11

Majestic Fireplaces

®

 BR/BC Series 

7412944

The following table gives firestop spacer model num-
bers:

The 

inside dimension

 of the frame 

must be 

the same 

as the hole size selected from Figure 13 in order to 
provide the required 1

¹⁄₂

" (38 mm) of air space between 

the outside diameter of the chimney and the edges of 
the framed ceiling hole.

Positioning, Safety Strips, 

Securing the Fireplace

Slide fireplace into position.
Lift the fireplace front slightly and slide the metal safety 
strips under front bottom edge about 1

¹⁄₂

" (38 mm), al-

lowing the remainder to extend in front of firebox. Over-
lap strips at least 1/2" (13 mm) to provide a positive 
joint. (Flat safety strips are packed with fireplace.)  (Fig. 14) 
Safety strips are used to ensure that any combustible 
materials in front of the fireplace are protected even 
though a noncombustible hearth extension is required.
If fireplace is to be elevated above the floor, a “Z” 
shaped metal safety strip must be fabricated and used 
to protect combustible surfaces in front of the fireplace.  
This “Z” shaped safety strip is not provided but must be 
fabricated of metal with each horizontal leg at least 1

¹⁄₂

(38mm) wide and equal in length to the metals strips 
provided with the fireplace.

Note:  

Safety strips are not required over noncombusti-

ble floors where all supports at the base of the fireplace 
are noncombustible.
Four (4) nailing flanges are supplied with the fireplace 
(found on the fireplace hearth). To level the box and 
secure it firmly in place, remove the nailing flanges from 
the hearth and install at the sides of the fireplace as 
shown in Figure 15.

Installing Outside Air Kit

An outside air kit is installed in all BR/BC Series Fire-
places. If desired, or if local codes mandate the use of 
an air kit, then an AK-MST is required to complete the 
installation (from air kit to the outdoors). If the outside 
air kit is to be used, the AK-MST 

MUST

 be installed 

BE-

FORE

 the fireplace is enclosed. Refer to the AK-MST 

instructions for field installation. 

FP549

Fig. 15

  Fasten fireplace in position.

FP549

9/29/97

BR/BC

Nail Top 

Standoffs

Nail Side-

Nailing 

Flanges

Fig. 13

 Ceiling chimney hole sizes necessary for installing 

firestop spacer.

  Size of Chimney 

Vertical 

30°

 

8" Flue 

SKFS2A 

SKFS6A

 

"SK" Series 

14

¹⁄₂

" x 14

¹⁄₂

14

¹⁄₂

" x 25

¹⁄₂

"

 

 

(368 mm x 368 mm) (368 mm x 648 mm)

 

8" Flue 

FS2A 

FS6A

  "S" Series 3-Wall 

17

¹⁄₂

" x 17

¹⁄₂

17

⁷⁄₈

" x 29

⁵⁄₈

"

 

 

(445 mm x 445 mm) (454 mm x 753 mm)

 

Angle of Chimney at Ceiling

WF557

BR

11/10/97

���

" (13mm)

Min. Overlap

����

"

(38mm)

"Z" 

Safety 

Strip

Fire-

Place

Plat-

Form

Hearth Ext.

(not supplied)

FP557

Fig. 14

  Safety strip installation.

Metal Safety Strip

(1,2 or 3 pieces)

Summary of Contents for Royalton BC36

Page 1: ...Woodburning Fireplace For Models BR36 BR42 BC36 BC42 DO NOT DISCARD THIS MANUAL Retain for future use 7412944 12 06 Rev 19 For use in U S Canada Underwriter s Laboratories Report No MH6018 Homeowner...

Page 2: ...se of any component part not manufactured or approved by CFM Corpo ration in combination or assembly with a Majes tic Fireplaces replace system notwithstanding any independent testing laboratory or ot...

Page 3: ...1041mm 8 Dia 203mm 8 2 2 m m If elbows are offset to the back of the unit chase depth will be 22 575mm Fig 2 BC36 Series speci cations and framing BC36 Series Woodburning Fireplace Circulating Model 1...

Page 4: ...Air Gas Line Access Electrical Access 1194mm 8 Dia 203mm 8 9 5 m m If elbows are offset to the back of the unit chase depth will be 22 575mm BR42 Series Woodburning Fireplace Fig 3 BR42 Series speci c...

Page 5: ...Collar Pan Flashing Draftstop Standoff Surround Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Outside Air Cover Plate Electrical Access Gas Line...

Page 6: ...42 Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a structu...

Page 7: ...nning a chimney system it is important to know 1 The height of a chimney is measured from the hearth to the exit point on the termination 2 A chimney cannot be offset more than 30 from a vertical plan...

Page 8: ...location or how the chimney system should be run contact your Majes tic Fireplaces dealer for assistance If you live in a cold climate it is not required but highly recommended that you insulate repl...

Page 9: ...kit Remove knockout in the center of the back of the EB1 and install listed cable clamps Feed electrical wire through listed cable clamp leaving approximately 6 152 mm of wire exposed through the EB1...

Page 10: ...requirement at attic level Offset Installation In order to clear an obstruction it may be necessary to offset chimney from vertical This is accomplished by using CFM Corporation elbows Use the 30 Offs...

Page 11: ...ls strips provided with the replace Note Safety strips are not required over noncombusti ble oors where all supports at the base of the replace are noncombustible Four 4 nailing anges are supplied wit...

Page 12: ...de minimum required air space to chimney pipe for ceiling thickness up to 8 203mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be mad...

Page 13: ...additional ceilings repeat same steps required for rst ceiling installation See restop illus tration on Page 12 Figure 18 Penetrating the Roof Run pipe to roo ine Since chimney system must be vented...

Page 14: ...he wall with material of your choice Do not install a combustible mantel shelf less than 12 305mm from the top of the replace opening for radiant models and 12 305mm from top of grille opening for cir...

Page 15: ...2 305mm Min 1 38mm 6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Standoff N...

Page 16: ...ecure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension with a noncombusti...

Page 17: ...inch Units of K BTU SQ FT HR F IN Thickness of Listed Material FP533ADD Addendum 6 1 99 djt 8 4 99 changed 2 to 1 one inch to 1 2 inch djt FP533ADD Fig 24 Hearth extension material factors FP550 Fig 2...

Page 18: ...ll chisel and hammer carefully tap around the knockout until it loosens and falls out Install 1 2 inch certi ed gas pipe through opening After gas pipe installation is complete use insulation that was...

Page 19: ...03 or 20007494 3032103 or 20007496 6b Firebrick Rear 3030102 or 20007495 3032102 or 20007497 6c Firebrick Rt Side 3030160 or 20007492 3030160 or 20007492 6d Firebrick Lt Side 3030104 or 20007493 30301...

Page 20: ...provided by the owner s insurance Accessories Contact your Majestic Fireplaces distributor or dealer for nishing Marble and Mantels available in a wide selection of styles Glass Door Standard Bi Fold...

Page 21: ...himney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low pro le pyramid sty...

Page 22: ...ion Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 Chim...

Page 23: ...s extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructions fu...

Page 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: