The next screen gives the user 
a choice to set the 4mA or 20mA 
values or to Exit the procedure.  
Here the user will select the 4mA 
menu position.

The HART Communicator requests 
the user to set the Level (or 
Interface) to the position that is 
to provide the 4mA loop current 
output.  When that has been done, 
the user must press OK to continue 
with the procedure

.

The HART Communicator then 
requests a measurement reading 
from the transmitter indicating 
the digital value at this range 
position.  The user then has the 
option of setting this value as 
the lower range value, getting an 
update of the digital reading from 
the transmitter or leaving the 4mA 
range point as it was.

If the user accepts the 
measurement value as the 
4mA loop current point, the 
HART Communicator issues the 
command changing the LRV 
and when the transmitter replies, 
returns to the Set screen.

If the user desires to change the 
20mA measurement value, he 
selects the 20mA menu option and 
must press ENTER to continue the 
procedure. 

The HART Communicator requests 
the user to set the Level (or 
Interface) to the position that is 
to provide the 20mA loop current 
output.  When that has been done, 
the user must press OK to continue 
with the procedure.

The HART Communicator then 
requests a measurement reading 
from the transmitter indicating the 
digital value at this range position.  
The user then has the option of 
setting this value as the upper 
range value, getting an update 
of the digital reading from the 
transmitter or leaving the 20mA 
range point as it was.

If the user accepts the 
measurement value as the 
20mA loop current point, the 
HART Communicator issues the 
command changing the URV 
and when the transmitter replies, 
returns to the Set screen

When the user desires to leave the 
Apply values procedure, he must 
select the Exit menu entry.

The user is then notified that 
the loop may now be returned 
to automatic control.  After the 
user presses OK the HART 
Communicator returns to the 
Rerange screen.

Detailed Setup Selections

In the Overview section, it was 
shown that if the user selects the 
Detailed setup menu from the 
Device setup screen, the following 
screen presents the following 
selection of menus to the user.

If the user selects Sensors from the 
Detailed setup screen, he may edit 
the Unit code for Level/Interface or 
edit the units code for Temperature.  
The third option is a menu Sensor 
Trim that gives the user additional 
selections.

If the user selects Sensor Trim 
from the Sensors menu, calibration 
procedure options are presented.  If 
the transmitter is not configured for 
Temperature, the Zero Temper Trim 
and Full Temper Trim options will 
not be presented.  The description 
of these procedures is given in the 
previous section on Calibration.

If the user selects Signal Condition 
from the Detailed setup screen, he 
is presented with three additional 
selections.  The Keypad rerange 
and Apply values procedures are 
presented in the Rerange section.  
The third option allows the user to 
modify the Level/Interface damping 
factor.

17

Summary of Contents for LTM-300 Series

Page 1: ...81 488 0788 FAX 281 488 7080 EMAIL magtech isemagtech com www isemagtech com LTM 300 Series Magnetostrictive Level Transmitter Instruction Operation Manual 3902 Magnolia Road Pearland Texas 77584 Jan...

Page 2: ...r Installation 3 3 1 Standalone Transmitter Installation 3 3 2 Recommended Wiring Single Loop 4 Section 4 Speci cations Page 4 0 Transmitter Electrical Speci cations 4 4 1 Transmitter Sensor Tube 4 Se...

Page 3: ...hange and continuously activates the sensor in the tube The electronics in the housing process the changing signal and update an analog 4 20 mA output This analog output is precisely proportional to t...

Page 4: ...e base to resolve sub microsecond timing increments The binary number equivalent to the microseconds of the echo travel time is written to an output D A Converter and subsequently converted to a 4 20...

Page 5: ...ectronicshousingmountedatthebottomofthegageforeasyaccess THIS MUST BE SPECIFIED AT TIME OF PURCHASE Installation Note European The cable entry devices and blanking elements of unused apertures shall b...

Page 6: ...gurations A single output version with only one variable that will output a 4 20 mA signal for level The second con guration is a transmitter tted with a second oat to provide a digital output for in...

Page 7: ...elect Data not required Span Trim Move the oat to the 20mA mark 100 on the probe Using the arrow buttons input the correct distance from the zero point and then Select Level O set Enter the desired va...

Page 8: ...ion Problems 6 2 Magnetic Interface 6 3Troubleshooting Power Supply Problems Never move a magnet in a perpendicular motion from along the sensor tube This will always leave a residual eld in the waveg...

Page 9: ...as this could leave magnetic indentation in the sensor wire The LTM 300 level transmitter has an inductor located inside the bulkhead of the sensor tube During operation of the transmitter this induc...

Page 10: ...d the Alarm type In addition this screen presents the procedure to select the Primary variable PV if the transmitter is con gured with both Level and Interface It also displays the menu that will allo...

Page 11: ...t are not normal Any status items not reported are within the normal range of operation or calibration The HART Communicator issues a command to receive the results of the transmitter diagnostics Duri...

Page 12: ...xited if the user selects End The example shows the user selection 4mA The user must press ENTER before the procedure continues When the user selects the Loop test option the HART Communicator display...

Page 13: ...output to 4 000mA the user is to enter the reference meter reading For example if the meter actually reads 4 234mA that value is input with the keypad The user must press ENTER when the current value...

Page 14: ...matic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Zero Level Trim Full Level Trim Starting at...

Page 15: ...now be returned to automatic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Full Level Trim Zero...

Page 16: ...ed Once the measurement is stable the procedure will continue without user intervention The HART communicator will then send the command to the transmitter to calculate the new Temperature zero calibr...

Page 17: ...t Value for 4mA and 20mA by Keypad If you desire to change the Level value at which the Current output is 4mA and 20mA when the Level is the selected Primary Variable or change the Interface value at...

Page 18: ...g the edit box to continue with the reranging of the transmitter On returning to the Keypad rerange screen the values shown for LRV and URV are the changes that the user has made The user should check...

Page 19: ...pper range value getting an update of the digital reading from the transmitter or leaving the 20mA range point as it was If the user accepts the measurement value as the 20mA loop current point the HA...

Page 20: ...h is set in the factory when the unit is prepared for shipment The probe length is used as a reference for a number of diagnostics fuctions as well as setting the URL and LRL shown on the Keypad reran...

Reviews: