. Rt must =1.85 
minimum.

Examples of wall shield insulation:

1.  Manville - CERAFORM 126, K=.27, 
  1/2 inches thick
2.  CFM Corporation - EH2416, K = .458, 
  1 inch thick required.

Hearth Installation

A hearth extension is required to protect a combustible 
floor in front of the fireplace. Refer to Figure 23 for mini-
mum dimensions and mounting detail.

NOTE:  Hearth Extension must not cover the air 
inlet opening of a fireplace.

The hearth extension described in Figure 23 must be a 
durable noncombustible material with a minimum (total) 
Rt value of 1.09; see Figure 24 for examples. The over-
all height (above a combustible floor), depth and width 
must be as indicated, with the extension centered to the 
fireplace opening.
The top of insulation must be covered with a noncom-
bustible decorative covering 

or

 a piece of .018” mini-

mum sheet metal, to protect hearth extension material.  
(Fig. 23)
Secure the hearth extension to the floor to prevent 
shifting, using trim molding or other similar means at 
three (3) outer edges. Seal crack between the fireplace 
hearth and hearth extension with a noncombustible 
material.  (Figs. 23 and 25)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the 

fireplace

and hearth

extension with

noncombustible

material

Safety strips 

must overlap 

���

" minimum

May install 

noncombustible 

decorative 

covering

OR

 .018" min. 

sheet metal

Fireplace 

Hearth

Combustible 

Floor

Minimum 

Insulation 

Value "R"

4" MIN.

FP594
SR/SC
11/20/97

Firebox

Opening

A -

 Min. clearance 

to combustible

perpendicular wall

B -

 Min. clearance 

to combustible

perpendicular wall when

using noncombustible wall shield*

Side

Wall

Side

Wall

F

**

C

**

E

E

D

4" Brick

(Example material)

Combustible material permitted within shaded area.  

 * Noncombustible wall shield requires 1" CFM Corporation 

    EH2416 insulation (minimum R Value = 1.85) between 

    decorative noncombustible rigid covering and combustible wall.  

    Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness 

    of noncombustible surround facing.

4"

Shaded area starts

1/2" away from 

edge of unit

FP594

Fig. 23  

 Combustible side wall protection and hearth extension dimensions.

   

J

  BR/BC36 

16" 

12" 

48° 

41° 

18" 

14" 

9" 

16" 

48" 

   

406 mm  305 mm 

 

 

457 mm  356 mm  229 mm  406 mm  1219 mm

  BR/BC42 

20" 

12" 

42° 

35° 

18" 

14" 

12" 

20" 

61

¹⁄₂

   

508 mm  305 mm 

 

 

457 mm  356 mm  305 mm  508 mm  1562 mm

Summary of Contents for Royalton BC36

Page 1: ...Woodburning Fireplace For Models BR36 BR42 BC36 BC42 DO NOT DISCARD THIS MANUAL Retain for future use 7412944 12 06 Rev 19 For use in U S Canada Underwriter s Laboratories Report No MH6018 Homeowner...

Page 2: ...se of any component part not manufactured or approved by CFM Corpo ration in combination or assembly with a Majes tic Fireplaces replace system notwithstanding any independent testing laboratory or ot...

Page 3: ...1041mm 8 Dia 203mm 8 2 2 m m If elbows are offset to the back of the unit chase depth will be 22 575mm Fig 2 BC36 Series speci cations and framing BC36 Series Woodburning Fireplace Circulating Model 1...

Page 4: ...Air Gas Line Access Electrical Access 1194mm 8 Dia 203mm 8 9 5 m m If elbows are offset to the back of the unit chase depth will be 22 575mm BR42 Series Woodburning Fireplace Fig 3 BR42 Series speci c...

Page 5: ...Collar Pan Flashing Draftstop Standoff Surround Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Outside Air Cover Plate Electrical Access Gas Line...

Page 6: ...42 Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a structu...

Page 7: ...nning a chimney system it is important to know 1 The height of a chimney is measured from the hearth to the exit point on the termination 2 A chimney cannot be offset more than 30 from a vertical plan...

Page 8: ...location or how the chimney system should be run contact your Majes tic Fireplaces dealer for assistance If you live in a cold climate it is not required but highly recommended that you insulate repl...

Page 9: ...kit Remove knockout in the center of the back of the EB1 and install listed cable clamps Feed electrical wire through listed cable clamp leaving approximately 6 152 mm of wire exposed through the EB1...

Page 10: ...requirement at attic level Offset Installation In order to clear an obstruction it may be necessary to offset chimney from vertical This is accomplished by using CFM Corporation elbows Use the 30 Offs...

Page 11: ...ls strips provided with the replace Note Safety strips are not required over noncombusti ble oors where all supports at the base of the replace are noncombustible Four 4 nailing anges are supplied wit...

Page 12: ...de minimum required air space to chimney pipe for ceiling thickness up to 8 203mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be mad...

Page 13: ...additional ceilings repeat same steps required for rst ceiling installation See restop illus tration on Page 12 Figure 18 Penetrating the Roof Run pipe to roo ine Since chimney system must be vented...

Page 14: ...he wall with material of your choice Do not install a combustible mantel shelf less than 12 305mm from the top of the replace opening for radiant models and 12 305mm from top of grille opening for cir...

Page 15: ...2 305mm Min 1 38mm 6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Standoff N...

Page 16: ...ecure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension with a noncombusti...

Page 17: ...inch Units of K BTU SQ FT HR F IN Thickness of Listed Material FP533ADD Addendum 6 1 99 djt 8 4 99 changed 2 to 1 one inch to 1 2 inch djt FP533ADD Fig 24 Hearth extension material factors FP550 Fig 2...

Page 18: ...ll chisel and hammer carefully tap around the knockout until it loosens and falls out Install 1 2 inch certi ed gas pipe through opening After gas pipe installation is complete use insulation that was...

Page 19: ...03 or 20007494 3032103 or 20007496 6b Firebrick Rear 3030102 or 20007495 3032102 or 20007497 6c Firebrick Rt Side 3030160 or 20007492 3030160 or 20007492 6d Firebrick Lt Side 3030104 or 20007493 30301...

Page 20: ...provided by the owner s insurance Accessories Contact your Majestic Fireplaces distributor or dealer for nishing Marble and Mantels available in a wide selection of styles Glass Door Standard Bi Fold...

Page 21: ...himney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low pro le pyramid sty...

Page 22: ...ion Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 Chim...

Page 23: ...s extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructions fu...

Page 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: