6.0 MONITORING PLC CYCLE
•
Press ESC button on the Mini PLC
•
Press the
⇓
arrow to the Set Param line.
•
Press OK button. Main counter B1 should display with Cnt value at bottom of the screen
•
Cnt value represents current count in minutes for the total cycle. If counter B1 fails to display,
press
⇓
or
⇑
arrows until B1 displays with Cnt value.
•
To fast cycle advance counter B1 connect the 115V hot wire to PLC input I2.
•
Check schematic diagram for wires numbers to jump for fast cycle advance. Each
1 minute count becomes 1 second in the fast advance mode.
•
On initial start fast advance B1 counter to 0 or 1 counter value. Reference the chart below for
sequence of operation.
6.1 8- Hour Sequence of Operation
Time
Counter, B1
8 Hour Cycle
0 Hour, 0 Minute
0
Bed shift, left bed drying, overtemp alarm inactive.
0 Hour, 1 Minute
1
Right bed regen heater on.
0 Hour, 20 Minute
20
Overtemp alarm active.
1 Hour, 37 Minute
97
Right bed regen cooling, regen heater off.
4 Hour, 0 Minute
240
Bed shift, right bed drying, overtemp alarm inactive
4 Hour, 1 Minute
241
Left bed regen heater on.
4 Hour, 20 Minute
260
Overtemp alarm active.
5 Hour, 37 Minute
337
Left bed regen cooling, regen heater off.
8 Hour, 0 Minute
480
Bed shift, left bed drying.
6.2 PLC Counter Settings
Counter
ON Value
OFF Value
Description
B1
480
0
Cycle reset
B3
0
240
Bed shift
B4
241
337
Left bed regen heater
B5
1
97
Right bed regen heater
B7
240
260
Right bed drying alarm delay
B8
0
20
Left bed drying alarm delay