10
DVRTSB Bay Window Fireplace
10003848
General Venting Information – Termination Location
Your fireplace is approved to be vented either through
the rear wall or the vertical side wall, or vertical through
the roof.
•
Only venting components specifically approved and
labeled for this fireplace may be used.
•
Venting terminals shall not be recessed into a wall or
siding.
•
Horizontal venting must be installed on a level plane
without any incline or decline.
There must not be any obstruction such as bushes, gar-
den sheds, fences, decks or utility buildings within 24”
from the front of the termination hood.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on this page.
*Check with local codes or in absence of same with
CSAB149.1 Installation Codes (1991) for Canada or fol-
low the current National Fuel Gas Code, ANSIZ223.1/
NFPA 54 for installations in the USA.