Doc.2016002
CX300 MODULE – User manual
-23-
8.4.
SPEED MEASUREMENT
Table 7
Configuration
Description
Show Unit
Speed show unit. Can be: RPM or Hz
Scale
Scale value, from selection: 200 to 20000 (in
Show Unit
)
Alarm speed
Enable/Disable alarm.
Trigger measurement alarm condition.
Warning Speed
Warning level for speed (in
Show Unit
)
Danger Speed
Danger level for speed (in
Show Unit
)
Map Warning Speed Map speed Warning Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4
Map Danger Speed
Map speed Danger Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4
Before doing any change, just make sure that the machine is not running!
The manufacturer is not responsible for any damages caused by improper
settings. Modification should be conducted by qualified personnel. During
setting modification, all the available safety requirements should be
considered.
NOTE:
The four current outputs (4 to 20 mA) are available only for Total Vibration value. By
request, additional four current outputs can be equipped for
Temperature
measurements, but two
relays (RLY3 and RLY4) will be removed (only RLY1 and RLY2 will be available).
In the above configuration, a part of the terminals table (Table 2) must be changed as shown
below (Table 8):
Table 8 -Modified terminals assignment
Terminal label
Description
48
OUT5 (mA) - positive
49
OUT5/6 COM - negative
50
OUT6 (mA) - positive
51
OUT7 (mA) - positive
52
OUT7/8 COM - negative
53
OUT8 (mA) - positive
Summary of Contents for CX300